WISILICA Radiar AR10 Bluetooth 5.2 Controllable Dual Channel 0-10V Room Controller User Manual

June 9, 2024
WISILICA

Radar AR10 Bluetooth 5.2 Controllable Dual Channel 0-10V Room Controller
User Manual

WISILICA Radiar AR10 Bluetooth 5 2 Controllable Dual Channel 0 10V Room
Controller - Fig Radar AR10

Radar AR10 Bluetooth 5.2 Controllable Dual Channel 0-10V Room Controller

Radar AR10 is a BLE5.2 controllable, dual-channel 0-10V room controller. The device is powered by 277VAC voltage, also has a 20A relay to use it as a room controller or as  a plug-load controller. It comes with Class-1 and Class-2 dual channel 0-10V dimming outputs, 0-10V sensor input, and 12V auxiliary output. The high output ratings  within the device makes it suitable to control multiple numbers of light fixtures within a room. The device comes with 150mm external wire antenna for communication.
The Lumos Controls ecosystem comprises controllers, sensors, switches, modules, drivers, gateways, and analytical dashboards, and can be connected to the Lumos Controls  cloud for data analytics and configuration management. The lighting network’s configuration, commissioning, and controlling can be done super-quick from any mobile  device. The ecosystem is listed by the Design Lights Consortium (DLC), qualifying it for energy conservation incentive programs and rebates utility companies in North America.

Features

  • Dual channel 0-10V independent output to control intensity and color temperature (CCT).
  • Load control up to 20A @ 120/277VAC.
  • Auxiliary 12V/100mA output to power the sensors.
  • 0-10 VDC input channel to integrate with third party sensors.
  • Class-1 and Class-2 dual channel 0-10V outputs to control the dimming and CCT.
  • It acts as a Plug load controller to manage, control and monitor the plug loads efficiently.
  • Instantaneous current and voltage measurement of connected load.
  • BLE5.2 based non-flooding intelligent communication.
  • Standard ½ inch chase nipple allows easy mounting to a junction box.
  • Zero downtime Over-the-Air (OTA) firmware updates.

Specifications

Electrical Value Remarks
Input Voltage 120 – 277 VAC
Input Current 40 Ma @230 75 Ma @ 110v
Frequency 50 – 60 Hz
Load Voltage 90-277 V
Load Current 20A
Max LOAD output wattage 5 KW
Inrush current 4A
Surge protection 4 kV
Standby current 14 Ma @ 110v 12 Ma @ 230 V
0-10V Output Value Remarks
--- --- ---
Number of channels 2
Voltage range 0-10VDC Tolerance: ±0.2V
Current 100mA Source current per channel
Dimming Range 0-100% 1000 steps resolution
Dimming curve linear (default) /logarithmic
Sensor Input Value Remarks
--- --- ---
Voltage Range 0-10VDC Analog input
Auxiliary Output Value Remarks
--- --- ---
Voltage 12VDC
Current 100mA
Bluetooth Value Remarks
--- --- ---
Frequency 2402-2480 MHz
Max output power 8 dBm
Receive sensitivity -95 dBm
Connection distance (device to device) 45m (146 ft) vary depending on the

installation environment
Environmental| Value| Remarks
---|---|---
Operating temperature (in °C, °F)| -20 – 50 ºC|
Case temperature (in °C, °F)| 70 ºC|
Relative humidity (in °C, °F)| 20 – 85 %|
Mechanical| Value| Remarks
---|---|---
Dimensions| 109.5 x 96.5 x 28 mm| L x W x H
Dimensions| 4.3 x 3.8 x 1.10 inch| L x W x H
Weight (in gm, oz)| 160 gm (2.11 oz)|
Case material| ABS Plastic (Blue color)|
Flammability rating| UL 94 5VA|

Dimensions

Radar AR10

WISILICA Radiar AR10 Bluetooth 5 2 Controllable Dual Channel 0 10V Room
Controller - Dimensions

Wire Description

WISILICA Radiar AR10 Bluetooth 5 2 Controllable Dual Channel 0 10V Room
Controller - Wire

Class-1 outputs

Pin Name Color Gurage Rating Description
1 Line Black 12AWG (4.0mm2) 600V 120-277VAC
2 Common Neutral White 12AWG (4.0mm2) 600V 120-277VAC
3 Load Red 14AWG (2.5 mm2) 600V 120-277VAC
4 0-10V DIM1+ Purple 20AWG (0.5mm2) 600V 0-10VDC/100mA
5 0-10V DIM2+ Orange 20AWG (0.5mm2) 600V 0-10VDC/100mA
6 0-10VDIM-/GND Pink 20AWG (0.5mm2) 600V 0-10VDC/GND
7 12VDC Yellow 20AWG (0.5mm2) 600V 12VDC/100mA
8 0-10VDC sensor input Blue 20AWG (0.5mm2) 600V 0-10VDC/2mA

Class-2 Outputs

Pin Name Push-in connector Color Description
1 0-10V DIM1+ Purple 0-10VDC/100mA
2 0-10V DIM2+ Orange 0-10VDC/100mA
3 0-10VDIM-/GND Pink 0-10VDC/GND
4 0-10VDC sensor input Blue 0-10VDC/2mA
5 12VDC Yellow 12VDC/100mA
6 0-10VDIM-/GND Pink 0-10VDC/GND

Antenna Information

150mm wire antenna

WISILICA Radiar AR10 Bluetooth 5 2 Controllable Dual Channel 0 10V Room
Controller - wire antenna

Antenna Properties


Frequency range| 2.4 GHz-2.5GHz
Impedance| 50 Ω Nominal
VSWR| 1.92:1 Max
Return loss| -10 dB Max
Gain(peak)| 2 dB
Cable loss| 0.3 dB Max
Polarization| Linear vertical

Wiring Types

Class-1 wiring

  • In Class-1 wiring, the 0-10V low voltage control wires run along with the line voltage wires in a same conduit. (See the image below)
  • Class 1 installations require wire with insulation that is rated for the voltage carried (most wiring has 600V rated insulation) and must be installed in conduit or a  protective cable assembly.

WISILICA Radiar AR10 Bluetooth 5 2 Controllable Dual Channel 0 10V Room
Controller - Wiring Types

Class-2 wiring

  • In Class-2 wiring, the 0-10V low voltage wires run separately in another conduit (See the image below)
  • These circuits do not have high enough voltage or current to present a hazard to personnel and have less stringent installation requirements in regards to protection of the wiring.
  • A Class 2 wiring may be installed free within the wall or ceiling without line voltage rated insulation or protection of conduit or a cable assembly.

WISILICA Radiar AR10 Bluetooth 5 2 Controllable Dual Channel 0 10V Room
Controller - Wiring Types1

Wiring Diagram

  1. Configuring Radar AR10 for dimming, tuning and an external sensor control.WISILICA Radiar AR10 Bluetooth 5 2 Controllable Dual Channel 0 10V Room Controller - Wiring Types 2
  2. Configuring Radar AR10 for Plug Load ControlWISILICA Radiar AR10 Bluetooth 5 2 Controllable Dual Channel 0 10V Room Controller - Radiar AR10

Items included in the package box

  • Radar AR10
  • User Manual
  • Antenna

Ordering Information

Product Code| Product Description| Communication| Voltage Rating| Sensor Input| Output Channel| Aux Power| Relay Control| Inbuilt Power
Measurement
---|---|---|---|---|---|---|---|---
WCA2CSRN| Wireless 0-10V dual channel dimming AC powered room controller without Power measurement.| BLE5.2| 120-277V AC| 0-10 VDC| 0-10V
2 Channels| 12VDC| 20A| No
WCA2CSRN P| Wireless 0-10V dual channel dimming AC powered room controller Measurement.| BLE5.2| 120-277V AC| 0-10 VDC| 0-10V
2 Channels| 12VDC| 20A| Yes

FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide  reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed  and  used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Caution: Any changes or modifications to this device not explicitly approved by manufacturer could void your authority to operate this equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this  device must accept any interference received, including interference that may cause undesired operation.
RF Exposure Information
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance
20cm between the radiator and your body.

CONNECTING THINGS TO LIFE
WI Silica Inc
23282 Mill Creek Dr #340, Laguna Hills, CA 92653 United States of America
info@wisilica.com www.wisilica.com
www.wisilica.com
sales@wisilica.com

Read User Manual Online (PDF format)