PENTAIR 521139 IntelliTouch Pool Control Systems Installation Guide
- June 9, 2024
- Pentair
Table of Contents
521139 IntelliTouch Pool Control Systems
EASYTOUCH® and INTELLITOUCH®
CONTROL SYSTEM FOR POOL AND SPA (WITH OPTIONAL INTELLICHLOR® SALT CHLORINE
GENERATOR) LOAD CENTER INSTALLATION GUIDE
IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Custoomer Support
Contact Customer Support at:
800-831-7133 – (8 A.M. to 7:30 P.M.)
Sanford, North Carolina Fax:
919-566-8920 Moorpark, California Fax:
805-553-5515
visit www.pentair.com
P/N 521139 Rev. C 2/2020
i
Contents
IMPORTANT WARNING AND SAFETY INSTRUCTIONS ………………………………………………………………… iii
General Installation Information ……………………………………………………………………………………………………..v
Section 1: Pentair Water Pool and Spa Control System Load Center and Power
Center Overview.. 1 Load Center and Power Center Installation Overview
……………………………………………………………………… 2
Load Center with subpanel (EasyTouch and IntelliTouch
Systems)…………………………………………………. 3 Power Center (without built-in Subpanel) –
IntelliTouch System Only ………………………………………………. 4 Preparing the Load Center and
Power Center Enclosure …………………………………………………………………. 5 Mounting the Load Center
and Power Center…………………………………………………………………………………. 6 Connecting AC Power to the
Load Center and Power Center……………………………………………………………. 7 Electrical Wiring High
Voltage Connections ……………………………………………………………………………………. 8 Installing Conduit and
Wire to the Enclosure ………………………………………………………………………………….. 8 Accessing the
EasyTouch or IntelliTouch Circuit Board and Electronics……………………………………………. 10
Connecting the EasyTouch System Relays ………………………………………………………………………………….. 11
Connecting the IntelliTouch System Relays ………………………………………………………………………………….. 12
Installing Valve Actuators …………………………………………………………………………………………………………… 13
Adjusting the valve position…………………………………………………………………………………………………….. 13
Installing and Connecting Temperature Sensors……………………………………………………………………………. 15
Water Temperature Sensor …………………………………………………………………………………………………….. 15 Ambient
Air Temperature Sensor (for freeze protection) ……………………………………………………………… 15
Solar Temperature Sensor (Optional)……………………………………………………………………………………….. 16
Connecting a Standard Gas Heater (EasyTouch and IntelliTouch System)
……………………………………….. 17 Wiring Pentair UltraTemp Heat Pump
………………………………………………………………………………………….. 18 Wiring Pentair IntelliFlo Pumps
…………………………………………………………………………………………………… 18 Connecting IntelliChlor (SCG) Power
Cord to the Enclosure ………………………………………………………….. 20 Connecting IntelliChlor
(SCG) COM Port Cable …………………………………………………………………………… 21 Wiring a Salt Chlorine
Generator ………………………………………………………………………………………………… 23 Wiring IntelliChlor
……………………………………………………………………………………………………………………. 23 Wiring IntelliChlor (SCG)
Transformer to a Filter Pump ………………………………………………………………….. 24 Rewiring the
IntelliChlor SCG Transformer for 120VAC ………………………………………………………………….. 26
Rewiring the System Transformer for 240 VAC ……………………………………………………………………………… 27
Section 2: EasyTouch System Overview …………………………………………………………………………………. 28
EasyTouch 8 and 4 Pool and Spa Control System Kit Contents
…………………………………………………… 28 EasyTouch Accessory
Equipment……………………………………………………………………………………………. 28 EasyTouch Model Part
Numbers……………………………………………………………………………………………… 29 EasyTouch System Start-Up
………………………………………………………………………………………………………. 30 EasyTouch Circuit Board
Connections…………………………………………………………………………………………. 31 EasyTouch System Wiring
Diagram ……………………………………………………………………………………………. 32
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
ii
Contents (continued)
Section 3: IntelliTouch System Overview ………………………………………………………………………………… 33
IntelliTouch System Components………………………………………………………………………………………………… 33
Load Center or Power Center …………………………………………………………………………………………………. 33
IntelliTouch Personality Kits ……………………………………………………………………………………………………. 33
IntelliTouch Accessory Power Center Expansion Kits………………………………………………………………….
34 IntelliTouch Personality Kit Contents…………………………………………………………………………………………….
34 Optional Equipment (IntelliChem) ……………………………………………………………………………………………….. 34
Optional IntelliTouch Expansion Enclosure …………………………………………………………………………………… 36
Kit Contents ………………………………………………………………………………………………………………………….. 36 Affixing the
System Wiring Diagram Label…………………………………………………………………………………. 36 System Start-
Up……………………………………………………………………………………………………………………….. 37 Check Electronics
…………………………………………………………………………………………………………………. 37 System
Test………………………………………………………………………………………………………………………….. 37 Testing the auxiliary
relays ……………………………………………………………………………………………………… 37 Solar System Installation
…………………………………………………………………………………………………………… 38 Solar System Start-Up
…………………………………………………………………………………………………………… 38 Pool Cleaner Protection
…………………………………………………………………………………………………………….. 38 Installing the IntelliTouch
Control Panel ……………………………………………………………………………………….. 39 IntelliTouch Outdoor
Control Panels ……………………………………………………………………………………………. 40 IntelliTouch System
Wiring Diagrams…………………………………………………………………………………………… 41 Plumbing
Requirements…………………………………………………………………………………………………………….. 44 Equipment Location
………………………………………………………………………………………………………………….. 45
Glossary…………………………………………………………………………………………………………………………………. 47
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
iii
IMPORTANT WARNING AND SAFETY INSTRUCTIONS
READ AND FOLLOW ALL WARNING AND SAFETY INSTRUCTIONS
SERIOUS BODILY INJURY OR DEATH CAN RESULT IF THIS PRODUCT (UNIT) IS NOT
INSTALLED AND USED CORRECTLY. INSTALLERS, POOL OPERATORS AND POOL OWNERS MUST
READ THESE WARNINGS AND ALL INSTRUCTIONS BEFORE USING THIS PRODUCT. This Guide
provides installation and operation instructions for the product. Consult
Pentair Water Pool and Spa, Inc. (“Pentair”) with any questions regarding this
product. This product is intended for use in swimming pool applications only.
Most states and local codes regulate the construction, installation, and
operation of public pools and spas, and the construction of residential pools
and spas. It is important to comply with these codes, many of which directly
regulate the installation and use of this product. Consult your local building
and health codes for more information.
IMPORTANT NOTICE – Attention Installer: This Installation Guide (“Guide”)
contains important information about the installation, operation and safe use
of this product. This Guide should be given to the owner and/or operator of
this equipment. Attention User: This Guide contains important information that
will help you in operating and maintaining this product. Please retain it for
future reference. Before installing this product, read and follow all safety
warning notices and instructions which are included. Failure to follow safety
warnings and instructions can result in severe injury, death, or property
damage. Call 800-831-7133 for
additional free copies of these instructions.
This product is designed and manufactured for safe and reliable service when
installed, operated and maintained according to the information and
installation codes referred to in this Guide.
This is a safety alert symbol. When you see this symbol in this manual or on
the product, look for one of the following signal words; DANGER, WARNING,
CAUTION and NOTICE and comply with the information. Be alert to the potential
hazard. Ensure to read and comply with all of the warnings and cautions in
this manual.
Risk of Electrical Shock or Electrocution! – Always disconnect power at the
circuit breaker before servicing the load center – Improper installation can
create an electrical shock hazard that can result in death or serious
injury.
This product must be installed by a licensed or certified electrician or a
qualified pool professional in accordance with the current National Electrical
Code (NEC), NFPA 70 or the Canadian Electrical Code (CEC), CSA C22.1. All
applicable local installation codes and ordinances must also be adhered to.
Improper installation will create an electrical hazard which could result in
death or serious injury to pool users, installers or others due to electrical
shock, and may also cause damage to property. Always disconnect the power to
the pool light at the circuit breaker before servicing the light. Failure to
do so could result in death or serious injury to serviceman, pool users or
others due to electrical shock.
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
iv
IMPORTANT WARNING AND SAFETY INSTRUCTIONS
Water temperature in excess of 100° F (37.7° C) may be hazardous to your
health. Prolonged immersion in hot water may induce hyperthermia. Hyperthermia
occurs when the internal temperature of the body reaches a level several
degrees above normal body temperature of 98.6° F (37° C.). Effects of
hyperthermia include: (1) Unawareness of impending danger. (2) Failure to
perceive heat. (3) Failure to recognize the need to leave the spa. (4)
Physical inability to exit the spa. (5) Fetal damage in pregnant women. (6)
Unconsciousness resulting in danger of drowning. The use of alcohol, drugs, or
medication can greatly increase the risk of fatal hyperthermia in hot tubs and
spas.
A pool or spa pump must be installed by a qualified pool and spa service
professional in accordance with the current National Electrical Code and all
applicable local codes and ordinances. Improper installation may create an
electrical hazard which could result in death or serious injury to pool users,
installers, or others due to electrical shock, and may also cause damage to
property.
The use of alcohol, drugs, or medication can greatly increase the risk of
fatal hyperthermia in hot tubs and spas. This product is intended to control
heaters with built-in high limit circuits ONLY. Failure to do so may cause
property damage or personal injury. Do not use this product to control an
automatic pool cover. Swimmers may become entrapped underneath the cover. For
units intended for use in other than single-family dwellings, a clearly
labeled emergency switch shall be provided as part of the installation. The
switch shall be readily accessible to the occupants and shall be installed at
least five (5) feet (1.52 m) away, adjacent to, and within sight of, the unit.
Except for listed spa-side remote controls, install a minimum of five (5) feet
(1.52 m) from the inside wall of the pool and spa.
The electrical supply for this product must include a suitably rated switch or
circuit breaker to open all ungrounded supply conductors to comply with the
current National Electrical Code (NEC), NFPA 70 or the Canadian Electrical
Code (CEC), CSA C22.1. All applicable local installation codes and ordinances
must also be adhered to. The disconnecting means must be readily accessible to
the tub occupant but installed at least five 5ft. (1.52 m), (Canada 3 m (9.75
ft) from the inside wall of the pool.
Use only copper supply conductor’s rated for 60C/75C sized based on ampacity
to support all loads (refer to NEC tables). Load center input supply to be
protected by 150 Amp Maximum, 240 VAC Main Circuit Breaker.
For information about the Virginia Graeme Baker Pool and Spa Safety Act,
contact the Consumer Product Safety Commission at
301-504-7908 or visit www.cpsc.gov.
NOTE: Always turn off all power to the pool pump before installing the cover
or working on any suction outlet.
Two Speed Pump Controls Notice (Title 20 Compliance) Please read the following
important Safety Instructions – When using two-speed pumps manufactured on or
after January 1, 2008, the pump’s default circulation speed MUST be set to the
LOWEST SPEED, with a high speed override capability being for a temporary
period not to exceed one normal cycle, or two hours, whichever is less.
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
v
IMPORTANT WARNING AND SAFETY INSTRUCTIONS
FCC Standard – 47 CFR Part 15, Subpart C (Section 15.247). This version is
limited to chapter 1 to chapter 11 by specified firmware controlled in the
U.S.A.
Canada – Industry Canada (IC) – The IntelliChlor device complies with RSS210
of Industry Canada. (1999). Operation is subject to the following two
conditions: (1) this device may not cause interference, and (2) this device
must accept any interference, including interference that may cause undesired
operation of the device.
Instruction to user – The IntelliChlor device has been tested and found to
comply with the limits for a Class B digital device, pursuant to Part 15 of
the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. The IntelliChlor
device generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this device does
cause harmful interference to radio or television reception, which can be
determined by switching the device off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
· Reorient or relocate the receiving antenna. · Increase the separation
between the equipment and receiver. · Connect the equipment into an outlet on
a circuit different from that to which the receiver is
connected. · Consult the dealer or an experienced radio/TV technician for
help. Note: The user is cautioned that changes and modifications made to the
IntelliChlor SCG device without the approval of the manufacturer could void
the user’s authority to operate this equipment.
General Installation Information
1. All work must be performed by a licensed electrician, and must conform to all national, state, and
local codes.
2. Install to provide drainage of compartment for electrical components.
3. If this system is used to control underwater lighting fixtures, a ground- fault interrupter (GFCI) must
be provided for these fixtures. Conductors on the load side of the ground- fault circuit-interrupter
shall not occupy conduit, junction boxes or enclosures containing other conductors unless such
conductors are also protected by a ground-fault circuit-interrupter. Refer to local codes for details.
4. A terminal bar stamped
is located inside the supply terminal box. To reduce the risk of electric
shock, this terminal must be connected to the grounding means provided in the electric supply
service panel with a continuous copper wire equivalent in size to the circuit conductors supplying
this equipment (no smaller than 12 AWG or 3.3 mm). The bonding lug(s) provided on this unit
are intended to connect a minimum of one No. 8 AWG for US installation and two No. 6 AWG for
Canadian installations solid copper conductor between this unit and any metal equipment, metal
enclosures or electrical equipment, metal water pipe, or conduit within 5 feet (1.5 m) of the unit.
5. The electrical supply for this product must include a suitably rated switch or circuit breaker to open
all ungrounded supply conductors to comply with in accordance with the current National Electrical
Code (NEC), NFPA 70 or the Canadian Electrical Code (CEC), CSA C22.1. All applicable local
installation codes and ordinances must also be adhered to. The disconnecting means must be
readily accessible to the tub occupant but installed at least 10 ft. (3.05 m) from the inside wall of
the pool.
6. GAS HEATER: This automation control system is designed to supply high voltage (120 VAC / 240
VAC) to a gas heater and override the thermostat in the heater’s control circuit. This automation
control system is intended to control gas heaters with a high temperature limit switch(s) safety
circuit.
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
vi
Pentair Water Pool and Spa® IMPORTANT SAFETY INSTRUCTIONS
For Installation of Electrical Controls at Equipment Pad (ON/OFF Switches,
Timers and Automation Power Center)
Install all electrical controls at equipment pad, such as on/off switches,
timers, and control systems, etc. to allow the operation (start-up, shut-down,
or servicing) of any pump or filter so the user does not place any portion of
his/her body over or near the pump strainer lid, filter lid or valve closures.
This installation should allow the user enough space to stand clear of the
filter and pump during system start-up, shut down or servicing of the system
filter.
CAUTION! INSTALL POWER CENTER TO ALLOW USER ENOUGH SPACE TO STAND CLEAR OF
PUMP AND FILTER WHEN SERVICING.
HAZARDOUS PRESSURE: STAND CLEAR OF PUMP AND FILTER DURING START-UP
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
1
Section 1
EasyTouch® and IntelliTouch® Control System Load Center and Power Center
Overview
Load Center and Power Center Description Load Center with sub-panel
(EasyTouch® and IntelliTouch® Control System): A Load Center enclosure
provides a built-in a 120 VAC/240 VAC 150 AMP circuit breaker base (sub-panel)
for highvoltage power relays, transformer, and low voltage circuit breakers. A
Load Center can be factory configured for an EasyTouch Control System (8 or 4
auxiliary relays) or IntelliTouch Control System (for Personality Interface
Kits, see page 33) automation control system. The optional IntelliChlor Salt
Chlorine Generator (SCG) transformer is available in the Load Center
enclosure. The Load Center dimensions are 26″ H x 17″ W x 5¼” D.
EasyTouch / IntelliTouch Control System Load Center
Note. For EasyTouch and IntelliTouch Control System product information, see
the Pentair Product Catalog.
Power Center without sub-panel (IntelliTouch Control System only): A Power
Center enclosure does not include a built-in circuit breaker base (subpanel).
An IntelliTouch control system automation control system Power Center is
factory configured (depending on the IntelliTouch control system Personality
interface kit. Multiple Power Centers can be connected together for additional
high voltage relay and transformer requirements. The optional IntelliChlor
Salt Chlorine Generator (SCG) transformer is available in the Power Center
enclosure. The Power Center dimensions are 20″ H x 17″ W x 5¼” D. Note: For
IntelliTouch systems (see page 33), up to three additional Power Centers (with
Expansion Center Personality kit, i5x or i10x) can be connected to a base
IntelliTouch Load Center or Power Center (models i5+3, i5+3S, i7+3, i9+3,
i9+3S, i10+3D. For more information about using multiple expansion centers,
refer to the IntelliTouch Systems User’s Guide (P/N 521075).
Main IntelliTouch Control System Load Center (i5+3, i5+3S, i7+3, i9+3, i9+3S, i10+3D)
Power Center (i5x or i10x),
(P/N 521214 with IntelliChlor SCG transformer)
Additional Expansion Center
Additional Expansion Center (3 maximum)
(P/N 521216 without IntelliChlor SCG transformer)
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
2
Load Center and Power Center Installation Overview
RISK OF ELECTRICAL SHOCK. BEFORE REMOVING THE HIGH VOLTAGE COVER PANEL FROM
THE ENCLOSURE switch the main power OFF into the home at the main circuit
breaker box.
Before installing the Load Center or Power Center read the following
guidelines carefully:
· The Load Center and Power Center must be installed at the equipment pad. ·
AC power for the Load Center or Power Center must be provided from the main
circuit
breaker panel located at the house. · All electrical equipment, except for UL
Listed spa-side remote switches, must be installed
no less than five (5) feet (1.5 m), (Canada, 3 mm (9.75 ft) from pool and/or
spa, andcomply with all national, state, and local codes (UL Listed spa-side
remote switches may be installed at near waterline). · Install the Load Center
or Power Center no less than five (5) feet (1.5 m) from pool, spa, and hot
tub. Additionally, the installation shall allow the user enough space to stand
clearof the filter and pump during system start-up, as explained on page vi. ·
The TYPE 3R “Rainproof” enclosure can be mounted outside or inside of a pool
equipment shed or other enclosure. · Before choosing the final location for
the enclosure, consider the length of all of the conductors that will have be
connected to the enclosure. Make sure to consider cable lengths for the
sensors to the load center location. The air temperature sensor cable isthree
(3) feet (91.44 cm) long and the water temperature sensor cable is 25 feet
(7.62 m)long. · Mount the load center on a flat vertical surface so the
conduit knockouts are located at the bottom of the enclosure. Upper and lower
brackets are provided to mount the enclosure. · DO NOT mount the enclosure
horizontally. Water can enter the conduit knockouts and cause damage to the
system and an electrical shock hazard. Install with conduit knockouts down. ·
Consider the load center location when routing conduit carrying the AC power
to the load center, and the conduit that will be run to the high voltage
equipment. · Install the load center so that drainage is provided for all
electrical components. · Motors should be listed for pool and spa applications
and have built-in thermal protection. · Allow at least 5 ft (1.5 m) of
unobstructed access to the front of the load center for the owner or service
personnel. · The load center provides grounding screw terminals for grounding
all equipment. All equipment including the load center enclosure must be
bonded to earth ground. · RS-
485recommendedcablelengthandAWG:UseaULapproved#22to#18AWGfour
conductorcabletotheLoadCenterorPowerCenter.#22AWGisrecommendedforruns
lessthan30ft.(9m),and20ft.(6m)AWGforrunsover30ft.(9m)).Thepreferredwire
colorschemeisRed,Yellow,Green,andBlack.Themaximumrecommendedcablelength
is200ft(61m).TheRS-485cablemustberuninaseparateconduit.
3
Load Center (with built-in Subpanel) EasyTouch® and IntelliTouch® Control Systems
The Load Center must be installed at the equipment pad. The AC power for the Load Center is provided from the main-panel circuit breaker located at the house.
EasyTouch or IntelliTouch Control
System Control Panel (EasyTouch
(shown)
Auxiliary, (1-4) relay locations
with additional five (5 ) relays or
2-Speed Pump relay (optional)
Control Panel / Low voltage compartment
3 AMP Low voltage (12 VAC, 18 VAC, 24 VAC) system circuit breakers
Optional 12 AMP Low voltage (24 VAC) circuit breaker (IntelliChlor Salt
Chlorine Generator)
Door Spring latch
Circuit breaker base 150 AMP
(Subpanel)
Low voltage raceway
(Air and water temperature sensors, mo-
torized valves, indoor control panel, spa side
remote, and wireless antenna)
Ground buss bar
AC Power Connector
Transfomrer foralSt Chilnoer Generator(SCG) Option
System transformer: 120VAC, 2.5A, 240VAC, 1.3A, 50/60 Hz
Optional IntelliChlor Salt Chlorine Generator (SCG) and power supply
transformer (SCG system only). 120VAC, 2A, 240VAC, 1A, 50/60 Hz
GFCI/GFCB knockout (approved rainproof cover required) – Standard Single gang
box.
Optional IntelliChlor (SCG) cell connector socket
Enclosure conduit knockouts (see page 7): 1¼”, 1″, ¾” and ½” conduit knockouts (lower and rear) for high voltage output. 1″ conduit knockout (lower) for high voltage input
Bonding lugs (two each) No.8 AWG (US) or No.6 AWG (Canada)
EasyTouch or IntelliTouch Control System Load Center (26″ H x 17″ W x 5¼” D)
Load center front door
High voltage cover panel
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
4
Power Center (without built-in Subpanel) – IntelliTouch® Control System Only
The IntelliTouch Control System Power Center (without sub-panel) must be
installed at the equipment pad. AC power to the Power Center is provided from
the an electrical circuit breaker panel (sub-panel) installed at the equipment
pad. The Power Center should be installed next to the
Control Panel/Low voltage compartment
IntelliTouch Control System
Control Panel
Auxiliary, (1-5) relay locations with additional four
relays or 2-Speed Pump relay
(optional)
Low voltage raceway (Air and water
temperature sensors, motorized valves, indoor
control panel, spa side remote, and wireless antenna)
Optional IntelliChlor Salt Chlorine
Generator power supply
transformer (SCG system only).
120VAC, 2A, 240VAC, 1A,
50/60 Hz
Optional Serial COM Port Expansion Board (Brackets support two boards)
IntelliChlor SCG circuit board (optional)
3 AMP Low voltage Control system circuit breakers (12 VAC, 18 VAC, 24 VAC)
Optional 12 AMP circuit breaker for IntelliChlor Salt Chlorine Generator (24 VAC)
Ground buss bar
Door spring latch
System transformer. 120VAC, 2.5A, 240VAC, 1.3A, 50/60 Hz
GFCI/GFCB knockout (approved rainproof cover required)
Optional IntelliChlor (SCG) cell connector socket
Enclosure conduit knockouts (see page 7): 1¼”, 1″, ¾” and ½” conduit knockouts (lower and rear) for high voltage output. 1″ conduit knockout (lower) for high voltage input
Bonding lugs (two each) No.8 AWG (US) or No.6 AWG (Canada)
IntelliTouch Control System Power Center (20″ H x 17″ W x 5¼” D) (Front view with door and high voltage cover panel removed)
5
Preparing the Load Center and Power Center Enclosure
BEFORE INSTALLING THE LOAD CENTER AND POWER CENTER, ALWAYS SWITCH OFF THE MAIN
POWER into the home at the main circuit breaker box.
Before mounting the Load Center or Power Center, first remove the front door
and the high voltage cover panel to access the enclosure conduit knockouts and
low voltage raceway (see pages 3 and 4).
To remove the Load Center or Power Center high voltage cover panel:
1. Unpack the Load Center or Power Center from the shipping carton. 2.
Unlatch the front door spring latch and open the front door. 3. Remove the two
(2) retaining screws securing the high voltage cover-panel. Remove the
HIGH VOLTAGE COVER PANEL from the enclosure. 4. For new installation, proceed
with:
· Mounting the Load Center and Power Center, page 6 · Connecting AC Power to
the Load Center and Power Center, page 7 · Electrical Wiring and High Voltage
Connections, page 8 · Installing Conduit and Conductors to the Enclosure, page
8 · Accessing the EasyTouch or IntelliTouch Control Circuit Board and
Electronics, page 10 · Connecting a Standard Gas Heater (EasyTouch and
IntelliTouch System), page 17 5. After electrical connections have be
completed, reinstall the high voltage panel and secure it with the two (2)
retaining screws.
Front door
Retaining screws (for High Voltage Cover Panel)
High Voltage Cover Panel
Load Center (front view)
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
6
Mounting the Load Center and Power Center
Mount the Load Center (EasyTouch® Control System enclosure show below) and
Power Center on a flat vertical surface, such as a wall or post at eye level,
at least 5 ft. (1.5 m), (Canada 3 m (9.75 ft)) from the pool, spa or hot tub.
To mount the Load Center and Power Center:
1. Position the enclosure against a vertical flat surface. If wall anchors
are being used, support the enclosure in position (horizontally level and
square) against the surface and mark the bracket hole pattern on the wall.
2. Secure the enclosure with three (3) screws in the top and lower mounting
bracket holes. If using wall anchors, drill and set the anchors and secure the
enclosure with screws. Top mounting bracket screw holes
Lower mounting bracket screw holes Load Center (front view)
(front door and high voltage panel removed)
7
Connecting AC Power to the Load Center and Power Center
Before installing electrical conduits and connecting AC power to the Load
Center and Power Center enclosure, read the following recommended guidelines:
TO AVOID AN ELECTRICAL HAZARD AND EQUIPMENT DAMAGE TO THE ENCLOSURE AND
INTELLICHLOR CELL: FIRST DISCONNECT AC POWER TO THE ENCLOSURE BEFORE
CONNECTING THE INTELLICHLOR COMMUNICATION CABLE.
· Determine the number of low and high voltage circuits being used in the Load
Center or Power Center. The conduit size and runs needed based on the
conductor size, and the number of conductors within the conduit. The enclosure
conduit knockouts sizes are 1¼”, 1″, ¾” and ½”.
· Enclosure conduit knockouts for AC power are located on the sides, bottom
and back of the enclosure. Conduit knockouts sizes for AC power are: 1¼”, 1″,
½” and ¾”. It is recommended to use 1¼” x 1″ conduit for the main AC power
conductors.
· The Load Center and Power Center enclosure must be located a minimum of 5
ft. (1.5 m), (Canada 3 m (9.75 ft)) from the inside wall of pool or spa.
Remove the enclosure conduit knockouts as needed: · Low voltage raceway has
two ½” x ¾” conduit knockouts located on the left side and rear of the
enclosure. · High voltage compartment has twelve ½” x ¾”, five ¾” x 1″ and two
1¼” x 1″ conduit knockouts located on the bottom of the enclosure.
Note: Subpanel wiring: 14 AWG minimum copper conductors for relays and other
equipment sized according to the ampacity of the load
1¼” x 1″
Optional GFCI/ GFCB Receptacle knockout (standard single gang type 3R cover required)
½” x ¾” conduit knockout (2x) Low voltage only
¾” grommet fittings (4x) (low voltage and
sensor conductors)
½” x ¾” rear conduit knockout (5x)
¾” x 1″ conduit knockout (5x)
1¼” x 1″ conduit knockout
½” x ¾” conduit knockout (8x)
NOTE: DO NOT ROUTER LOW VOLTAGE CONDUCTORS (VALVES, SENSORS etc.) THROUGH THE
HIGH VOLTAGE KNOCKOUTS ON BOTTOM OF LOAD CENTER.
EasyTouch Load Center (lower, side and back panel knockouts)
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
8
Electrical Wiring and High Voltage Connections
Main AC Power Connection (Circuit Breaker Subpanel) The EasyTouch® and
IntelliTouch® Control System Load Center with circuit breaker sub-panel is
rated for 150 AMP maximum Single Phase (3 conductor). Run properly rated
conductors (L1,L2, N, and GROUND) from the primary house electrical panel to
the main AC power connections on the Load Center circuit breaker base (see
page 27). The connection at the main house panel should be to a 240 VAC
circuit breaker rated at 150 AMP maximum. Grounding and Bonding Connections
Connect a ground conductor from the primary house electrical panel to the Load
Center or Power Center GROUND BUS BAR (see page 27). Also ground each piece of
high voltage (120 VAC or 240VAC) equipment that is connected to the Load
Center or Power Center relays or circuit breakers. Also connect the Load
Center and Power Center to the pool bonding system using 8 AWG (6 AWG for
Canada) conductor. There are two (2) GROUND LUGS provides on the bottom of the
Load Center and Power Center. Circuit Breakers (For Load Center with sub
panel) Circuit Breakers are to be supplied and installed by the site
installer. For recommended circuit breaker types, refer to the circuit breaker
chart on the inside front door of the Load Center and Power Center. Be sure to
follow all manufacturer’s circuit breaker rating requirements. Some pool
equipment require connection to ground fault circuit breakers (GFCI). Check
local and NEC (CEC) codes for these requirements. Note: For recommended field
conductor gauge usage, refer to conductor size listed on the circuit breaker
label.
Installing Conduit and Conductors to the Enclosure
Before installing electrical conduit to the enclosure, read the following
recommended guidelines:
NOTE: All electrical installation, including electrical wiring methods and
materials used to complete the electrical installation of the EasyTouch and
IntelliTouch Control System Pool/Spa control system MUST BE PERFORMED BY A
SERVICE PROFESSIONAL AND/OR UNDER DIRECT SUPERVISION OF A QUALIFIED
ELECTRICIAN in accordance with the National Electrical Code or the Canadian
Electric Code, as well as any local electrical codes in effect at the time of
installation. Refer to NEC 680 (b) or CEC 687-060, 062, and 066 for further
details.
· Determine the number of low and high voltage circuits being used in the
EasyTouch and IntelliTouch Control System Load Center and Power Center. The
conduit size and runs is based on the conductor size, and the number of
conductors within the conduit. The number of pieces of equipment to be
controlled will dictate the size of the conduit. DO NOT RUN HIGH VOLTAGE AND
LOW VOLTAGE CONDUCTORS IN THE SAME CONDUIT.
· Use 14 AWG minimum to 6 AWG maximum 140°/158° F (60°/70° C) or better copper
conductors for relay circuits depending on the load requirement. Be sure to
follow all NEC regulation safety codes for the number and size of conductors
that can be installed in various sizes of conduit.
· Supply conductor must be sized to support all loads. The maximum supply
current must NOT exceed 150 AMP at 120 VAC/240 VAC.
· Supply circuit must be protected by suitable breaker rated no higher than
150 AMP. If one relay is used for more than one device, verify that the total
current draw (all equipment) does not exceed the current rating of the
circuit.
· The EasyTouch and IntelliTouch automation control circuit board requires 120
VAC, 3A power to operate the control logic circuits and the optional
IntelliChlor Salt Chlorine generator. This power should be connected to one of
the circuit breakers in the sub-panel.
9
· To avoid obstruction into the Load Center and Power Center, when using
electrical conduit complete the installation of the conduit before concrete is
poured. Also, underground conduit should be positioned in well compacted soil.
Ensure that all conduit joints are well sealed and watertight.
To install electrical conduit and conductors as needed
TO AVOID AN ELECTRICAL HAZARD – Do not connect the power source conductors to
the Load Center circuit breaker until all electrical connections for all loads
(heaters, pumps, motorized valves, and lights etc.) have been completed.
· Use the rectangular knockout on the right side of the Load Center and Power
Center enclosure to mount an approved GFCI or GFCB with rainproof type 3R
cover (supplied by installer) for direct connection of underwater pool and spa
lights.
· Use the one of the three low voltage raceway 3/4″ holes located on the
underside of the enclosure for the temperature sensor conductors (see page 7).
NOTICE: For the AC supply conductor into the Load Center and Power Center from the main circuit breaker at the house, use three conductors, one each for red, black, and white (or red, red and black for 240 VAC). The maximum load is 150 AMP at 120 VAC/240 VAC 60 Hz/50 Hz. These conductors should be secured to supply side of circuit breaker base. For the main AC power conduit, it is recommended to use the 1¼” x 1″ conduit knockout located directly under the enclosure circuit breaker (see page 7).
EasyTouch Load Center Wiring Diagram (for complete wiring details, see page 32 and inside front door of load center)
EasyTouch Control
System Load Center
12
FILTER PUMP RELAY
· For Wiring InteliChlor
(SCG) Transformer to
System Transformer
Filter Pump Relay, see page 24.
· For Rewiring the System Transformer for 240 VAC, see page 27.
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
10
Accessing the EasyTouch® or IntelliTouch® Control Circuit Board and
Electronics
The main EasyTouch and IntelliTouch Control System circuit board is located
behind the control panel located on the front of the Load Center and Power
Center. The main circuit board provides connectors for the auxiliary relays,
valve actuators and sensors. To access the circuit board connectors, fold down
the main control panel. Note: For IntelliTouch Personality circuit board
models, see pages 40-42. To access the control circuit board connectors:
1. Loosen the two retaining screws securing from the top edge of the control
panel. 2. Fold down the control panel to access the rear of the circuit board
for the electrical
connections. 3. For relay, valve actuators and sensors installation and
connection instructions see the
following: · Connecting EasyTouch System Relays, page 11 · Connecting
IntelliTouch System Relays, page 12 · Installing Valve Actuators, page 13 ·
Installing and Connecting Temperature Sensors, page 15 4. After electrical
connections have be completed, close the control panel and tighten the two
Retaining screw Retaining screw
Control panel (fold down to access circuit board and low voltage compartment)
Load Center (front view) (front door and high voltage compartment panel
removed)
11
Connecting EasyTouch® Control System Relays
The EasyTouch Control System Load Center includes four or eight pre-installed
relays. To connect the pre-installed relay cable plugs to the EasyTouch
control system circuit board:
· Route each of the power relay cable plugs up into the low voltage
compartment to the EasyTouch circuit board. Insert the relay plugs into the
two-pin sockets on the circuit board, beginning with FLTR PUMP, then AUX1,
AUX2, AUX3, and AUX4. For the actuator two-pin socket locations, see below.
For the EasyTouch system wiring diagram, see page 31 or the load center front
door inside panel.
Note: Install the optional Two-Speed Pump relay (P/N 520198) cable plug into
the 2SPD two-pin socket on the EasyTouch control system circuit board. For
installation and operation information, refer to the
Auxiliary relay locations Optional relay positions
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
12
Connecting IntelliTouch® Control System Relays
There are five (5) pre-installed relays in the IntelliTouch® Control System
Load Center and Power Center. To connect the pre-installed relay cable plugs
to the IntelliTouch control system Personality circuit board:
· Route the power relay cable plugs up into the low voltage compartment to the
Personality circuit board. Insert the plug into the two-pin sockets, beginning
with FLTR PUMP, then AUX1, AUX2, AUX3, and AUX4. For the two-pin socket
locations, refer to the diagram shown below. For IntelliTouch control system
system wiring diagrams, see pages 41-43. Note: For optional relays; insert
each optional auxiliary relay plug into the one of the twopin sockets,
beginning with AUX5, AUX6, AUX7 and AUX8.
· Dual Equipment: Pool and Spa with Dual Sets of Equipment The IntelliTouch
control system i10+3D (P/N 521222) is designed to operate two sets of pool
equipment. Each set of a equipment (Pool or Spa) can control one temperature
setting. This IntelliTouch control system Personality Kit can control up to 10
pumps and/or lighting circuits, plus two heater circuits. The Personality Kit
includes, eight auxiliary circuits plus a filter pump.
· Single Equipment: Pool Only or Spa Only Applications The IntelliTouch
i5S+3 (P/N 521223) and i9+3S provide advanced automation for a single body of
water. The i5S+3 Personality Kits includes four auxiliary circuits plus filter
pump operation. Five relays are included in the Load Center. The i9+3S (P/N
521224) Personality Kits includes eight auxiliary circuits plus filter pump
operation and the +3 option (create a Feature Macro circuit for valve
actuators without using an existing output aux circuit). Four relays are
included in the Personality kit and five in the Load Center. You can create a
Feature circuit for valve actuators without using an existing output auxiliary
circuit, and special light functions for color lighting. This model also
allows HI-TEMP and LO-TEMP settings.
IntelliTouch Personality Circuit Board
Auxiliary relay locations
Optional relay positions
Note: Install the optional Two-Speed Pump relay (P/N 520198) cable plug into the 2SPD two-pin socket on the Personality board. For installation and operation information, refer to the
13
Installing Valve Actuators
The EasyTouch® and IntelliTouch® Control Systems can control up to four
automatic valve actuators. Two of the valve outputs are dedicated to the
pool/spa intake (INTAKE) and return (RETURN) valves. Valve A or Valve B
actuators are for general purpose use (solar, water-feature, in-floor cleaner,
etc.). Using the IntelliTouch control system Valve Expansion Board, an
addition three actuators can be added to the IntelliTouch Personality circuit
board (for more information, see next page). For EasyTouch and IntelliTouch
control systems shared equipment systems there are two motorized valve
actuators (CVA-24T, P/N 263045) provided in the kit.
To install the valve actuator (two-way valve example shown):
1. Remove the valve knob, handle and the four screws, from the valve cover (indicated with arrows).
2. Align the splines of the actuator shaft over the shaft of the valve.
3. If the actuator is not aligned with the mounting holes on the valve cover, rotate the actuator (while still attached to the valve) until the actuator is positioned correctly over the valve.
4. Secure the actuator with the screws provided. Only use self-tapping screws when required.
5. Mount the valve handle and knob onto the actuator.
Screw
Valve actuator
Screw
Screw
Adjusting the valve position (3-way valve shown below) If the valve rotates to the wrong position, adjust the switch on the back of the actuator between ON1 and ON2 positions. This will rotate the valve to the correct position. The following diagram shows the standard plumbing and valve actuator position.
Valve Handle Operation: To reposition the valve handle: Rotate the handle to
the desired “OFF” position. The diverter valve handle OFF indicator,
represents the current position of the valve’s internal diverter seal which
will stop the flow of water. The valve handle stop-pins determine the position
of the diverter valve’s internal seal to stop or allow water flow. Note: When
a motorized valve actuator is installed, stop-pins are not required.
Handle Stop-Pins Positions: The two movable stop-pins can be set to allow the
valve handle’s position to completely stop the flow of water, regulate a
limited flow, or allow the maximum flow. To set the stop-pins: Insert the
stop-pins in the pin holes according to the corresponding “degree indicator”
displayed on top of the handle. The stop-pin positions can be set to 180°,
L90° (left-side) and R90° (right side). Repositioning of either stop-pins
allows the handle to be set to any desired percentage of water flow.
PORT A
PORT C
OFF
OFF
Stop Pins Set for 180°
PORT B (Common Port)
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
14
6. At the Load Center or Power Center, route the cable up through the 1″
grommet and low voltage raceway to the circuit board (see page 3).
7. EasyTouch® Control System Circuit Board: Connect the Valve A actuator
cable plug into the INTAKE (suction) 3-pin socket, and Valve B actuator cable
plug into the RETURN three-pin socket on the right side of the EasyTouch
circuit board. Excess cable can be coiled in the enclosure low voltage raceway
left side compartment (see page 3). Do not coil the conductor in upper low
IntelliTouch® Control System Personality: Connect the Valve A actuator cable
plug into the INTAKE (suction) 3-pin socket, and Valve B actuator cable plug
into the RETURN three-pin socket on left side of the Personality circuit
board. Excess cable can be coiled in the enclosure low voltage raceway left
side compartment. Do not coil the conductor in upper low voltage compartment.
For valve actuator circuit board socket location see below and pages 41-42.
For plumbing requirements, see Item 2 and 3 on page 44. IntelliTouch Control
System Optional Valve Module Expansion Board: Using a Valve Module Expansion
board (P/N 520285), three additional valve actuators (VALVE C, D and E) can be
added to the system. The expansion board attaches to the edge of the
IntelliTouch Personality board. For installation and operation information,
refer to the IntelliTouch Valve Actuator Installation Guide (P/N 520294).
IntelliTouch Control System Personality Circuit Board
15
Installing and Connecting Temperature Sensors
Water Temperature Sensor
To install the water sensor: 1. Select a convenient location to mount the
water sensor in the plumbing system between the filter pump and filter. Drill
a 3/8″ diameter hole in one side of the pipe,
2. Insert tip of sensor into the hole. Use the band clamp to secure the
sensor to the pipe. Tighten the clamp just enough so that the o-ring begins to
flatten. Do not overtighten
3. Fasten the cable to the plumbing with cable ties.
4. Run 22 AWG two-conductor cable (included in kit) between the sensor and
the enclosure. Route the cable up through the low voltage raceway to the
circuit board.
5. Cut off the excess conductor and the strip conductors ¼ inch. Use
waterproof connectors (provided) to connect the sensor to cable.
EasyTouch® Control System: Insert the conductors into the WATER SENSOR screw
terminals (J21) on right-side of the motherboard. For sensor circuit board
screw terminal location (see below and page 31).
IntelliTouch® Control System: Insert the conductors into the WATER SENSOR
screw terminals (J5) on right-side of the Personality circuit board. For
sensor circuit board screw terminal location (see below and pages 41 and 42).
Ambient Air Temperature Sensor (for freeze protection)
To install the air sensor: 1. Mount the sensor in the open air, in a shaded
area, away from air conditioners. During the winter months, to avoid freeze
damage to pool and spa equipment, mount the air sensor in a shaded area to
assure proper temperature readings. The main screen displays the current
ambient air temperature.
2. Fasten the cable to the plumbing with cable ties.
3. Run 22 AWG two-conductor cable (included in kit) between the sensor and
the enclosure. Route the cable up through the low voltage raceway to the
circuit board.
5. Cut off the excess conductor and the strip conductors ¼ inch. Use
waterproof connectors (provided) to connect the sensor to cable.
EasyTouch Control System: Insert the conductors into the AIR screw terminals
(J21) on right side of the EasyTouch circuit board. For sensor circuit board
screw terminal location (see below and page 31).
IntelliTouch Control System: Insert the conductors into the AIR screw
terminals (J5) on right side of the Personality circuit board. For sensor
circuit board screw terminal location, see below and pages 41 and 42.
EasyTouch Control System Circuit Board
ersonality
EasyTouch Control System Circuit Board
IntelliTouch Control System Personality Circuit Board
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
16
Solar Temperature Sensor (Optional)
Run a two-conductor cable between the sensor and the EasyTouch® Control System
circuit board in the Load Center. To install the solar sensor:
1 Mount the sensor on a flat surface, with the same exposure to sun as the
solar collectors (next to the collectors is recommended) or any sunny
location. Do not let the sensor touch the panels. WARNING: DO NOT DRILL HOLE
AND CLAMP SENSOR INTO SOLAR PIPE. For glazed panels, install the sensor
between collector and glazing.
2 If necessary, splice a two-conductor extension conductor to the sensor. Run
two-conductor cable between the sensor and the enclosure. Use waterproof
connectors to connect the sensor to the cable. Use twisted pair 20 AWG outdoor
rated sensor wiring and be sure the conductor connections are protected from
the environment. Use shielded cable for long runs or runs near other
electrical wiring.
3. Cut off the excess conductor and the strip back conductors ¼ inch. Use
waterproof connectors (provided) to connect the sensor to cable. EasyTouch
System: Insert the conductors into the SOLAR SENSOR screw terminals (J21) on
right side of the EasyTouch circuit board. For sensor circuit board screw
terminal location (see below and page 31). IntelliTouch System: Insert the
conductors into the SOLAR SENSOR screw terminals (J5) on right side of the
Personality circuit board. For sensor circuit board screw terminal location
(see below and pages 41 and 42).
EasyTouch Control System Circuit Board
EasyTouch Circuit Board
IntelliTouch® Control System Personality
17
Connecting a Standard Gas Heater
For EasyTouch® and IntelliTouch® Control System heater control, there are low
voltage dry contacts that can be connected to most gas heaters or heat pumps
with 24 VAC control circuits . The following connection instructions are for
gas heaters and heat pumps with low voltage thermostats.
To connect the heater thermostat cable plug to the EasyTouch or IntelliTouch
control system circuit board: 1. Switch the power OFF to the heater. 2. Remove
the factory installed jumper from the heater’s “Ext Switch” connector. CAUTION
IMPORTANT: DO NOT disconnect or conductor around the thermostat, pressure
switch, high limit switch, or other safety devices. At the heater, connect the
conductors in accordance with heater manufacturer’s instructions. For older
heaters without instructions for remote operation, connect the conductors to
the Fireman’s switch connections in series with the thermostat, pressure
switch, and other safety switches. 3. Run a two-conductor cable from the
heater thermostat “Ext Switch” connector to the low voltage raceway to the
Personality board in the Load Center. NOTE: Use 221° F (105° C) temperature
rated conductor for connection to the heater. When connecting conductors
inside the heater, be cautious of HOT internal parts of the heater. Refer to
the minimum temperature rating for conductors recommended by the manufacturer.
See the heater owners manual for details. 4. Strip back the conductors ¼ in.
EasyTouch Control System: Insert the conductors into the GAS HEATER two-screw
terminals (J19) on the motherboard. For heater circuit board screw terminal
location, see below and page 31). IntelliTouch Control Personality circuit
board: Insert the two conductors into the GAS HEATER (J30) two-screw terminal
on the left side of the Personality circuit board. For heater circuit board
screw terminal location, see below and pages 41 and 42). CAUTION: Be sure that
the conductors from the heater to the Load Center or Power Center are not near
or touching any line voltage conductors in the heater. Failure to follow these
instructions may cause the heater to malfunction. 5. Set the Power (Thermostat
Select) switch to either “Pool” or “Spa.” 6. Set the “Pool” and “Spa”
thermostats to their maximum position.
J30
J19 EasyTouch Control System Circuit Board
IntelliTouch Control System Personality Circuit Board
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
18
Wiring Pentair UltraTemp® Heat Pump
Be sure to check the UltraTemp Heat Pump terminal block conductor colors and
pinouts (located on the back of the Auto Set board) before connecting it to
the EasyTouch® or IntelliTouch® Control System COM ports. The See the wiring
table below for the pin configuration.
IMPORTANT: On the UltraTemp heat pump AutoSet circuit board ONLY CONNECT PIN 3
(YELLOW) and PIN 2 (GREEN) to the EasyTouch and IntelliTouch Control System
COM port pins YELLOW and GREEN respectively. Do not connect pin 1 or pin 4 on
the AutoSet board or the COM port. These pins are not used.
COM port wire color
Descripion
UltraFlo pin number and wire color
PIN 4 (RED) (DO NOT USE)
+15 VDC
PIN 4 (DO NOT USE)
PIN 3 (YELLOW)
+ DATA
PIN 3 (YELLOW)
PIN 2 (GREEN)
– DATA
PIN 2 (GREEN)
PIN 1 (BLACK) (DO NOT USE) GROUND
PIN 1 (DO NOT USE)
Wiring Pentair IntelliFlo® Pumps
The RS-232 communication cable (provide with pump) consists of a 50 ft 22 AWG
four conductor low voltage cable. The EasyTouch and IntelliTouch control
system filter pump output is rated at 120 VAC, 15 AMP maximum. Check the
electrical rating marked on the pump motor before connecting it to the system.
To connect the IntelliFlo communication cable to the Load Center or Power
Center (IntelliTouch only):
1. Switch AC power OFF to the load center or power center at the main house
circuit breakers.
2. Run the communication cable from the pump to the enclosure. 3. Insert the
cable conductors into the one of the plastic grommet fittings, located on the
lower left side of the enclosure and pull the cable up through the low voltage
to the EasyTouch or IntelliTouch circuit board. 4. Strip back the outer jacket
four (4) inches. Strip back each conductor a ¼-inch.
19
5. EasyTouch: Insert the conductors into the COM PORT (J20) screw terminals
located on the top of the EasyTouch circuit board (see diagram below). Secure
the conductors with the screws. For wiring details, refer to the pin
configuration shown below. Note: Multiple conductors may be inserted into a
single screw terminal.
IntelliTouch COM PORT (J7/J8) screw terminal
COM Port screw terminal connector
IntelliFlo (2-wire cable)
EasyTouch Control System Circuit Board
Pin configuration
6. IntelliTouch® Control System: Insert the conductors into the either of the COM PORTS (J7 and J8) screw terminals located on the left side of the Personality circuit board. Secure the conductors with the screws. For wiring details, refer to the pin configuration shown below. Note: Multiple conductors may be inserted into a single screw terminal.
J7 J8 IntelliTouch Control System Personality Circuit Board
IntelliTouch COM PORT (J7/J8) screw terminal
Pin configuration
COM Port screw terminal connector
IntelliFlo (2-wire cable)
2 (GRN)
GREEN (Pin 6)
3 (YEL)
YELLOW (Pin 7)
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
20
Connecting IntelliChlor (SCG) Power Cord to the Enclosure
The IntelliChlor (SCG) cell power cord is connected to the socket on the
bottom of the EasyTouch or IntelliTouch enclosure. Note: Only one IntelliChlor
cell can be installed per system.
BEFORE REMOVING THE HIGH VOLTAGE COVER PANEL FROM THE LOAD CENTER OR POWER
CENTER, switch the main power OFF into the home at the main circuit breaker
box and also switch OFF the main power to the Load Center or Power Center.
TO AVOID AN ELECTRICAL HAZARD AND EQUIPMENT DAMAGE TO THE ENCLOSURE AND
INTELLICHLOR CELL: FIRST DISCONNECT AC POWER TO THE ENCLOSURE BEFORE
CONNECTING THE INTELLICHLOR CELL POWER CABLE TO THE ENCLOSURE SOCKET.
To connect the IntelliChlor power cord to the Load Center or Power Center
(IntelliTouch only): 1. Switch AC power OFF to the Load Center or Power
Center. 2. Align the four pins of the IntelliChlor cell power cord connector
with the socket on the bottom of the enclosure and insert the cord connector
into the socket. 3. Rotate the socket nut until it locks the connector in
place. Do not over tighten the nut (hand tighten only). 4. Switch AC power ON
to the load center.
IntelliChlor SCG Power Cable Con-
nector
Connector socket nut
To IntelliChlor cell
EasyTouch/IntelliTouch Control System Load Center
IntelliChlor SCG Power Cable Con-
nector
Connector socket nut
To IntelliChlor cell
IntelliTouch Control System Power Center (with IntelliChlor SCG option)
21
Connecting IntelliChlor® (SCG) COM Port Cable
The IntelliChlor (SCG) communicates from the EasyTouch® and IntelliTouch®
Control System circuit board to the IntelliChlor (SCG) circuit board via an
RS-485 communications four conductor, 22 AWG or larger cable. This cable
(provided in kit) connects to both the IntelliChlor (SCG) circuit board COM
port terminal and the EasyTouch or IntelliTouch control system circuit board
COM port.
TO AVOID AN ELECTRICAL HAZARD AND EQUIPMENT DAMAGE TO THE ENCLOSURE AND
INTELLICHLOR CELL: FIRST DISCONNECT AC POWER TO THE ENCLOSURE BEFORE
CONNECTING THE INTELLICHLOR COMMUNICATION CABLE.
To connect the IntelliChlor (SCG) COM port cable (see page 22 for connector
pinouts/color match):
1. Switch AC power OFF to the enclosure at the main house panel circuit
breaker. 2. Loosen the two retaining screws securing the EasyTouch or
IntelliTouch control system
control panel. Lower the control to allow access the low voltage compartment
behind the control panel circuit board as shown below.
3. EasyTouch Control System circuit board: Connect the cable to COM port #1
on the IntelliChlor (SCG) circuit board. Connect the other end of the cable to
the EasyTouch control system COM port (J20) screw terminal located on the top
of the EasyTouch control system circuit board (see screw terminal location on
next page). Note: Any of the three COM ports on the EasyTouch circuit board
can be used for the IntelliChlor (SCG). IntelliTouch Control System
Personality circuit board: Connect the cable to COM port #1 on the
IntelliChlor (SCG) circuit board. Connect the other end of the cable to either
of the COM ports (J7 and J8) screw terminals located on the left side of the
Personality circuit board (see screw terminal location on next page).
4. After electrical connections have be completed, close the control panel
and tighten the two retaining screws.
5. Switch AC power ON to the load center.
Retaining screw
Connect to COM port on EasyTouch or IntelliTouch main circuit board
Load Center (front view)
Retaining screw
Control panel (fold down to access circuit board and low voltage compartment)
IntelliChlor SCG circuit board
(Use COM port #2, #3 for optional equipment, e.g. IntelliFlo pump, wireless control panel antenna)
IntelliChlor power cord
Communication cable
EasyTouch/IntelliTouch Control System Load/Power Center (with IntelliChlor SCG option) (Control Panel not shown)
COM Port #1
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
22 Connecting IntelliChlor® (SCG) COM Port Cable (continued)
EasyTouch® Control System Circuit Board
EasyTouch COM PORT (J20) screw terminal
IntelliTouch Control System COM PORT (J7/J8) screw terminals
IntelliTouch® Control System Personality Circuit Board
23
Wiring a Salt Chlorine Generator
Be sure to check each conductor color between the salt chlorine generator and
the EasyTouch®, or IntelliTouch® Control System load/power center as shown in
the following wiring tables. Commonly used salt chlorine generator wiring is
shown but you should still verify with the manufacturers documentation.
Failure to connect the salt chlorine generator properly can permanently damage
the EasyTouch and IntelliTouch control system and/or salt chlorine generator.
Wiring Description (EasyTouch, IntelliTouch COM Port to the IntelliChlor® SCG
Circuit board COM Port)
SCG COM Port Wiring Color Connection
Descripion
From IntelliChlor SCG Power Center COM Port
RED
+15 VDC
RED
YELLOW
+ DATA
YELLOW
GREEN
– DATA
GREEN
BLACK
GROUND
BLACK
Wiring Description (IntelliTouch Control System Only) (Hayward® or Jandy® Chlorinator to Pentair Load Center COM
Port)
Hayward or Jandy Chlorinator Wiring Color Connection
Descripion
From IntellliTouch Control System COM Port
RED
+15 VDC
RED
BLACK
+ DATA
YELLOW
YELLOW
– DATA
GREEN
GREEN
GROUND
BLACK
Wiring IntelliChem® Controller
Be sure to check each conductor color between IntelliChem Controller and the
EasyTouch or IntelliTouch control system load/power center as shown in the
following wiring table.
Wiring Description (IntelliChem COM Port to EasyTouch and IntelliTouch COM
Port)
IntelliChem Controller COM Port (J7) wiring color connection
Descripion
From EasyTouch or IntelliTouch Control System COM Port
RED
+15 VDC
RED
YELLOW
+ DATA
YELLOW
GREEN
– DATA
GREEN
BLACK
GROUND
BLACK
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
24
Wiring IntelliChlor (SCG) Transformer to Filter Pump Relay
IMPORTANT! IntelliChlor (SCG) AC transformer wiring Instructions: When using
the EasyTouch or IntelliTouch automation control system with the IntelliChlor
(SCG) option , be sure the IntelliChlor (SCG) AC transformer conductors are
connected to the PUMP SIDE OF THE MAIN FILTER PUMP RELAY located in the
enclosure (see page 25). This ensures that the IntelliChlor cell produces
chlorine only when the main filter pump is on. This method does not require a
ground fault circuit-interrupter (GFCI) for the IntelliChlor power center.
BEFORE REMOVING THE HIGH VOLTAGE COVER PANEL FROM THE LOAD CENTER OR POWER
CENTER, switch the main power OFF into the home at the main circuit breaker
box and also switch OFF the main power to the Load Center or Power Center.
TO AVOID AN ELECTRICAL HAZARD AND EQUIPMENT DAMAGE TO THE ENCLOSURE AND
INTELLICHLOR CELL: FIRST DISCONNECT AC POWER TO THE ENCLOSURE BEFORE
CONNECTING THE INTELLICHLOR COMMUNICATION CABLE.
To connect the IntelliChlor (SCG) transformer conductor to the main filter
pump relay: 1. Switch AC power OFF to the enclosure at the main house panel
circuit breaker. 2. Loosen the two retaining screws securing HIGH VOLTAGE
FRONT COVER PANEL. Remove the panel from the enclosure (see illustration
below). 3. Locate the MAIN FILTER PUMP RELAY. Connect the IntelliChlor SCG
transformer conductors to the LOAD SIDE of the relay as shown on page 25. 4.
After electrical connections have be completed, install the HIGH VOLTAGE FRONT
COVER PANEL and tighten the two retaining screws to secure in place. 5. Switch
AC power ON to the enclosure.
CONNECT SCG TRANSFORMER TO FILTER PUMP RELAY
CONNECT SCG TRANSFORMER TO FILTER PUMP RELAY
Retaining screws
HIGH VOLTAGE FRONT COVER PANEL
Load Center (with SCG option)
IntelliTouch Power Center (with SCG option)
IntelliChlor (SCG) Transformer
25
AC power cord connects to IntellilChlor SCG circuit board in enclosure)
IntelliFlo pump connects to EasyTouch or IntelliTouch COM port
LOAD SIDE LOAD SIDE
TO AUX (FILTER PUMP) SOCKET (ON EASYTOUCH or INTELLITOUCH CIRCUIT BOARD)
FILTER PUMP RELAY
(IN POWER CENTER)
LINE SIDE LINE SIDE
Source voltage: 120 VAC or 240 VAC to circuit breaker sub-panel
LOAD SIDE (VOLTAGE) LOAD SIDE (VOLTAGE)
IntelliChlor SCG Transformer
EasyTouch or IntelliTouch Load/Power Center
2-SPEED PUMP OPTION
TO PUMP SOCKET ON CIRCUIT BOARD
2-SPD Filter Pump (wired for 120 or 240 VAC)
120 VAC
120 VAC
TO AUX SOCKET ON CIRCUIT BOARD
TO PUMP MOTOR TERMINALS
IntelliChlor SCG and Automation Load Center Connection Diagram
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
26
Rewiring the IntelliChlor SCG Transformer for 120VAC
The IntelliChlor power supply transformer located in the Load Center and Power
Center can be wired for 240 VAC at 1AMP (factory installed) or 120 VAC at 2AMP
50/60 Hz. The IntelliChlor transformer is pre-wired at the factory for 240 VAC
service. To rewire the IntelliChlor transformer and for 120 VAC:
BEFORE REMOVING THE HIGH VOLTAGE COVER PANEL FROM THE LOAD CENTER OR POWER
CENTER ENCLOSURE switch the main power OFF into the home at the main circuit
breaker box and also switch OFF the main power to the Load Center and Power
Center. 1. Switch the power OFF to the Load Center and Power Center. 2.
Unlatch the front door latch and open the front door. 3. Remove the two (2)
retaining screws securing the high voltage cover-panel. Remove the HIGH
VOLTAGE COVER PANEL from the enclosure (see illustration on page 5). 4. Rewire
the Transformer for 120 VAC as shown in the wiring diagram below. 5. Install
the high voltage cover panel and secure it with the two retaining screws. 6.
Close the enclosure front door and secure with the latch.
INPUT: 120 VAC AT 2.5 A, 50/60 Hz 240 VAC AT 1.3 A, 50/60 Hz
27
Rewiring the System Transformer for 240 VAC
The EasyTouch and IntelliTouch Control System Load Center and Power Center
system transformer can be wired for 120 VAC at 2AMP 50/60 Hz (factory
installed) or 240 VAC at 1AMP 50/60 Hz. The system transformer is pre-wired at
the factory for 120 VAC service. To rewire the system transformer and for 240
VAC:
BEFORE REMOVING THE HIGH VOLTAGE COVER PANEL FROM THE LOAD CENTER OR POWER
CENTER ENCLOSURE switch the main power OFF into the home at the main circuit
breaker box and also switch OFF the main power to the Load Center and Power
Center. 1. CAUTION! Switch the power OFF to the Load Center and Power Center.
2. Unlatch the front door latch and open the front door. 3. Remove the two (2)
retaining screws securing the high voltage cover-panel. Remove the HIGH
VOLTAGE COVER PANEL from the enclosure (see illustration on page 5). 4. Rewire
the system transformer for 240 VAC as shown in the wiring diagram below. 5.
Install the high voltage cover panel and secure it with the two retaining
screws. 6. Close the enclosure front door and secure with the latch.
12
System Transformer
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
28
Section 2 EasyTouch® Control System Overview
EasyTouch Control System and 4 Pool and Spa Control System Kit Contents
The following items are included in the EasyTouch Control System 8 and
EasyTouch 4 control system kit which may also include the optional
IntelliChlor cell.
· EasyTouch control system control panel (mounted in the load center) ·
EasyTouch load center enclosure · Two motorized valve actuators (CVA-24T P/N
263045) – Not included with single-body
system · Water sensor with 25 foot cable, o-ring and hose clamp (P/N 520272) ·
Air sensor with 25 foot cable (P/N 520272) · EasyTouch 8 and EasyTouch control
system 4 Pool and spa Control System Installation
Guide (this manual)
Optional Equipment · IntelliChlor® Salt Chlorine Generator Electrolytic Cell
model IC20 (P/N 520554) or
IC40 (P/N 520555) · IntelliChem® Controller no-pump (P/N 521357), one-pump
(P/N 521356), two-pump (P/N
521355) · IntelliChlor SCG User’s Guide (P/N 520589) · For EasyTouch control
system operating instructions, refer to the EasyTouch control system
User’s Guide (P/N 521044)
WIRELESS CONTROL PANEL
EasyTouch Control System 4 Indoor Control Panel (P/N 520548)
EasyTouch Control System 8 Indoor Control Panel (P/N 520549)
ON/OFF
EasyTouch Control System Wireless Control Panel (8 circuit) (P/N 520547)
Menu
Alarm Select
SpaCommand® Spa-Side Controller (P/N 521176)
QuickTouch® II Wireless Controller (P/N 521245)
IntelliChem® Controller (P/N 521356)
29
EasyTouch® Control System Model Part Numbers
EASYTOUCH CONTROL SYSTEM WITHOUT INTELLICHLOR SCG TRANSFORMER BUILT-IN
520591 520703 520538 520540
EasyTouch 4P – Single Body (base system – no ICP, no actuators) EasyTouch 8P – Single Body (base system – no ICP, no actuators) EasyTouch 4 – Pool/Spa (base system – no ICP, 2 actuators) EasyTouch 8 – Pool/Spa (base system – no ICP, 2 actuators)
EASYTOUCH CONTROL SYSTEM WITH INTELLICHLOR SCG TRANSFORMER AND INTELLICHLOR SCG CELL
520592 520593 520704 520705 520542
520543 520544 520545 521150
EasyTouch 4PSC-IC20 – Single Body (includes SCG integration & IC20 cell) EasyTouch 4PSC-IC40 – Single Body (includes SCG integration & IC40 cell) EasyTouch 8PSC-IC20 – Single Body (includes SCG integration & IC20 cell) EasyTouch 8PSC-IC40 – Single Body (includes SCG integration & IC40 cell) EasyTouch 4SC-IC20 – Pool/Spa (includes SCG integration & IC20 cell, 2 actuators) EasyTouch 4SC-IC40 – Pool/Spa (includes SCG integration & IC40 cell, 2 actuators) EasyTouch 8SC-IC20 – Pool/Spa (includes SCG integration & IC20 cell, 2 actuators) EasyTouch 8SC-IC40 – Pool/Spa (includes SCG integration & IC40 cell, 2 actuators) EasyTouch 8SC-IC60 – Pool/Spa (includes SCG integration & IC60 cell, 2 actuators)
CANADIAN EASYTOUCH CONTROL SYSTEMS
520914 520915 520911
EasyTouch 4P-C – Single Body (salt ready system, cell must be ordered
separately)
EasyTouch 8-C – Pool/Spa (salt ready system, cell must be ordered separately)
IntelliChlor IC20 cell for Canada
EasyTouch Control System Accessory Equipment
EasyTouch Wireless Control Panel, 4 circuits EasyTouch Wireless Control Panel,
8 circuits SpaCommand 10 Ten-Function Spa-Side remote, 150 ft. cable Two-Speed
Three HP Relay up to three additional valve actuators Three HP Power Relay
QuickTouch four-function wireless remote kit with transceiver assembly
QuickTouch II four-function wireless remote kit with transceiver assembly
IntelliChem Controller IntelliChlor Acid Cleaning Kit IntelliChlor Spacer
pass-through cell for new pool start-up
(P/N 520546) (P/N 520547) (P/N 521176) (P/N 520198) (P/N 520106) (P/N 520148) (P/N 521245) (P/N 521356) (P/N 520670) (P/N 520588)
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
30
EasyTouch Control System Start-Up
Perform the following start-up procedures to ensure that the EasyTouch control
system load center is installed correctly. If you need more detailed operating
information, refer to the EasyTouch control system User’s Guide (P/N 521044).
Before you power up the EasyTouch control system load center check the
following:
Check Electronics
Check that the following plugs are seated correctly on the motherboard:
· Relay connectors – FLTR PUMP – AUX1 – AUX7 (EasyTouch 8), AUX1 – AUX3
(EasyTouch 4)
· Temperature sensors connectors WATER, SOLAR, AIR · Transformer conductor
harness (J1) attached to the motherboard. · Heater control connector ELEC HTR
or two-conductor screw terminal. Refer to Summary Installation Steps (page 2)
and EasyTouch System Wiring Diagrams, on page 23.
EasyTouch Control System Test
The following describes how to test the main control panel to activate the
heater, valves and pumps. Before testing the system, be sure that all pool and
spa equipment has been properly installed and connected to the EasyTouch
control system load center.
Testing Valve Actuators and Filter Pump
Use the following steps to test the valve actuators (CVA24T) for proper
rotation.
To test the valve actuators and pump:
1. Power up the EasyTouch control system load center. 2. Press the Mode
button on the main control panel. The display shows “SERVICE”. 3. Press the
Valve (V) button to select POOL. 4. Press the Filter Pump (F) button to
activate the filter pump. Water will be removed from
the pool and returned to the pool. 5. Repeat steps 3 and 4 selecting Fill
(Spillway) then Drain. 6. Set both valve actuators (CVA-24T) for suction and
return. Use the toggle switch on the
rear of the CVA-24T to withdraw and return water from the pool. Note: With the
filter pump operating, if the water is not being removed and returned to the
pool, check that the valve actuator plugs are connected correctly on the
motherboard.
Testing the auxiliary relays
Affix the auxiliary relay labels to the appropriate AUX buttons on the
EasyTouch control system control panel to identify the connected equipment.
· Press the Mode button to enable “Service” pool mode. Press the Filter Pump
button (LED on) and each auxiliary (AUX) circuit button, the Heater and Solar
buttons to verify the functions. Press the Mode button twice to return the
system to “AUTO” mode when done.
31
EasyTouch® Control System Circuit Board Connections
The EasyTouchs Control System circuit board is mounted in the top of the Load
Center. The circuit board provides the voltage connections to the filter pump,
heater, auxiliary relays, motorized valves and for temperature sensors. The
COM port on the EasyTouch circuit board provides connection to the EasyTouch
control system indoor control panel, wireless remote transceiver, SpaCommand
and iS4 spa side remote and to the IntellilFlo® Pump.
EasyTouch Control System Outdoor Circuit Board Connections
EasyTouch Control System Outdoor Control Panel
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
32 EasyTouch® Control System Wiring Diagram
33
Section 3 IntelliTouch® Control System Overview
IntelliTouch Control System Components The main required components of an
IntelliTouch Control System system is a Load Center or Power Center,
IntelliTouch Control System Personality Kit, and Interface:
Load or Power Center · Load Center: Provides a larger footprint (26″ H x 17″ W
x 5-1/4″ D) Includes built-in sub panel (150 AMPS) capable of holding up to
eight 1″ breakers. Also includes five 25 AMP three HP relays, 110/240 V
transformer with secondary side circuit protection. Multiple knockouts for
different sizes of conduit are supplied as well as a GFCI side knockout. The
Load Center provides ample space for all high and low voltage wiring needs. ·
Power Center: Offers a smaller footprint (20″ H x 17″ W x 5-1/4″ D) than the
Load Center. The Power Center does not include a circuit breaker base. Users
should choose this enclosure if they already have existing circuit breakers
/sub-panel for their equipment.
IntelliTouch Personality Kits There are several types of IntelliTouch control
systems available for different pool/spa configurations:
· Shared Equipment: Pool and spa combinations with shared filtration system
Pool owners can enjoy the convenience of motorized valves for water flow
separation between pool and spa. The Personality Kit models are:
· i5+3 (P/N 521219) Four auxiliary circuits plus filter pump operation
(create a Feature circuit for valve actuators without using an existing output
auxiliary circuit, and special light functions for color lighting). Five
relays are included in the Load Center.
· i7+3 (P/N 521220) Six auxiliary circuits plus filter pump operation and
the +3 option (create a Feature circuit for valve actuators without using an
existing output auxiliary circuit, and special light functions for color
lighting). Two relays are included in the kit and five in the Load Center.
· i9+3 (P/N 521221) Eight auxiliary circuits plus filter pump operation and
the +3 option (create a Feature circuit for valve actuators without using an
existing output auxiliary circuit, and special light functions for color
lighting). Four relays are included in the kit and five in the Load Center.
· Dual Equipment: Pool and Spa with Dual Sets of Equipment The IntelliTouch
i10+3D (P/N 521222) is designed to operate two sets of pool equipment. Each
set of a equipment (Pool or Spa) can control one temperature setting. This
IntelliTouch Personality Kit can control up to 10 pumps and/or lighting
circuits, plus two heater circuits. The Personality Kit includes, eight
auxiliary circuits plus a filter pump. The +3 option (create a Feature Macro
circuit for valve actuators without using an existing output auxiliary
circuit). Five relays are included in the kit and five in the Load Center. You
can create a Feature circuit for valve actuators without using an existing
output auxiliary circuit, and special light functions for color lighting.
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
34
· Single Equipment: Pool Only or Spa Only Applications The IntelliTouch
i5S+3 (P/N 521219) and i9+3S provide advanced automation for a single body of
water. The i5+3S (P/N 521223) and i9+3S (P/N 521224) Personality Kits includes
four auxiliary circuits plus filter pump operation. Five relays are included
in the Load Center. The i9+3S Personality Kits includes eight auxiliary
circuits plus filter pump operation and the +3 option (create a Feature Macro
circuit for valve actuators without using an existing output aux circuit).
Four relays are included in the kit and five in the Load Center. You can
create a Feature circuit for valve actuators without using an existing output
auxiliary circuit, and special light functions for color lighting. This model
also allows HI-TEMP and LO-TEMP settings.
IntelliTouch® Control System Accessory Power Center Expansion Kits
· Expansion Kits: Models i5X (P/N 521225) and i10X (P/N 521226), offer five or
ten additional Auxiliary Circuits for systems i9+3, i9+3S and i10+3D. Each
IntelliTouch Expansion Kit requires a Load Center (P/N 521213) or Power Center
(P/N 521214). Up to three Expansion Kits and Load or Power Centers may be
added to a system, for control of up to 38 Auxiliary Circuits (40 auxiliary
circuits for i10+3D).
IntelliTouch Control Personality Kit Contents
The following items are included in the IntelliTouch Personality Kit. If any
item is missing or damaged in the IntelliTouch kit, contact your authorized
dealer, or contact Pentair Technical Support (page 9).
· An IntelliTouch interface · Outdoor Control Panel. Includes a motherboard
and a Personality circuit board. · Power Relays – (Models i5+3, i5S+3 no
relays, i7+3 Qty. 2, i9+3, i9+3S Qty 4, i10+3D Qty
5, i5x (no relays, i10x (5 relays) · Valve Actuators – Qty 2 (Models i5+3,
i7+3, i9+3) · Temperature Sensors – Water Sensor (with long cable, including
o-ring and hose clamp),
Air Sensors (with short cable). For i10+3D only, two Water Sensor (with long
cable) · Wiring Diagram Label for models i5S+3 and i9+3S and i10+3D. For
models i5+3, i7+3,
i9+3, refer to the Load Center and Power Center inside front door. · Load
Center or Power Center parts bag: Includes relay screws. (see page 2) · Label
Sheet – A set of adhesive labels for custom identification (used to label the
outdoor
control panel buttons). Use a pair of fine-tip tweezers to remove the labels
from the sheet. · IntelliTouch Personality Kit Installation Guide (P/N 521074)
Optional Equipment (IntelliChem® Controller) · IntelliChem controller no-pump
(P/N 521357), one-pump (P/N 521356), two-pump (P/N 521355) · IntelliChem
Installation and User’s Guide (P/N 521363)
Menu
Alarm Select
IntelliChem® Water Chemistry Controller (P/N 521356)
35
IntelliTouch Interfaces Choose one or more of the following interface options
to control pool and spa operations.
· iPhoneTM/iPad® Touch Interface (P/N 520500) Includes Protocol Interface
Adapter that connects to existing Desktop or Laptop PC. This allows control of
IntelliTouch or EasyTouch pool and spa systems via PC (requires PC with an
Ethernet connection, and Windows® XP operating system).
· iTC35 Kit (P/N 520502) Includes in-wall color touch screen with Ethernet
(RJ45) connection and Protocol Interface Adapter and wireless router. The in-
wall Touch screen is custom configured for IntelliTouch and EasyTouch systems.
Requires an Ethernet cable to router.
· iTC45 Kit (P/N 520503) Includes wireless Tablet with color touch screen,
Protocol Interface Adapter, and wireless router. The Tablet is custom
configured for IntelliTouch and EasyTouch systems.
iPhoneTM (for use with ScreenLogic2TM)
In-Wall Touch Screen
Digital Tablet
Indoor Control Panel
· Indoor Control Panel (P/N 520138) 3.75” monochrome backlit LCD control
panel. Connects to the IntelliTouch Personality board in the Load Center.
· MobileTouch® Kit (P/N 520906) 3.75” monochrome backlit LCD wireless
control panel with Transceiver antenna. Allows any IntelliTouch wired system
to also have a wireless remote with all the capabilities of the Indoor Control
Panel. With an average range of 300 feet, pool owners have system control
anywhere around the home or yard. Powered by a rechargeable lithium-ion
battery. Includes a cradle for recharging. The MobileTouch control panel
without the Transceiver antenna (P/N 520907) is also available.
· QuickTouch® II (P/N 521245) and QT4 (P/N 520148) Wireless Remote: Four-
function wireless remote for pool and spa functions of your choice. This
controller transmitter operates up to 150 feet range from the Load Center or
Power Center.
· SpaCommand® (P/N 521176) – iS10 (P/N 520149) – iS4 (P/N 520094) :
10-function (SpaCommand/iS10) and 4-function (iS4) Spa-Side remote controller
for pool and spa functions of your choice. The controllers can operate up to
150 feet range from the Load Center or Power Center.
MobileTouch® Wireless Controller
SpaCommandTM
QuickTouch® II wireless remote
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
36
Optional IntelliTouch® Control System Expansion Enclosure
Expansion enclosures can support all of the same high voltage connections as
the main load to the Load Center or Power Center. The Expansion enclosure
supports the same COM port connections, and includes two actuators as the Load
Center or Power Center. The Expansion enclosure can be expanded to include up
to five actuators (with valve module P/N 520285). Refer to the IntelliTouch
Expansion Kit Installation Guide (P/N 520471) for more information.
Main IntelliTouch Control System Load Center (i5+3, i5+3S, i7+3, i9+3, i9+3S,
i10+3D)
Kit Contents
Power Center (with Expansion Center Personality Kit i5x or i10x),
(P/N 521214 with IntelliChlor SCG transformer)
(P/N 521216 without IntelliChlor SCG transformer)
Additional Expansion Center
Additional Expansion Center (3 maximum)
The following items are included in the Load Center or Power Center kit.
· IntelliTouch Control System Load Center or Power Center enclosure. · Relays:
(i7+3 (qty. 2), i9+3, i9+3S (qty. 4), i10+3D ((qty. 5) · Actuators: i5+3.
i7+3, i9+3 (qty. 2) · Temperature Sensor (all models): Water Sensor Long Cable
(qty. 1) (o-ring and hose
clamp) Air sensor – Short cable (qty. 1) – i10+3D additional water sensor long
cable (qty. 1) · Wiring Diagram Label – To affix to the inside front door (for
models i5S, i9+3S, i10+3D, i5x and i10x). i5, i7+3 and i9+3 not required in
kit (see load center door). · Parts bag: Relay screws (qty. 0, 4, 8, or 10)
label sheet · IntelliTouch Load Center Installation Guide (this manual). · For
additional IntelliTouch installation information, refer to the IntelliTouch
Personality Kit
Affixing the System Wiring Diagram Label (provided in kit) – see page 43) To affix the wiring diagram label on the enclosure inside front door: 1. Open the enclosure front door. 2. Peel the backing off the wiring diagram label. 3. Position the label in middle of the inside of the front door. Apply even pressure on the surface of the label to secure in place.
37
System Start-Up
The following information describes basic start-up procedures. For more
detailed troubleshooting information, refer to the IntelliTouch Systems User’s
Guide (P/N 521075). Before you power up the Power/Load Center check the
following:
Check Electronics
Check that the following plugs are seated correctly on the Personality board:
· Relay connectors – FLTR PUMP – AUX1 – AUX10 · Temperature sensors connectors
WATER, SOLAR, AIR · Transformer conductor harness J2 attached to the
Personality board. · Heater control connector ELEC HTR or two-conductor screw
terminal. Refer to Summary Installation Steps (page 5) and Power/Load System
Wiring Diagrams, on page 32 and 43.
System Test
The following describes how to test the Outdoor Control Panel to activate the
heater, valves and pumps. This test assumes that all system equipment has been
properly installed and connected to the Power/Load Center.
Testing Valve Actuators and Pumps
Use the following steps to test the valve actuators (CVA24T) for proper
rotation. For Outdoor Control Panel System i5+3, i7+3, i9+3 (shared
equipment).
To test the valve actuators and pump:
1. Power up the Power/Load Center.
2. Press the SYSTEM CONTROL button on the Outdoor Control Panel until the
SERVICE light is on.
3. Press the V (Valve) button to select POOL.
4. Press the F (Filter Pump) button to activate the filter pump. Water will
be removed from the pool and returned to the pool.
5. Set both valve actuators (CVA-24T) for suction and return. Use the toggle
switch on the rear of the CVA-24 to withdraw and return water from the pool.
Note: With the filter pump operating, if the water is not being removed and
returned to the pool, it may be necessary to reverse the RETURN with VLV A (or
VLV B) plugs on the Personality board.
Testing the auxiliary relays
Affix the auxiliary relay labels to the appropriate buttons on the Outdoor
Control Panel. If necessary, write the function on the control panel.
· Toggle the filter pump, each auxiliary circuit, heater and solar and verify
the function. Press the SYSTEM CONTROL button to set the system in “AUTO” mode
when done.
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
38
Solar System Installation
· To ensure maximum flow of water through the solar panels, a solar booster
pump should be added if panels are installed at a very high elevation.
· It is recommended that the solar panels are mounted in a way that gravity
will allow draining whenever the filter pump is not on.
· For systems with glazed panels, damage can occur from overheating if the
filter pump is still running after the solar has turned off. To enable glazed
panels to automatically drain whenever the solar turns off (even if the filter
pump is still running), a 1/2″ motorized solar drain valve should be plumbed
from the solar feed line, through a check valve, to a zero psi point (such as
pool fill line or jet air intake).
Solar System Start-Up
1. Switch power on to the IntelliTouch Load Center.
2. If pool cleaner protection has been added to the system, the pool cleaner
pump motor should be activated whenever the pool cleaner timer is on.
Momentarily turn pool cleaner on and off to check the motor is operating
correctly.
3. Check that Solar Valve is in “solar bypass” position, diverting water away
from solar panels. If Solar Valve is staged incorrectly (diverting water to
the solar panels), reverse switch on back of Valve Actuator (change from ON1
to ON2, or vice-versa). The Valve Actuator will automatically rotate to the
correct position.
4. Check that Solar Valve has rotated from the “solar bypass” position to the
“solar” position, diverting water through the solar panels.
5. The system is now ready to be operated as desired.
Pool Cleaner Protection Recommended for use in pool systems which utilize a
“booster pump” pool cleaner. This feature automatically turns off the pool
cleaner pump for a few minutes whenever solar is initiated. This will protect
the pump from damage caused by air in the solar panels at system start-up.
39
Installing the IntelliTouch® Control System Outdoor Control Panel
BEFORE INSTALLING THE LOAD CENTER AND POWER CENTER, ALWAYS SWITCH OFF THE MAIN
POWER into the home at the main circuit breaker box.
The IntelliTouch Control System Outdoor Control Panel includes a main circuit
board and the Personality circuit board. The Personality board is mounted on
top of the main circuit board which mounts on the back of the Outdoor Control
Panel. The control panel installs in the top part of the Power/Load Center
enclosure. The Power/Load Center receives control inputs from the Personality
board and distributes high voltage power to Pentair Valve Actuators (PVA),
control pumps, lights, and heater operations. The IntelliTouch remote Indoor
Control Panel also controls these and other functions, such as pool and spa
lights. To install the Outdoor Control Panel:
1. Unlatch the front door spring latch and open the front door of the Load
Center. 2. Remove the two (2) retaining screws securing the high voltage
cover-panel. Remove the
HIGH VOLTAGE COVER PANEL from the enclosure. 3. Remove the Outdoor Control
Panel from the Personality Kit and its packaging. 4. Mount the Outdoor Control
Panel in the top part of the Load Center. Secure the lower edge
of the control panel with the two retaining screws. Once secured, the Control
Panel can hinge out and down to access the Personality board for low voltage
connections. 5. When finished with the low voltage connections on the
Personality board, close the hinged control panel and secure it with the two
access screws. 6. Install the cover-panel and secure it with the two screws.
7. Close the front door of the Load Center. Fasten the two spring latch.
Control Panel: Fold down to access circuit board and low voltage compartment)
Front door
Retaining screws (for High Voltage Cover Panel)
High voltage Cover Panel
Retaining screw
Load Center (front view) (front door and high voltage compartment panel
removed)
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
40
IntelliTouch® Control System Outdoor Control Panels
For IntelliTouch control system wiring diagrams, see pages 41-43.
Shared Equipment Systems Model i5+3, i7+3, i9+3
Single Body Systems Model i5+3S, i9+3S
Operates the same as i5+3, i9+3, except no valve controls.
Dual Body Dual Equipment System Model i10+3D
The i10+3D is designed to operate two sets of pool equipment. Each set of a
equipment (Pool or Spa) can control one temperature setting. Operation same as
i9+3 except S and P buttons operate independent filter pumps and the Heater
and Solar buttons operate independent heating systems and no valve controls.
Expansion Centers Model i5x, i10x Expansion Centers provide additional valve
and auxiliary circuits. They are designed to operate with base systems: i9+3,
i9+3S, i10+3D. The “Auxiliary circuit control capability” buttons operate the
same way as on the main base Outdoor Control Panel.
41 IntelliTouch® Control System Wiring Diagram (i5+3, 7+3 and i9+3)
IntelliTouch® Control System Wiring Diagram (i5+3S and i9+3S)
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
42
IntelliTouch® Control System Wiring Diagram (i10+3D)
IntelliTouch® Control System Wiring Diagram (i10x and i5x)
iS10
43
IntelliTouch® Control System Wiring Diagram EasyTouch®, IntelliTouch® Control
System Load Center Installation Guide
44
Plumbing Requirements
It is important that the pool and spa plumbing system be in accordance with
local codes and the Recommended Hydraulic Schematics (page 45 and 46). Before
starting, please review the diagrams and the following recommended guidelines:
1 The spa should be at or above the level of the pool.
If the spa is attached to the pool, provide a dam between the two bodies of
water to allow the spa to overflow into the pool. If the spa is not attached
to the pool, an overflow, sufficient in size to carry a full pump-flow, must
be installed at the water level in the spa.
2 Plumb a three-port Intake Valve on the suction-side of the filter pump, so
that the center port of the valve is connected to the pump inlet. Connect the
spa suction to one side of the Intake Valve, and the pool suction to the other
side.
3 Plumb a three-port Return Valve on the return-side of the heater, so that
the return water will enter the valve through the center port.
Connect the spa return to one side of Return Valve, and the pool return to the
other side.
4 If required, install a spa makeup line (consisting of a manual gate or ball
valve, for elevated spas install a check valve) to bypass the pool return
line. This will enable some of the chemicallybalanced water from the pool to
cycle through the spa. The manual valve will allow the amount of bypass to be
adjusted.
5 If the spa is to be constructed in concrete, special provision should be
made at this time for the installation of the Spa-Side remote control.
Select a convenient location in the deck or above water level in the spa wall
(where the Spa-Side remote will not be submerged by the spa water), and
install a 6 in to 12 in length of one inch PVC pipe to provide a receptacle
for the Spa-Side remote. The pipe should be level and protrude beyond the
finished surface of the spa. It will be cut back later at installation time.
Reduce the pipe size down to ½ in or ¾ in conduit, and run it to the proposed
Load/Power Center location at the equipment pad. Use sweep elbows for turns.
The Spa-Side remote will not be installed until the spa construction is
completed.
6 For systems which incorporate a skimmer, it is possible to balance the
amount of suction between the skimmer and main drain for maintenance purposes.
This is easily accomplished by installing a manual three-port mixing valve at
the suction line. Plumb one port to the skimmer and the other to the main
drain.
7 If a “non-booster pump” pressure-side pool cleaner is being used, plumb a
manual three-port valve between the filter pump and filter, with the third
port plumbed to the pool cleaner line, and install a motorized two-port Pool
Cleaner Valve at this line. The motorized valve will automatically open
whenever the Control System activates the pool cleaner.
8 If a booster pump pool cleaner is being used, plumb the booster pump so that
its suction-side is connected to the pool return, after the heater, and as
close to the ground as practical.
45
9 Plumb the solar feed and return lines between the filter and the heater.
Install a three-port valve at the feed line. Use a solar valve (model SOL-2T),
to allow automatic draining of the panels.
10 A solar booster pump should be used when the distance to the panels exceed
200 ft., or the panels are elevated higher than 25 ft.
11 Glazed solar panels require a drain valve (model HW-5B) to allow draining
of the panels. This prevents damage from overheating water. Install a drain
valve at the solar feed line and connect to the pool fill line.
12 SCG systems only: IntelliChlor IC40 or IC20 salt chlorine generator (SCG)
cell with check valve at the heater output. Refer to IntelliChlor User’s Guide
(P/N 520589) for plumbing requirements.
Equipment Location
All equipment, with the exception of the spa-side remote, must be located at
least 10 ft. from the water’s edge.
INTELLICHLOR
Recommended Hydraulic Schematic for Shared Equipment System
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
46
INTELLICHLOR SCG
Check Valve
2
INTELLICHLOR SCG
Recommended Hydraulic Schematic for Single Body System
47
Glossary
Control Panel: The EasyTouch® Control System control panel with flexible
hinge. Installed in upper portion of EasyTouch control system load center. EMI
(Electromagnetic interference) filter: Protective circuit element that must be
used between the IntelliChlor transformer and supply lines. High Voltage
Panel/Compartment: Removable panel for the high voltage compartment of
EasyTouch load center. The high voltage wiring including circuit breakers,
relays, GFCI and optional IntelliChlor transformer/filter. Indoor Control
Panel: This 9 or 13 button remote controller with LCD (liquid crystal display)
is wired to the control circuit board in the EasyTouch control system load
center. The control panel can be wall mounted inside a house to control the
EasyTouch system. IntelliChlor® (SCG): Salt Chlorinator Generator. Uses a
process known as electrolysis to produce sodium hypochlorite (liquid chlorine)
from a low concentration of salt added to the pool water. Model IC 20 Cell
(P/N 520554) for pools up to 20,000 U.S. gallons (75 liters) and model IC 40
Cell (P/N 520555) for pools up to 40,000 U.S. gallons (151 liters). iS4
Wireless Controller: Four function spa-side remote. Spa wall or deck mounted.
Load Center: Metal enclosure with power relays, transformer, and circuit
breakers. Used for distributing power for controlling EasyTouch control
system. Also known as the “sub-panel.” Low Voltage Compartment: Top
compartment of load center for all low voltage wiring. Low Voltage Raceway:
Vertical space in the left side of load center for low voltage cabling.
Motherboard: The circuit board mounted behind the EasyTouch control system
control panel. Relay Circuits: The circuits that control the relays on the
motherboard. Connectors on top edge of the circuit board. Screw Terminal
Connector: Removable connector that may attach to circuit board with multiple
sockets (anywhere from 2 to 6) to receive conductors from controllers and
sensors; conductors held by screw terminals; multiple conductors of a small
enough gauge (usually 22 AWG) may be coupled to a single socket of a terminal
connector. Salt Chlorine Generator (SCG): Automated pool chlorinator that
sanitizes using salt water (see IntelliChlor). SpaCommand® Controller: Up to
ten function spa-side remote with temperature changing capability. Can be spa
wall or deck mounted. Transceiver: Used by the EasyTouch control system
wireless control panel. Circuit board with attached antenna that can send and
receive radio frequency (wireless) transmissions.
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
48
Glossary
Expansion Kit (IntelliTouch® Control System): A kit that includes additional
auxiliaries to an existing Personality Kit. Requires a Load Center for each
Expansion Kit Power Center.
Feature Circuits: Programmable circuits that may control relays and/or valve
actuators. For details, see the IntelliTouch Systems User’s Guide (P/N 521075)
High Voltage Compartment: Large lower right compartment of Load Center for all
high voltage wiring including circuit breakers, relays, and GFCI.
Indoor Control Panel: This EasyTouch® or IntelliTouch control system remote
controller with LCD (liquid crystal display) is wired to the Personality board
(IntelliTouch) or Motherboard (EasyTouch) in the Power/Load Center. The
control panel can be wall mounted inside a house to control IntelliTouch or
EasyTouch systems.
SpaCommand® Controller: Up to ten function spa-side remote with temperature
changing capability. Can be spa wall or deck mounted.
Load Center: Metal enclosure with power relays, transformer, and circuit
breakers. The Load Center is Installed prior to Personality Kit installation
(Intellitouch only). Used for distributing power for controlling IntelliTouch
or EasyTouch systems. Also known as the “sub-panel.”
Low Voltage Compartment: Top compartment of Load Center for all low voltage
wiring.
Low Voltage Raceway: Vertical space in the left side of Power/Load Center for
low voltage cabling.
MobileTouch® Controller (IntelliTouch Control System): Wireless controller for
the IntelliTouch Systems with all the functionality of the Indoor Control
Panel.
Mud Box: Enclosure to provide mounting features for SpaCommand controller or
iS10 spa-side remote that is cast into gunite, concrete, or other spa
wall/deck construction.
Outdoor Control Panel: Control panel with flexible hinge installed in upper
portion of Power/Load Center to control IntelliTouch systems.
Personality Board (IntelliTouch Control System): The circuit board mounted on
top of the Outdoor Control Panel motherboard. The Personality board defines
the system capabilities.
Personality Kit (IntelliTouch Control System): Set of parts to define the
capability of a system; may include: Outdoor Control Panel, temperature
sensors, actuators, control panel (Indoor or MobileTouch), additional relays,
actuators.
Power Center: Same as Load Center with the exception of the circuit breaker
base.
Relay Circuits: The circuits that control the relays on the Personality Board
(IntelliTouch control system) or Motherboard (EasyTouch control system).
Connectors on top edge of the circuit board.
Screw Terminal Connector: Removable connector that may attach to circuit board
with multiple sockets (anywhere from 2 to 12) to receive conductors from
controllers and sensors; conductors held by screw terminals; multiple
conductors of a small enough gauge (usually 22 AWG) may be coupled to a single
socket of a terminal connector.
Transceiver: Circuit board with attached antenna that can send and receive
radio frequency (wireless) transmissions. Used with wireless controllers.
49 NOTES
EasyTouch®, IntelliTouch® Control System Load Center Installation Guide
50
1620 HAWKINS AVE., SANFORD, NC 27330 ·
919-566-8000 10951 WEST LOS ANGELES
AVE., MOORPARK, CA 93021 · 805-553-5000
www.pentair.com All indicated Pentair trademarks and logos are property of
Pentair Inc. or its global affiliates in the U.S.A. and/or other countries.
Third party registered and unregistered trademarks and logos are the property
of their respective owners © 2020 Pentair. All rights reserved. This document
is subject to change without notice.
521139
P/N521139Rev.C 2/2020