MORNINGSTAR 021363 Readyrail System Dry Contact Block
IMPORTANT SAFETY INFORMATION
-
WARNING: Shock Hazard
The Morningstar Ready Block must be installed by a qualified technician in accordance with the electrical regulations of the location of installation. -
WARNING: Shock Hazard
Disconnect all power sources to the host and all other connected devices before working with ReadyRelay wiring. Do not install or remove a ReadyRelay while the host device is powered ON. -
CAUTION: Equipment Damage
The relay circuit has no overcurrent protection. A fuse no larger than six (6) Amps must be installed – in either leg – to protect the circuit. Since the internal relay circuitry has no overcurrent protection, the installer must ensure that the circuit is fused. ReadyRelay failures that result from lack of overcurrent protection are not covered by the Morningstar warranty. -
CAUTION: Equipment Damage
Power surges with in-rush current greater than 10 Amps can damage the relay. -
CAUTION: This guide must be used with the full product manual that includes important information. Carefully read the ReadyRelay product manual for all specifications, safety, regulatory and warranty information, and for all required instructions on installation procedures, configuration, and operation.
The ReadyRelay requires a Morningstar ReadyRailTM-enabled host device, e.g., GenStar controller or ReadyEdge System Monitor and Communication Center to provide a mounting surface, power, and programming capability.
FEATURES
MOUNTING
- Power OFF host device
- Pull yellow slider out
- Fit Block slot downward onto DIN Rail
- Slide the Block to the left, but before joining the male and female mates, be sure that pin guards and pins are lined up correctly. Carefully slide the Block farther to the left to securely join the Block with host-device female mates.
- Push yellow slider in, to secure Block on rail
- Secure Block(s) to DIN rail with cover, clamp, or other means provided with host device.
Install additional Blocks in the same fashion as above.
CONFIGURATION
first connect the battery to the host device to power the host device-relay
block system ReadyRelay settings are adjusted in the host device’s Morningstar
LiveView web page. Refer to the Morningstar Website ReadyRelay full manual for
details on how to connect to LiveView and access Installer Setup.
CAUTION: Configure the ReadyRelay via the host-device and the Morningstar
Liveview webpage, FIRST, before wiring the relay.
See important topics in Configuration Section – 4.0 – of the ReadyRelay manual titled: Threshold; Faults and Alarms; Charge Stage; External Source Control (ESC) Start-Stop, e.g., generator; Command/Schedule.
WARNING: Shock Hazard
Disconnect all power sources to the host and all other connected devices
before working with ReadyRelay wiring.
General Use
Relay contact terminals can be wired to a generator starting circuit (consult
ReadyRelay manual Section 5.2 for details), vent fan, communications
equipment, larger relays for power switching, buzzer or trouble light (no
auxiliary devices included).
After wiring, tighten the terminal connector screws to 5 in-lb (0.56 N-m) of torque. Connect the battery to power the host device-relay block system.
LED INDICATIONS and TROUBLESHOOTING
The top ReadyRelay LED indicates Block status. The middle LED indicates operation of Relay A. The lower LED indicates operation of Relay B. The status LED will operate with a momentary heartbeat off every (5) seconds.
Contact Information:
www.morningstarcorp.com
Phone: 1-215-321-4457