Schneider Electric TM241C24T Programmable Logic Controller Instructions

June 9, 2024
Schneider Electric

Schneider Electric TM241C24T Programmable Logic Controller Instructions
Schneider Electric TM241C24T Programmable Logic
Controller

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

DANGER

  • Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
  • Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
  • Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
  • Use only the specified voltage when operating this equipment and any associated products.

Failure to follow these instructions will result in death or serious injury

POTENTIAL FOR EXPLOSION

DANGER

  • Only use this equipment in non-hazardous locations, or in locations that comply with Class I, Division 2, Groups A, B, C and D.
  • Do not substitute components which would impair compliance to Class I Division 2.
  • Do not connect or disconnect equipment unless power has been removed orthe area is known to be non-hazardous.

Failure to follow these instructions will result in death or serious injury

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

TM241| Ethernet| CANopen Master| Digital Inputs| Digital Outputs| Cartridge| Power Supply
---|---|---|---|---|---|---
TM241C24T| No| No| 8 fast inputs, 6 regular inputs| Source outputs4 fast transistor outputs 6 regular outputs| 1| 24 Vdc
TM241CE24T| Yes| No
TM241CEC24T| Yes| Yes
TM241C24U| No| No| 8 fast inputs, 6 regular inputs| Sink outputs4 fast transistor outputs 6 regular outputs
TM241CE24U| Yes| No
TM241CEC24U| Yes| Yes
TM241C40T| No| No| 8 fast inputs, 16 regular inputs| Source outputs4 fast transistor outputs 12 regular outputs| 2
TM241CE40T| Yes| No
TM241C40U| No| No| 8 fast inputs, 16 regular inputs| Sink outputs4 fast transistor outputs 12 regular outputs
TM241CE40U| Yes| No

  1. Run/Stop switch
  2. SD Card slot
  3. Battery holder
  4. Cartridge slot 1 (40 I/O model, cartridge slot 2)
  5. LEDs for indicating I/O states
  6. USB mini-B programming port
  7. Clip-on lock for 35-mm (1.38 in.) top hat section rail (DIN rail)
  8. Output terminal block
  9. CANopen Line termination switch
  10. 24 Vdc power supply
  11. CANopen port
  12. Ethernet port
  13. Status LEDs
  14. Serial line port 1
  15. Serial line port 2 terminal block
  16. Input terminal block
  17. Protective cover
  18. Locking hook (Lock not included)
    Product Overview

WARNING

UNINTENDED EQUIPMENT OPERATION

  • Use appropriate safety interlocks where personnel and/or equipment hazards exist.
  • Install and operate this equipment in an enclosure appropriately rated for its intended environment and secured by a keyed or tooled locking mechanism.
  • Power line and output circuits must be wired and fused in compliance with local and national regulatory requirements for the rated current and voltage of the particular equipment.
  • Do not use this equipment in safety-critical machine functions unless the equipment is otherwise designated as functional safety equipment and conforming to applicable regulations and standards.
  • Do not disassemble, repair, or modify this equipment.
  • Do not connect any wiring to reserved, unused connections, or to connections designated as No Connection (N.C.)

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Top hat section rail
Top hat section rail

Panel
Panel

This table is made according to SJ/T 11364.

O: Indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572.
X: Indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as stipulated in GB/T 26572.

Dimmensions

Dimensions

Place any TM2 module(s) at the end of your configuration after any TM3 module(s)

TM2 module
TM2 module

Pitch 5.08 mm

|     | | | | | | | | Ø 3,5 mm (0.14 in.)|
---|---|---|---|---|---|---|---|---|---|---
mm2| 0.2…2.5| 0.2…2.5| 0.25…2.5| 0.25…2.5| 2 x 0.2…1| 2 x 0.2…1.5| 2 x 0.25…1| 2 x 0.5…1.5| N•m| 0.5…0.6
AWG| 24…14| 24…14| 22…14| 22…14| 2 x 24…18| 2 x 24…16| 2 x 22…18| 2 x 20…16| lb-in| 4.42…5.31

Use copper conductors only

**Power supply

**

Type T fuse
Type T fuse

Make the power supply wiring as short as possible

WARNING

POTENTIAL OF OVERHEATING AND FIRE

  • Do not connect the equipment directly to line voltage.
  • Use only isolating PELV power supplies to supply power to the equipment.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTE: For compliance to UL requirement, use only Class II power supplies limited to 100 VA maximum.

Digital inputs

TM241C24T / TM241CE24T / TM241CEC24T
TM241C24U / TM241CE24U / TM241CEC24U
Digital inputs

TM241C40T / TM241CE40T
TM241C40U / TM241CE40U
Digital inputs
Digital inputs

**Fast input wiring

**

Type T fuse

  1. The COM0, COM1 and COM2 terminals are not connected internally
    A: Sink wiring (positive logic)
    B: Source wiring (negative logic)

Transistor outputs

TM241C24T / TM241CE24T / TM241CEC24T
Transistor outputs 

**TM241C40T / TM241CE40T
Transistor outputs 
Transistor outputs 
Fast output wiring

**

TM241C24U / TM241CE24U / TM241CEC24U
Transistor outputs 

TM241C40U / TM241CE40U
Transistor outputs 
Transistor outputs 

Type T fuse

  1. The V0+, V1+, V2+ and V3+ terminals are not connected internally
    Type T fuse

  2. The V0–, V1–, V2– and V3– terminals are not connected internally
    Type T fuse

Ethernet

Ethernet
1 TD +
2 TD —
3 RD+
4
5
6 RD —
7
8

NOTICE

INOPERABLE EQUIPMENT

Use only the VW3A8306Rpp serial cable to connect RS485 devices to your controller.
Failure to follow these instructions can result in equipment damage.

Serial line

SL1

RS 232 RS 485
1 RxD N.C.
2 TxD N.C.
3 N.C. N.C.
4 N.C. D1
5 N.C. D0
6 N.C. N.C.
7 N.C.* 5 Vdc
8 Common Common

**RJ45

**

SL2
Serial line

Ter. RS485
COM 0 V com.
Shield Shield
D0 D0
D1 D1

WARNING

UNINTENDED EQUIPMENT OPERATION

Do not connect wires to unused terminals and/or terminals indicated as “No Connection (N.C.)”.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

CANopen bus

LT: CANopen Line termination switch
CANopen bus

TM241CECppp
CANopen bus

NC: Not used
RD: Red
WH: White
BU: Blue
BK: Black
CANopen bus

SD Card

TMASD1

  1. Read only

SD Card

  1. Read/Write enabled

SD Card

Battery installation

  1. Battery installation 
        1. Battery installation 

DANGER

EXPLOSION, FIRE, OR CHEMICAL BURNS

  • Replace with identical battery type.
  • Follow all the instructions of the battery manufacturer.
  • Remove all replaceable batteries before discarding unit.
  • Recycle or properly dispose of used batteries.
  • Protect battery from any potential short-circuit.
  • Do not recharge, disassemble, heat above 100 °C (212 °F), or incinerate.
  • Use your hands or insulated tools to remove or replace the battery.
  • Maintain proper polarity when inserting and connecting a new battery.

Failure to follow these instructions will result in death or serious injury.

UK Representative
Schneider Electric Limited
Stafford Park 5
Telford, TF3 3BL
United Kingdom