aritech 2X-A-LB Addressable 2 Loop Board

Installation Sheet

Description

The 2X-A-LB Loop Board provides two additional loops (LOOP3 and LOOP4) and four additional supervised outputs (OUT5, OUT6, OUT7, and OUT8) to compatible 2X-A control panels.

Caution: The 2X-A-LB Loop Board is only compatible for installation in 2X-A control panels.

Installation

WARNING: To avoid personal injury or death from electrocution, disconnect the control panel from the mains power supply and batteries before installing this product.

Recommended cable
Use 0.13 to 3.31 mm² (12 to 26 AWG) shielded or unshielded twisted-pair cable. Use the earth studs in the control panel cabinet for termination.
See your control panel installation manual for more information on cable and wiring recommendations.

To install the expansion board:

  1. Install the loop board into slot 2 of the control panel chassis, as shown in Figure 1. Push firmly to ensure a good connection. Secure the board with the screws provided.

  2. Connect loops and configurable outputs as shown in Figure 2.
    Loop earth connection: Connect one side to the earth studs in the control panel cabinet (not to the loop earth terminal on the expansion board). The other side can be left floating.
    Output connection: If an output is not used, install an end-of-line resistor across the unused terminals (refer to the Specifications table, configurable outputs) to avoid an open circuit fault on the output.

  3. Restore power and add the device to the control panel configuration (see the control panel installation manual for further details).

  4. Configure loops, outputs, and all connected devices. Check loop installations using a loop load calculator.

See your control panel installation manual for detailed information on loop and configurable output wiring and configuration.

aritech-2X-A-LB-Addressable 2-Loop-Board-01

Maintenance

Basic maintenance consists of a yearly inspection. Do not modify internal wiring or circuitry.

Specifications

Table 1: Loop and mechanical specificationsaritech-2X-A-LB-Addressable 2
-Loop-Board-03

  1. Supplied by the control panel.
  2. Increased to 800 mA if the optional 2010-2A-PAK-HPL is installed.

Table 2: Configurable output specifications aritech-2X-A-LB-Addressable
2-Loop-Board-04

  1. Reverse polarity, end-of-line resistor.
  2. The maximum system consumption limit (Imax b) depends on the control panel power supply – see your control panel installation manual for details.
Regulatory information

aritech-2X-A-LB-Addressable 2-Loop-Board-05

Contact information and product documentation
For contact information or to download the latest product documentation, visit firesecurityproducts.com.

Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED PROFESSIONALS. CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR “AUTHORIZED RESELLER”, IS PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND SECURITY RELATED PRODUCTS.

For more information on warranty disclaimers and product safety information, please check https://firesecurityproducts.com/policy/product-warning/ or scan the QR code: