MTN6710-0102http://go2se.com/ref=MTN6710-0102

About this document

You can find all the information required for safe installation in this document.
More detailed product information is available on the Internet -> See QR code.

For your safety

DANGEHAZARD OF ELER CTRIC SHOCK, EXPLOSION, OR ARC FLASH
The safe electrical installation must be carried out only by skilled professionals. Skilled profession-als must prove profound knowledge in the follow-ing areas:

  • Connecting to installation networks
  • Connecting several electrical devices
  • Laying electric cables
  • Connecting and establishing KNX networks
  • Safety standards, local wiring rules and regulations
    Failure to follow these instructions will result in death or serious injury.

DANGER
death from electric shock.
If the flap lid of the device is open, protection rat-ing IP20 is not assured.

  • When the device is installed, keep the flap lid closed.

Failure to observe these instructions will lead to death or serious injuries.

Getting to know the device

The SpaceLogic KNX Universal Dimming Master is a KNX actuator that switches and dims various loads on 2 channels.
You can connect a maximum of two extension devices.
Possible extensions:

  • Spacelogic KNX Universal Dimming Extension MTN6810-0102
  • SpaceLogic KNX Switch/Blind Extension MTN6805-0008

The actuator automatically detects the connected load for each channel.
Dimming operating modes:

  • RC operating mode = trailing edge phase (automatic)
  • RL operating mode = leading edge phase (automatic)
  • RL-LED operating mode = leading edge phase (ETS)

For LEDs/CFLs the RC operating mode is automatically set. In some cases, however, LEDs/CFLs must be oper-ated with the RL-LED operating mode. Please also read the product information on the internet and the instruc-tions of the lamp manufacturers.

Connections and operating elements

Schneider-Electric-MTN6710-0102
-SpaceLogic-KNX-Universal-Dimming-Master-FIG-3

  • A Flap lid

  • B Bus connection

  • C Service connector

  • D Programming button with programming LED

  • E Load connections

  • F Function buttons with LEDs
    Master push-button, Extension 1/Extension 2 push-button, Manual push-button

  • G Channel and function buttons for channel 1 (C1) and channel 2 (C2)

  • H Link interface with cap

Installation and connection

Schneider-Electric-MTN6710-0102-SpaceLogic-KNX-Universal-Dimming-Master-
FIG-4Installing
WARNING Risk of death from electric shock. The device can be damaged
Safety clearance must be guaranteed in accord-ance with IEC 60664-1. There must be at least 4 mm between the individual cores of the 230 V supply cable and the KNX line A. WARNING
Risk of death from electric shock. Only install devices with at least basic insulation next to the device.
Failure to observe this instruction can result in death or serious injury.

ConnectingSchneider-Electric-MTN6710-0102-SpaceLogic-KNX-Universal-
Dimming-Master-FIG-5Schneider-Electric-MTN6710-0102-SpaceLogic-KNX-Universal-Dimming-
Master-FIG-6 WARNING Fire hazard due to overload. Only loop through the neutral conductor to a Universal Dimming Master or to a Universal Dimming Extension.
Failure to observe this instruction can result in death or serious injury.

CAUTION
The device can become damaged. Only connect dimmable transformers. Only use wound transformers with a load of at least 30% of the nominal load. Do not connect a combination of capacitive and inductive loads to one channel. Do not connect a load electrically in parallel to multiple channels. Do not dim socket-outlets.

Testing

  1. Activate override switching
  2. Select channel with connected load

The LEDs of the selected function buttons light up. The connected load is switched on.

Technical data

  • Supply voltage: KNX Bus

  • Master: approx. 7.5 mA

  • Master + 1 Extension: approx. 10 mA

  • Master + 2 Extensions: approx. 12.5 mA

  • Insulation: Protective separation between the bus and the mains voltage

  • Power dissipation: < 6 W

  • KNX medium: TP1-256

  • Number of channels: 2 (Connection to different phases possible)

  • Nominal voltage: AC 110-240 V, 50/60 Hz

  • Nominal power:Schneider-Electric-MTN6710-0102-SpaceLogic-KNX-Universal-Dimming-Master-FIG-2

  • Fusing: max. 16 A Miniature circuit breaker
    Dimmer type: 3-wire
    Environment
    Temperature in operation: -5 °C … +55 °CSchneider-Electric-MTN6710-0102
-SpaceLogic-KNX-Universal-Dimming-Master-FIG-8

  • Max. humidity: 93 %, no condensation Installation height: Up to 2000 m above sea level
    Protections: Electronic load detection, Short detection, Overload detection

Resistance to fire and

  • heat: Glow wire test according to IEC 60695

Connecting terminals

  • KNX: Bus connection terminal
  • Mains: 8-gang screw terminal
  • Device width: 4 modules = approx. 72 mm

Dispose of the device separately from household waste at an official collection point. Professional recycling protects people and the environment against potential negative effects.

Schneider Electric -Contact

Schneider Electric Industries SAS
35 rue Joseph Monier
Rueil Malmaison 92500
France
If you have technical questions, please contact the Customer Care Centre in your country. se.com/contact