LT-698 QX-5000 Mass. Code Upgrade Instruction Rev. 2
1. To prepare QIF-5000 hardware:
1.1. Remove U22 and replace with IC SF-179.
2. To prepare QDV-1000 hardware:
2.1. Remove U3 and replace with SF-180A.
2.2. Remove U7 and replace with SF-180B.
2.3. Connect QDV-1000 TS1, pin 1 to QIF-5000 J4, pin2.
2.4. Connect QDV-1000 TS1, pin 2 to QIF-5000 J4, pin
1. 3. Additional configuration:
3.1. Set rotary switches to 9 and 7.
3.2. From the Audio Configuration Utility, click QDV-1000 tap to open the following window.
Mircom LT-698 QX-5000 Voice Evacuation System - fig 1 3.3. Double click `Channel 2′ to bring up the following window and enter the parameters as shown.
Mircom LT-698 QX-5000 Voice Evacuation System - fig 33.4. Make sure the All Evacuation is not checked.
Mircom LT-698 QX-5000 Voice Evacuation System - fig 23.5. Carry on configuring the rest of the audio system.
3.6. Download to QIF-5000.
3.7. Change rotary switches back 00.