Schneider Electric MTN6705-0008 SpaceLogic KNX Switch/Blind Master Instruction Manual
- June 9, 2024
- Schneider Electric
Table of Contents
Schneider Electric MTN6705-0008 SpaceLogic KNX Switch/Blind Master
About this document
You can find all the information required for safe installation in this document.
More detailed product information is available on the Internet -> See QR code.
http://go2se.com/ref=MTN6705-0008
For your safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Safe electrical installation must be carried out only by skilled professionals. Skilled professionals must prove profound knowledge in the following areas:
- Connecting to installation networks
- Connecting several electrical devices
- Laying electric cables
- Connecting and establishing KNX networks
- Safety standards, local wiring rules and regulations
Failure to follow these instructions will result in death or serious injury.
DANGER
Risk of death from electric shock.
- If the flap lid of the device is open, protection rating IP20 is not assured.
- When the device is installed, keep the flap lid closed.
- Failure to observe these instructions will lead to death or serious injuries.
Getting to know the device
- The SpaceLogic KNX Switch/Blind Master is a KNX actuator that switches max. 8 loads or controls max. 4 blind motors with limit switches.
- You can connect a maximum of two extension devices.
Connections and operating elements
- A Load connections
- B Flap lid
- C Bus connection
- D Service connector
- E Programming button with programming LED
- F Function buttons with LEDs Master push-button, Extension 1/Extension 2 pushbutton, Manual push-button
- G Channel push-buttons
- H Link interface with cap
Installation and connection
Installing
WARNING
Risk of death from electric shock. The device can be damaged. Safety clearance
must be guaranteed in accordance with IEC 60664-1. There must be at least 4 mm
between the individual cores of the 230 V supply cable and the KNX line A.
WARNING
- Risk of death from electric shock.
- Only install devices with at least basic insulation next to the device.
- Failure to observe this instruction can result in death or serious injury.
Connecting
DANGER
Risk of fatal injury from electric shock.When the mains voltage is connected,
there may be voltage at the outputs.
- The switching contacts may switch to the connected state due to heavy jolting during transportation.
- Only connect the bus voltage.
- All relays are moved to a defined position: in factory setting to “Off” or depending on ETS programming. The Master LED lights up, the keypad shows the status of the channels.
- On the key pad: switch off the switched-on channels
- Disconnect the bus voltage
- Connect loads
- First switch on the bus voltage then the load voltage
- Failure to observe these instructions will lead to death or serious injuries.
Note
- Connect only one motor per blind channel.
- Connect only blind motors with thermal protection.
- Switch channels are not locked against each other. Only connect blind motors to channels that are configured as a blind channel. Failure to observe this instruction can damage the blind motors.
Testing
- Activate override switching
- Select channel with connected load
The LEDs of the selected function buttons light up. The connected load is switched on.
Technical data
- Supply voltage: KNX Bus
- Master: approx. 6.5 mA
- Master + 1 Extension: approx. 9 mA
- Master + 2 Extensions: approx. 12.5 mA
- Insulation: Protective separation between the bus and the mains voltage
- Power dissipation: < 8 W
- KNX medium: TP1-256
- Switching contacts: 8x make contacts, μ contact
- Nominal voltage: AC 250 V, 50-60 Hz
- Nominal current: 16 A AC-1, IEC 60947-4-1 10 A, IEC 60669-2-5
- Nominal power:
- Switching frequency: max. 10 per minute at nominal load
- Total device current: Relay data
- Inrush current: max. 800 A/200 μs, max. 165 A/20 ms
- Mechanical endurance: >1×106 operations
- Fusing: max. 16 A Miniature circuit breaker Environment
- Temperature in operation: -5 °C … +55 °C
- Max. humidity: 93%, no condensation
- Installation height: Up to 2000 m above sea level Resistance to fire and
- heat: Glow wire test according to IEC 60695 Connecting terminals
- KNX: Bus connection terminal
- Mains: 2x 8-gang screw terminal
- Device width: 4 modules = approx. 72 mm
Dispose of the device separately from household waste at an official collection point. Professional recycling protects people and the environment against potential negative effects.
Schneider Electric -Contact
Schneider Electric Industries SAS 35 rue Joseph Monier Rueil Malmaison 92500 France If you have technical questions, please contact the Customer Care Centre in your country. se.com/contact
UK Representative
Schneider Electric Limited Telford, TF3 3 BL, UK Stafford Park 5
References
- Go2SE
- Contact Support | Schneider Electric Global
- Schneider Electric Казахстан | Мировой эксперт в управлении энергией и автоматизации
- Систэм Электрик - официальный сайт
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>