Mircom BPS-602 Remote Power Supply Owner’s Manual
- June 9, 2024
- Mircom
Table of Contents
Mircom BPS-602 Remote Power Supply
Description
Mircom’s BPS-602 is an extremely cost effective 6.5 amp voltage regulated
remote power supply/battery charger. It may be connected to any 12 or 24 volt
Fire Alarm Control Panel (FACP). Primary applications include Notifi cation
Appliance Circuit (NAC such as strobes and horns) expansion support to meet
ADA requirements. It also provides auxiliary power to support system
accessories. The unit delivers regulated and fi ltered 24 or 12 volt power to
Class B or Class A NAC loop circuits. Additionally, a separate 1.0A auxiliary
output with reset for four (4)-wire smoke detectors is available. The 6.5 amp
rated supply current can be divided between the four (4) outputs for powering
NAC devices. Each output is rated at 2.5 amp max., and can be independently
programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs
may be programmed for Input to Output Follower Mode (output will follow input.
i.e. March Time Input, March Time Output). An individual output of 4 amp is
achieved by paralleling 2 outputs.
The BPS-602 in non-alarm condition independent loop supervision for Class A
and/or Class B FACP NAC circuits is provided. In the event of a loop trouble
the FACP will be notifi ed via the steered input (input 1 or input 2). In
addition, there are common trouble output terminals (N.C., C, N.O.) which are
used to indicate general loop/system trouble. A common trouble input is
provided for optional NC (normally closed) devices to report trouble to the
FACP. Two (2) FACP signaling outputs can be employed and directed to control
supervision and power delivery to any combination of the four (4) outputs. The
unit also features “Loop Output” trouble memory indication to help identify
trouble some sporatic problems.
Features
- Power input 115VAC 60 Hz, 1.45 amp.
- Two (2) Class A or two (2) Class B FACP inputs
- Field selectable 24VDC or 12VDC voltage regulated power limited outputs
- 24VDC or 12VDC rated @ 6.5 amp max total alarm current
- 2.5 amp max current per output
- Separate 1 Amp auxiliary output with built-in and remote reset capability
- Two (2) outputs may be paralleled for more power on an indicating circuit
- Programmable supervised indicating circuit outputs: Up to Four (4) Class B or Two (2) Class A or One (1)
- Class A and Two (2) Class BThermal and short circuit protection with auto reset
- Built-in charger for sealed lead acid or gel type batteries
- Automatic switchover to stand-by battery when AC Fails
- Zero voltage drop when switching over to battery backup
- PTC battery protection
- AC fail supervision (form “C” contact, 1 amp / 28VDC). Factory set for 1 minute with optional 18 hour delay setting (fi eld selectable)
- Battery presence and low battery supervision (form “C” contact, 1 amp / 28VDC)
- Input and output status LED indicators
- 2 wire horn/strobe Sync mode allows audible notifi cation appliances (horns) to be silenced while visual notifi cation appliances (strobes) continue to operate
- Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notifi cation appliances circuit)
- Horn/Strobe sync protocols include Mircom, Amseco, Gentex, System Sensor, Faraday and Wheelock
- March Time
- Compatible with 12 or 24VDC fi re panels.
- Filtered and electronically regulated output
- Output loop supervision steered to input 1 or input 2
- Common trouble input and output
- Ground fault detection
- Unit includes power supply, red enclosure, cam lock, open frame transformer and battery leads
Power Supply Specifi cations
AC Input | 115VAC / 1.45 amp @ 60Hz |
---|---|
Output | 12 – 24VDC. Maximum 2.5 amp per output Total of 6.5 amp in Alarm |
Condition
Battery| For 12VDC operation use a 12VDC / 12AH battery
For 24VDC operation use two (2) 12VDC / 12AH or two (2) 12VDC / 7AH batteries connected in series
Stand-by/Alarm Current:| 75mA/150mA
EOL Resistor (end of line)| 2.2K (2200 ohm)
Standby Specifications
Standby Batteries| Standby Time| Alarm Output Total
Amp/Minutes| Aux Output Current
---|---|---|---
24VDC/12AH
(use two (2) 12VDC batteries in series)
| 24 Hours| 6.5 amp/15 Minutes| 50mA
60 Hours| 6.5 amp/5 Minutes| –
24VDC/7AH| 24 Hours| 6.5 amp/5 Minutes| –
12VDC/12AH| 24 Hours| 6.5 amp/15 Minutes| 50mA
60 Hours| 6.5 amp/5 Minutes| –
24VDC/36AH Battery| 24 Hours| 6.5 amp/15 Minutes| 1 amp
12VDC/36AH Battery| 24 Hours| 6.5 amp/15 Minutes| 1 amp
Enclosure Dimensions
15.5”H x 12”W x 4.5”D
Ordering Information
Model | Description |
---|---|
BPS-602 | 6.5 Amp Remote Power Supply |
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Toll Free: 888-660-4655 Fax Toll Free:
888-660-4113
Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone:
905-660-4655 Fax:
905-660-4113
Web page: http://www.mircom.com
Email: mail@mircom.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>