SENSERT SST-RBM1XX Remote I or O Monitoring and Alert System Instruction Manual

June 9, 2024
SENSERT

SENSERT SST-RBM1XX Remote I or O Monitoring and Alert System
LOGO

SENSERT SST-RBM1XX Remote I or O Monitoring and Alert System

SENSERT SST-RBM1XX Remote I or O Monitoring and Alert System
PRODUCT

Product Name: SENSERT Remote I/O
Model No.: SST-RBM1XX
Manufacturer: Automatic Timing and Controls Diversified Electronics
Address of Manufacturer: 8019 Ohio River Blvd, PO Box 305, Newell, WV 26050 USA

SENSERT Remote I/O Unit Specifications

SENSERT SST-RBM1XX Remote I or O Monitoring and Alert System
01

FCC statement

This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:

  1.  This device may not cause interference.
  2.  This device must accept any interference, including interference that may cause undesired operation of the device.

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
FCC Radiation Exposure Statement This device complies with FCC RF radiation exposure limits set forth for an uncontrolled environment. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter. This device must operate with a minimum distance of 20 cm between the radiator and user body.

SENSERT REMOTE I/O Unit Diagram
SENSERT SST-RBM1XX Remote I or O Monitoring and Alert System
02 Powering SENSERT
SENSERT is able to be powered 5-30 V DC. See diagram below.
The 4-20 mA input from the sensor cannot be floating with the power supply that is used for the SENSERT Remote I/O Unit. The max common mode voltage of the AI +/- to the GND of DC power must be 0- 24 V. The floating 4-20 mA AI input might damage the SENSERT Remote I/O Unit.

Option 1:4-20mA 3/4 wire sensor
SENSERT SST-RBM1XX Remote I or O Monitoring and Alert System
03 Option 2:4-20mA 2-wire sensor
SENSERT SST-RBM1XX Remote I or O Monitoring and Alert System
04

Connecting to Bluetooth

Download the SENSERT Mobile App available in the Google Play or Apple App Store and log in using the credentials you used to register your account. After logging into your new SENSERT account, navigate to: Configuration Device to add a new SENSERT device. Input the serial number of the SENSERT Remote I/O Unit, located on the underside of the SENSERT device. Please make sure that your Bluetooth connections are enabled on your phone at this time. If the device has not previously been added to an account, it will automatically connect. If the unit does not automatically connect, please see the troubleshooting section to reset the Bluetooth Mesh.

Analog Input Channel Setup
Analog channel can be enabled or disabled in the configuration screen. If enabled, enter the following information:

Name:
User-defined name of the analog channel

Input Sensor Type:
Select from 0- 10 V, 0-5 V, 4-20 mA, and NTC.

Analog:
Select the type of sensor from the drop-down menu.

Unit:
Define the unit for the sensor output data.

Zero & Span:
Define the zero and span for the channel data for the display.

Report Intervals: The interval of the data updated on the cloud, but if the channel data has no changes larger than 0.05%, the data will not be reported to the cloud.

Alert:
Choose the boundaries for the lower and upper limits for the notification alarm.

Digital Input Channel Setup

Name: User-defined name of the digital channel

Report Intervals: The interval of the data updated on the cloud, but if the channel data has no changes of the status of the DI input, the data will not be re-reported to the cloud.

Sensor Type:
Dry Contact.

Input Mode:
DI input will be treated as digital input normally. The data will be 0 or 1.

Troubleshooting

Occasionally it may be necessary to reset the SENSERT Base Unit to re-enable connectivity.

Reset SENSERT Remote I/O Unit:
Using a pin or paperclip reset the device using the inset rest button on the side of the SENSERT Remote I/O Unit. Holding the reset pin for different durations determine the type of reset performed. (See below)

Power down SENSERT Base Unit:
Hold for 3 seconds until the Power LED flashes then release.

Reset Bluetooth Mesh:
Hold for 6 seconds until the Status LED flashes, then release. In addition to the hardware reset, the user with the account will need to open the smart phone app, go to configuration then device and click reset here as well as the hardware base unit reset.

Reset Factory Settings:
Hold for 9 seconds until both Power and Status LEDs flash, then release. For the user who has the SENSERT already in the account, need to go in smart phone app, go to configuration- device – click RESET to reset the mesh in the app too.
NOTE: This will reset the unit to Factory Settings.

Changes to Terms
Marsh Bellofram reserves the right, in its sole discretion, to change the Terms under which www.sensert.io is offered. The most current version of the Terms will supersede all previous versions. Marsh Bellofram encourages you to periodically review the Terms to stay informed of our updates.

Contact Us
Marsh Bellofram welcomes your questions or comments regarding the Terms:
Marsh Bellofram, Inc.
8019 Ohio River Blvd
Newell, West Virginia 26050
Email Address:
customerrfq@marshbellofram.com
Telephone number:
304-387- 1200
Effective as of January 01, 2020

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>