SIEMENS ASC77.2U OpenAir External Auxiliary Switch Instruction Manual

June 9, 2024
SIEMENS

SIEMENS ASC77.2U OpenAir External Auxiliary Switch

SIEMENS ASC77-2U-OpenAir-External-Auxiliary-Switch-
product

OpenAir™ External Auxiliary Switch

  • a External dual auxiliary switch
  • b. Position indicator
  • c. GCA/GBB/GIB position adapter
  • d. GMA/GEB position adapter
  • e. 3 mm hex key
  • f. Plastic mounting adapter inserts (2)
  • g. Threaded M5 × 25 screws (2)

Product Description

  • The OpenAir External Auxiliary Switch (EAS) provides switch functionality for standard model damper actuators with easy installation for in-service units.Product Description
  • The OpenAir External Auxiliary Switch (EAS) provides switch functionality for standard model damper actuators with easy installation for in-service units.

Product Number

  • ASC77.2U

Specifications

Dual Auxiliary Switches


AC rating

| 24 Vac to 250 Vac
---|---
AC 6A resistive
AC 2 FLA, 12 LRA
DC rating| 12 Vdc to 30 Vdc
DC 2A
Insulation system| Double insulated
Switch range Switch A

Recommended usage

Switch B

Recommended usage

| ****

0° to 90° with 5° intervals

0° to 45°
0° to 90° with 5° intervals
45° to 90°
Switching hysteresis| 2°




Agency certification

| UL listed to UL 873
cUL certified to Canadian Standard C22.2

No. 24-93

Electromagnetic

compatibility 89/336/EEC

Low voltage directive

73/23/EEC

Conduit Connection| Threaded 1/2-inch

NSPT, flex only

Shipping Weight| 1.1 lb (0.48 kg)

Warning/Caution Notations

WARNING:| ****| Personal injury/loss of life

may occur if you do not follow the procedures as specified.

---|---|---
CAUTION:| ****| Equipment damage, or loss of data may occur if you do not follow the procedures as specified.

Required Tools

  • Phillips screwdrivers
  • No. 2 for screws, No. 1 for adjustment

Expected Installation Time

  • 15 minutes

Prerequisites
Remove power from in-service damper actuator before installing external auxiliary switch.

WARNING:
Do not open the external auxiliary switch

Installation

New Actuators, Remove Pre-load

NOTE : For in-service actuators, skip Removing Preload. For new actuators, remove the factoryinstalled 5° pre-load.

Removing Preload

Before the External Auxiliary Switch can be installed on a new, out-of-the-box actuator, you must remove the factory-installed preload.

New Non-Spring Return Actuators

  1. Insert shaft adapter at position A (See Figure 4).
  2. Press the manual override button and move the shaft adapter counterclockwise until actuator reaches the internal stop (actuator will not move past this point).
  3. Remove the shaft adapter and manually reinstall it against the external end stop at position B (See Figure 4).
  4. Proceed with EAS installation

New Spring Return Actuators

  1. Without the shaft adapter installed, using the hex wrench, wind the manual override one full revolution and release the wrench (See Figure 5). The actuator will return to the 0° position and the preload is now removed
  2. Manually install the shaft adapter against the external stop on the left end of the actuator. (See position B in Figure 4.) Removing Factory Pre-load from New SR Actuator.

Preparing the Actuator Shaft Adapter

  1. Remove the position indicator from an in-service actuator.
  2. Determine the appropriate position adapter ring (See Figure 1).
  3. Align and snap the three open notches on the edge of the EAS position adapter ring in place over the three raised stubs on the actuator shaft adapter. (See Figure 6).

Short shaft applications

NOTE : The short shaft adapter is included in the packing box with the shaft adapter. With the short shaft adapter in place, align the notch of the EAS over the protruding tab on the position adapter ring and secure in place. (See Figure 7).

Preparing the EAS for Mounting

NOTE : The EAS label may cover the mounting holes.
See Figure 8 and Figure 9 for the mounting hole locations.

  1. On the back of the EAS, push the plastic inserts into the mounting holes. (See Figure 8 and Figure 9).
  2. Mount the position indicator on the face of the EAS (See Figure 8 step 2 and Figure 9, step 2).

Mounting External Auxiliary Switch to Actuator

  1. Nest the alignment peg of the EAS position adapter ring into the notch (See Figure 10). The EAS lies flush against the face of the actuator.
  2. Secure the EAS in place with the M5×25 screws provided. (See Figure 10).

CAUTION : The EAS should not shift when it is correctly installed firmly against the face of the actuator. The installation is complete.

Manual Override

NOTE : When EAS is installed, you can still access the manual override capability as shown in Figure

Auxiliary Switches

CAUTION:
There should be no load on the actuator when setting the auxiliary switches.

Setting the Switches

With the actuator in the full-closed (0°) position, press in and turn with a Phillips screwdriver to the desired setting. Release pressure to set the switch. The switch is now set.

Wiring

WARNING:
Do not mix operations. Apply only line voltage or only Class 2 voltages to the switching outputs of both auxiliary switches A and B.

Wiring Designation

Wire Code Color Switch – Function
S1 Gray/red A Input
S2 Gray/blue A – NC
S3 Gray/pink A – NO
S4 Black/red B Input
S5 Black/blue B – NC
S6 Black/pink B – NO

Dimensions

SIEMENS ASC77-2U-OpenAir-External-Auxiliary-Switch-fig-
\(15\)

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. OpenAir is a trademark of Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2018 Siemens Industry, Inc

Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 + 1 847-215-1000
Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com
Document No. 129-420 Printed in the USA

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>