IOTA IISM Modular Inverter Series 1000W
IISM
MODULAR INVERTER SERIES
1000W – 2000W
Installation Guide
This unit contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY! There are NO USER-SERVICEABLE PARTS inside this unit.
IMPORTANT SAFEGUARDS
When using electrical equipment, you should always follow basic safety precautions, including the following:
- READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
- Do not install the system outdoors.
- Do not install near gas or electric heaters or in other high-temperature locations.
- Use caution when servicing batteries. Depending on battery type, batteries contain either acid or alkali and can cause burns to skin and eyes. If battery fluid is spilled on skin or in the eyes, flush with fresh water and contact a physician immediately.
- Equipment should be mounted in locations where unauthorized personnel will not readily subject it to tampering.
- The use of accessory equipment not recommended by Manufacturer may cause an unsafe condition and void the warranty.
- Do not use this equipment for other than its intended use.
- Qualified service personnel must perform all servicing of this equipment
SAVE THESE INSTRUCTIONS
The installation and use of this product must comply with all national,
federal, state, municipal, or local codes that apply. If you need help, please
call Service at 1-610-868-5400.
CAUTION
READ ENTIRE MANUAL AND REVIEW ALL DOCUMENTATION BEFORE ATTEMPTING SYSTEM
INSTALLATION!
FOR SERVICE OR INSTALLATION INFORMATION:
TELEPHONE: 610-868-5400 (24 HR.
HOTLINE)
FAX: 610-954-8227
FOR YOUR PROTECTION….
PLEASE COMPLETE AND RETURN WARRANTY REGISTRATION CARD IMMEDIATELY.
SAFETY WARNINGS
Read the following precautions before you install the Inverter.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation and maintenance of the system and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
DANGER
This system contains LETHAL VOLTAGES. AUTHORIZED SERVICE PERSONNEL should
perform all repairs and service ONLY. There is NO USER SERVICEABLE PARTS
inside.
WARNING
- Do not install the system outdoors.
- Do not install near gas or electric heaters or in other high-temperature locations.
- Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or in the eyes, flush with fresh water and contact a physician immediately.
- Equipment should be mounted in locations where it is not readily subjected to tampering by unauthorized personnel.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Do not use this equipment for other than intended use.
- Only qualified service personnel (such as a licensed electrician) should perform the system and battery installation and initial startup. Risk of electrical shock.
INTRODUCTION
Please read this manual thoroughly before operating your safety system. Keep this manual and the system User’s Guide.
WARNING
Only qualified service personnel (such as a licensed electrician) should
perform the system and battery installation and initial startup. Risk of
electrical shock.
Please record your unit’s model number, serial number, and part number below.
You can find these numbers on the label on the inside of the system’s circuit
breaker door.
Model Number __
Serial Number __
Part Number __
BEFORE INSTALLING THE UNIT
Installation Dimensions
INVERTER MODULE DIMENSIONS – 10” X 10” X 26”
INVERTER MODULE WITH BATTERY MODULE DIMENSIONS
UNIT SIZE | WIDTH | HEIGHT | DEPTH |
---|---|---|---|
1000 | 26” | 30” | 10” |
1500 | 26” | 40” | 10” |
2000 | 26” | 50” | 10” |
Location Guidelines
Keep the following guidelines in mind when choosing the location for your
system and batteries:
- Verify that the environment meets the requirements in “Storage and Operating Environment” onpage 7. The environment can affect the reliability and performance of both the unit and thebatteries.
- Install any separate battery cabinets as close as possible to the unit to reduce the cost of DCwiring and to improve battery performance. We recommend no clearance between the unit andthe battery cabinet; in other words, the battery cabinet(s) should be directly under or to the leftside of the unit (when you face the front of the unit). If you must place the battery cabinet awayfrom the unit, you must supply the proper length, gauge, and type of battery cables, and you mustmake sure the installation meets the applicable NEC (CEC) requirements.
- Choose a permanent location for the unit and any battery cabinets. Attempting to move them afteryou have installed the batteries can damage the batteries and the cabinet
CAUTION
- Do not move the unit or the battery cabinet after you install the batteries. If you do, the unit or battery cabinet and batteries may be damaged.
- CEC (Canadian Electric Code) requires the unit to be located in a service room. If the room is equipped with a sprinkler system, the unit must be provided with sprinkler proof covers.
- The system should be connected to the emergency generator, if available.
- This equipment is heavy. Refer to Table 3.4 when you choose a site to make sure that the floor can support the weight of the system, the batteries, any separate battery cabinets, and any other necessary equipment
Table 3.4 System weight [in lbs. (kg)]
| 1000W| 1500W| 2000W
---|---|---|---
Battery Cabinet| 44 (20)| 66 (30)| 88 (40)
Inverter Cabinet| 72 (33)| 72 (33)| 72 (33)
Batteries| 216 (98)| 324 (147)| 432 (196)
System Total| 332 (151)| 462 (210)| 592 (269)
Receiving and Handling the Unit and the Batteries
This system can weigh several hundred pounds (see Table 3.4; ask your sales
representative for additional information). Make sure you are prepared for
these weights before you unload or move the unit or the batteries. Do not
install any batteries until you have permanently installed the unit with
battery cabinets and connected all conduit and wiring.
Storage and Operating Environment
Make sure you store and install the system in a clean, cool, dry place with normal ventilation for human habitation and level floors.
Storage Temperature
Store the batteries at -18 to 40°C (0 to 104°F). Batteries have a longer shelf
life if they are stored below 25°C (77°F). Keep stored batteries fully
charged. Recharge the batteries every 90–120 days. The system or battery
cabinet without batteries may be stored at -20 to 70°C (-4 to 158°F).
Ventilation
The air around the unit must be clean, dust-free, and free of corrosive
chemicals or other contaminants. Do not place the system or batteries in a
sealed room or container.
Operating Temperature
System can operate from 20° to 30°C (68° to 86°F) and up to 95% relative
humidity. The batteries’ service life is longer if the operating temperature
stays below 25°C (77°F)
Batteries
The temperature should be near 25°C (77°F) for optimum battery performance.
Batteries are less efficient at temperatures below 18°C (65°F), and high
temperatures reduce battery life. Typically, at about 35°C (95°F), battery
life is half of what it would be at a normal temperature of 25°C (77°F). At
about 45°C (113°F), battery life is one-fourth of normal. Make sure that
heaters, sunlight, air conditioners, or outside air vents are not directed
toward the batteries. These conditions can make the temperature within battery
strings vary, which can cause differences in the batteries’ voltages.
Eventually, these conditions affect battery performance. Remember that the
batteries should be installed as close as possible to the unit to reduce DC
wiring costs and improve battery performance.
Do not allow tobacco smoking, sparks, or flames in the system location because
hydrogen is concentrated under the vent cap of each cell of the battery.
Hydrogen is highly explosive, and it is hard to detect because it is
colorless, odorless, and lighter than air. Every type of battery can produce
hydrogen gas, even sealed maintenance-free batteries. The gas is vented
through the vent caps and into the air, mainly when the unit is charging the
batteries. The batteries produce the most hydrogen when maximum voltage is
present in fully charged batteries; the batteries do not produce hydrogen
during float charging. The amount of current that the charger supplies to the
batteries (not the battery ampere-hour) determines how much hydrogen is
produced.
High Altitude Operation
The maximum operating ambient temperature drops 1°C per 300m (2°F per 1000 ft)
above sea level. Maximum elevation is 3000m (10,000 ft).
INSTALLATION OVERVIEW
Figure 4.1 shows a typical vertical installation of the system. This drawing
depicts a 2000W inverter with battery cabinets. The modular system is capable
of single-phase power outputs up to 2,000 Watts depending on the number of
battery cabinets. The Inverter and Battery modules are shipped separate and
require attachment for the depicted typical vertical installation shown in
figure 4.1. All instructions included in this literature are for this type of
installation.
4 x ¼-20 bolts that the user must install secure each cabinet to each other.
There are Electrical Knock- Outs in the vertical and horizontal axis to allow
inter-connectivity in multiple configurations. The Vertical installation is
the most popular however; allowing the batteries to be mounted separately and
horizontally allows the user to fit this system almost anywhere where floor
space is tight or not available at all.
Inverter Module and Battery Module Assembly
Refer to Chapter 8 for Optional Wall Mounting directions.
5 x 8-32 screws located on the front and top of the module easily remove the
Inverter Module cover and 5 x 8-32 screws located on the front of the Battery
Module’s easily remove each cover. There are 4 holes located on each corner
that allow the ¼-20 hardware to attach to the different modules. There are
Electrical Knock-Outs that must be removed on the Inverter Module and the
Battery Module to allow passage of the battery cables. After the Electrical
Knock- Outs are removed, the factory provided plastic grommet must be inserted
through the hole to provide abrasion resistance for the wires. After the
plastic grommet is inserted, the bolts, washers and lock washers should be
inserted and tightened down. Use the plastic grommet as the alignment between
the two modules. Shown in figure 4.2 is the exploded view showing the
hardware, Electrical Knock-Out and the plastic Grommet. Battery Module to
Battery Module connections uses a plastic grommet, bolts, washers, lock
washers and nuts
TERMINAL BLOCK/CIRCUIT BREAKER STANDARD CONFIGURATION
Inverter Module
AC INPUT & AC OUTPUT INSTALLATION
WARNING
Only qualified service personnel (such as a licensed electrician) should
perform the AC installation. Risk of electrical shock.
Read the following cautions before you continue.
CAUTION
- Unit contains hazardous AC and DC voltages. Because of these voltages, a qualifiedelectrician must install the system, AC line service, and batteries. The electrician mustinstall the AC line service according to local and national codes and must be familiarwith batteries and battery installation.
- Before you install, maintain, or service the unit, always remove or shut off all sources ofAC and DC power and shut off the system. You must disconnect AC line input at theservice panel and turn off the Installation Switch (S1), the Main AC Input CircuitBreaker (CB2), and the Battery Fuse(s) to make sure the unit does not supply outputvoltage.
- Whenever AC and/or DC voltage is applied, there is AC voltage inside the unit; this isbecause the unit can supply power from AC line or from its batteries. To avoidequipment damage or personal injury, always assume that there may be voltage insidethe unit.
- Remove rings, watches, and other jewelry before installing the AC wiring. Always wearprotective clothing and eye protection and use insulated tools when working nearbatteries. Whenever you are servicing an energized unit with the inside panel open,electric shock is possible; follow all local safety codes. TEST BEFORE TOUCHING!
- To reduce the risk of fire or electric shock, install the unit and its batteries in atemperature- and humidity-controlled indoor area free of conductive contaminants. Seepage 7 for operating environment specifications.
-
Remove the Inverter Module’s cover. Make sure the installation switch and all the inputcircuit breaker are off (off = left).
-
Look at the ID label inside the Inverter Module’s Circuit Breaker Access Door. Writedown the following information:
Input Voltage: __ Output Voltage: __ -
Now, make sure the input and output voltages are what you need. Remember that thesystem provides single-phase power only.
-
Does the input voltage available for the system at the AC service panel match theinput voltage shown on the unit’s ID label?
Service Panel Voltage = ____ Input Voltage Yes /No -
Does the output voltage on the ID label match the voltage your loads (protectedequipment) need?
Load Voltage = _____ Output Voltage Yes/No
If you answered NO to either of the preceding questions, call SERVICE.
-
-
Now, use the information you wrote down in Step 2 to find the correct circuit breaker forthe service panel that is for your system.
Table 5.1 Recommended Circuit Breaker for Maximum Input Current System VA| 120VAC| 277VAC
---|---|---
1000| 30A| 15A
1500| 30A| 15A
2000| 30A| 15A -
Write down the circuit breaker value that applies to your system from Table 5.1:__
-
Now, look at Table 5.2 below, and use the notes below to find the proper gauge wirefor the recommended circuit breaker recorded in step 5.
-
The input circuit breaker in the input service panel provides the means fordisconnecting AC to the unit. Only authorized persons shall be able todisconnect AC to the unit [see NEC 700-20 and 700-21(CEC Section 46)]. Ifyou are using the input circuit breaker to disconnect AC, you must make surethat only authorized persons have control of the circuit breaker panel to meetthe requirements of NEC 700-20 (CEC Section 46).
-
Read the following “caution” before removing conduit knockouts
CAUTION
To prevent electrical shock or damage to your equipment, the Keyed Installation Switch (S1), the Main AC Input Circuit Breaker (CB2), and the circuit breaker at the input service panel should all be turned off. The DC Battery Fuse(s) should be removed and the Battery Circuit Breaker should be turned off. -
Remove knockouts for AC Input and AC Output in the top left or left side of the Inverter Module. AC input conductors and AC output conductors must be installed in separate conduits, and emergency and non-emergency output circuits must be installed in separate conduits.
CAUTION
Do not drill the cabinet; drilling cabinet will void factory warranty; drill filings may damage the unit and keep it from operating. If you need larger knockouts, use a chassis punch to punch out the appropriate knockout. -
Install the conduit. You must run the AC input service conductors and AC output conductors through separate conduits. Emergency output conductors and non-emergency output conductors must also be run through separate conduits. Emergency output circuits shall be installed in dedicated conduit systems and not shared with other electrical circuits as described in NEC 700-9(b) [CEC Section 47-108]
AC INPUT AND OUTPUT CONNECTION
Inverter Module
- Connect the AC Input and Output to the AC Terminal Blocks Labeled AC Input and AC Output. Ensure that the systems ac voltage matches the utility input.
- For the AC input, use a minimum 10 AWG wire for Line, Neutral and Ground.
- For the AC output, use a minimum 12 AWG wire for Line, Neutral and Ground.
- Earth Grounding of the system is achieved through the Ground terminal block. There is a ground terminal block provided for the input and output connections. The terminal block connects to the din rail through a clamping system and the din rail connects to the Chassis through the din rail hardware. No additional Ground lugs are required.
INSTALLING BATTERIES AND DC WIRING
WARNING
Only qualified service personnel (such as a licensed electrician) should
perform the battery and DC wiring installation. Risk of electrical shock.
This section explains how to install system batteries, fuses, and cables. An
electrician who is familiar with battery installations and applicable building
and electrical codes should install the batteries.
WARNING
- The batteries that will need to be installed in this system could cause you harm or severely damage the electronics if proper precautions are not followed. Batteries connected in series parallel configuration could produce lethal voltages with unlimited current. All batteries should be inspected for damage prior to installation. Never install a battery that is leaking electrolyte.
- Battery terminals should be cleaned with a wire brush to remove any oxidation. All tools should be insulated. Rubber gloves and safety glasses are recommended.
- IN THIS SYSTEM BATTERY NEGATIVE IS TIED TO GROUND INSIDE THE INVERTER. This means that the battery cabinet and shelves are at ground potential as soon as negative connections are made to the batteries.
- It is strongly recommended to make all negative connections to the batteries the last step to prevent any chance of shorting battery positive to ground. With the DC fuse removed, make connections to battery positive first, working your way towards battery negative.
- Leave individual strings of batteries open at the last battery negative until all batteries are installed. Then connect each strings negative.
Safety Instructions
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This section contains important instructions that a qualified service person
should follow during installation and maintenance of the system and batteries.
ONLY a qualified service person should work with the batteries.
CAUTION
- Full voltage and current are always present at the battery terminals. The batteries used in this system can produce dangerous voltages, extremely high currents, and a risk of electric shock.
- They may cause severe injury if the terminals are shorted together or to ground (earth). You must be extremely careful to avoid electric shock and burns caused by contacting battery terminals or shorting terminals during battery installation. Do not touch uninsulated battery terminals.
- A qualified electrician familiar with battery systems and required precautions must install and service the batteries. Any battery used with this unit shall comply with the applicable requirements for batteries in the standard for emergency lighting and power equipment, UL 924 (Canada’s National Building Code).
- Cabinets are design to be used with, and batteries must be replaced with, manufacturer battery number BAT-CG12015 or a manufacturer approved equivalent (see the battery wiring diagram that came with the battery cables).
- If you substitute batteries not supplied by manufacturer, the unit’s UL (cUL) listing is void and the equipment may fail. Installation must conform to national and local codes as well. Keep unauthorized personnel away from batteries.
The electrician must take these precautions:
- Wear protective clothing and eyewear. Batteries contain corrosive acids or caustic alkalis and toxic materials and can rupture or leak if mistreated. Remove rings and metal wristwatches or other metal objects and jewelry. Do not carry metal objects in your pockets where the objects can fall onto the batteries or into the system or battery cabinet.
- Tools must have insulated handles and must be insulated so that they do not short battery terminals. Do not allow a tool to short a battery terminal to another battery terminal or to the cabinet at any time. Do not lay tools or metal parts on top of the batteries, and do not lay them where they could fall onto the batteries or into the cabinet.
- Install the batteries as shown on the battery-wiring diagram provided with the system. When connecting cables, never allow a cable to short across a battery’s terminals, the string of batteries, or to the cabinet.
- Align the cables on the battery terminals so that the cable lug does not contact any part of the cabinet even if the battery is moved. Keep the cable away from any sharp metal edges
CAUTION
Install the battery cables so they cannot be pinched by the battery cabinet or
the system covers.
External battery cabinet chassis ground (or earth) must be connected to the
system’s chassis ground (or earth). The ground conductor must be insulated. If
you use conduit, this ground conductor must be routed in the same conduit as
the battery conductors. Where conductors may be exposed to physical damage,
protect conductors in accordance with the National Electrical Code (NEC)
[Canadian Electrical Code (CEC)]. If you are replacing batteries or repairing
battery connections, follow the procedure in the system user’s Guide to shut
down your system and remove both AC and DC input power.
Before Installing the Batteries
Location
Before you start installing the batteries, you must install the Inverter
Module and any Battery Modules in their permanent location. If you have not
already done this, see “Location Guidelines” on page 6 to choose a location.
CAUTION
To prevent damage to your equipment, do not move the system or separate
battery cabinets after the batteries are installed.
To make sure a location is acceptable for the system, review the requirements
in Chapter 3.
Tools
CAUTION
Always use insulated tools when you work with batteries. Always torque
connections to the manufacturer’s recommendations.
When you work with system batteries, you need the following tools. The tools
must be insulated so they do not short battery terminals to the cabinet. Wear
the safety equipment required by local code whenever the doors are open and
whenever you are working on batteries. Other tools may be necessary for
optional batteries.
- Digital volt-ohm meter
- Conductive grease or petroleum jelly
- 10mm / 7/16” open end wrench
- Brush (to apply grease or petroleum jelly to terminals)
- 3” extension socket
- Safety equipment required by local codes
- Ratchet
- Torque wrench calibrated in inch-pounds or Newton-meters
- Wire brush
- 10mm / 7/16” socket wrench
- Electrical tape
- Safety glasses with side shields
Battery Cable Sizing
The battery cable or wire used is No. 12 AWG for each string of batteries.
If the batteries must be more than four feet (1.2 meters) from the system, you
may need to install larger battery cables between the battery cabinets and the
system
Installing and Connecting the Batteries
Battery Wiring Diagram
You should have received a battery-wiring diagram with your system. This
battery-wiring diagram shows how you should install the batteries, make
terminal, and fuse connections. Use the diagram as you follow the steps below.
All systems are based on 48 VDC. When higher wattage is needed, the number of
battery strings (batteries in parallel) increases. For 1000W, two strings are
required. For 1500W, three strings are required and for 2000W, four strings
are required.
Connecting the Modules
- Wherever conductors may be exposed to physical damage, you must protect the conductors in accordance with the NEC (CEC). This includes battery cables between the system and a separate battery cabinet and cables between battery cabinets (if you have more than one).
- We recommend routing the battery cable through the Electrical Knock-Out’s.
- If the cabinets must be farther apart, we recommend that you use conduit (cables not included). Install the conduit for the battery cables according to local or national codes. If you are using conduit, you must substitute your own cables for the cables shipped with the unit as you follow the battery installation instructions. Remember that the terminal blocks supplied with the unit and battery cabinets accept up to 10 AWG wire. Use the correct type, length, and gauge of cable; make sure your installation meets all applicable electrical codes.
NOTE As you carry out the following steps, use these guidelines: If you are using conductive grease, apply a thin coating of high-temperature conductive grease on each post and every cable connector before you assemble and torque the connection to slow corrosion. If you use nonconductive grease like petroleum jelly, do not apply any grease before you make the connections and torque them. Instead, make the connection first, then torque it to 40 inch pounds. After you make the connection; apply a coating of the nonconductive grease to the hardware at the battery terminals.
Each Battery module has 4 batteries wired in series. Connect the Battery Module’s four batteries first and then connect the battery module(s) to the inverter module.
- Remove the Battery module fuse to isolate the battery module.
- Start with the Red (+) wire. Connect this wire to battery one positive.
- Jumper one (factory provided) is from battery one negative to battery two positive.
- Jumper two (factory provided) is from battery two negative to battery three positive.
- Jumper three (factory provided) is from battery three negative to battery 4 positive.
- The final connection is the Yellow (-) wire. Connect this wire to battery four negative.
Torque all battery connections to 40 inch pounds.
There are now 4 batteries connected in series between the red and yellow wire.
The red and yellow wires are connected into the Battery Module’s terminal
blocks.
Measure with a voltmeter between the yellow terminal block (battery -) and the
fuse block where the red wire comes into it. There should measure
approximately 48 VDC.
The voltage can vary as much as +/- 2 volts depending on the state of charge
on the batteries.
CAUTION
- If you do not verify that voltage and current direction are correct, the equipment may fail.
- Repeat this process for each battery module.
- After all of the battery modules are complete, the battery module(s) can be connected to the inverter module.
CAUTION
Hazardous voltage is present! System batteries are high current sources. These
batteries can produce dangerous voltages, extremely high currents, and a risk
of electric shock
BATTERY MODULE CONNECTION
Install 4 batteries wired in series to produce 48 VDC nominal. The Positive + wire (Red) and the Negative – (Yellow) are provided pre-installed into the Terminal Blocks. Connect the three jumpers and the positive and negative leads to the batteries as shown. Use the hardware provided (8 x 1/4-20 Bolt and Nut w/flat and Lock washers) and torque to 40-inch pounds (4.5 Nm) maximum.
Electronics Module to Battery Module Connections
NOTE If you are using conduit, you must supply the correct length, gauge,
and type of battery cables.
Refer to the battery-wiring diagram to identify the battery cables you use to
connect the unit to the battery cabinet(s). Pull the cables through the nipple
or conduit.
- Do not connect any cables at this time.
- If your unit has more than one battery cabinet, use the battery-wiring diagram to identify the cables you use to connect the battery cabinets. Pull these cables
- through the connecting nipple or conduit. Do not connect the cables.
Making the Equipment Ground Connection
CAUTION
All grounding conductors should be insulated. If you are using non-insulated
grounding conductors, take special care to make sure that the grounding
conductors cannot accidentally contact live wires or the batteries.
In the system, find the ground compression lug labeled “GROUND”. This terminal
is next to the AC and DC terminal blocks internal to the Inverter Module.
- There is a Green 12 AWG ground conductor supplied with each Battery Module as part of the cable kit. Cut this wire to the desired length and strip the insulation from both ends 3/8”. Then, connect one end of the conductor to the ground lug in the Inverter Module. There is a dedicated ground terminal block under the battery (-) terminal blocks.
- Connect the other end of the grounding conductor to the Ground Terminal Block located in the battery module.
- If the unit has two battery modules, you must connect a ground conductor that connects the Battery Module cabinets. This is easily accomplished by daisy-chaining the ground using the Ground terminal block. Since the Ground terminal block has two ends, simply cut the second ground wire to length and insert into the Ground Terminal Block in Battery Module 1 to Battery Module 2.
NOTE: When you connect a separate equipment-grounding conductor directly to building steel, use the knockouts that are already on the unit. Do not make a knockout anywhere on the cabinet where there is not already a knockout.
Fuse
Remove the DC Fuse in each of the Battery Module(s) before connecting the
Battery Module to the Inverter Module.
Positive Wire(s)
Included in the battery cable kit is a red wire that will connect the positive
conductor from the battery module to the inverter module.
- Run the wire between the battery module and the inverter module to get the approximate length required. Once the length is established, cut and strip the wire. The wire should be stripped 3/8’ from both ends.
- Insert the stripped wire into the battery positive terminal blocks in the Inverter Module and the Battery Module. Follow the colors – red wire to red terminal block.
- Torque the battery terminal block to 10 inch pounds to secure the wire into the terminal block.
- Repeat this process for additional Battery Modules.
Negative Wire(s)
Included in the battery cable kit is a yellow wire that will connect the
battery module to the inverter module.
- Run the wire between the battery module and the inverter module to get the approximate length required. Once the length is established, cut and strip the wire. The wire should be stripped 3/8’ from both ends.
- Insert the stripped wire into the battery negative terminal blocks in the Inverter Module and the Battery Module. Follow the colors – yellow wire to yellow terminal block.
- Torque the battery terminal block to 10 inch pounds to secure the wire into the terminal block.
- Repeat this process for additional Battery Modules.
Replacing the Batteries
CAUTION
A battery can present a risk of electrical shock and high short circuit
current. A qualified electrician familiar with battery systems should service
the batteries.
Review all the safety instructions at the beginning of this chapter before you
replace any batteries.
Use the Same Quantity and Type of Battery
CAUTION
You must use the same quantity and type of battery. Substituting batteries not
supplied by manufacturer voids the UL (CUL) listing and may cause equipment
damage.
To ensure continued superior performance of your system and to maintain proper
charger operation, you must replace the batteries in the system or battery
cabinets with the same number of batteries. These batteries must be the same
types as the original batteries. The replacement batteries should have the
same voltage and ampere-hour rating as the original batteries.
Handle Used Batteries with Care!
Assume that old batteries are fully charged. Use the same precautions you
would use when handling a new battery. Do not short battery terminals or the
battery string with a cable or tool when you disconnect the batteries!
Batteries contain lead. Please dispose of old batteries properly.
CAUTION
Do not dispose of batteries in a fire because the batteries could explode. Do
not open or mutilate batteries. Released electrolyte is harmful to the skin
and eyes. It may be toxic.
Dispose of Batteries Properly
CAUTION
Batteries contain lead. Many states and local governments have regulations
about used battery disposal. Please dispose of the batteries properly.
SETTING THE AUTOMATIC SYSTEM TEST PARAMETERS
Several parameters in the system software determine when and how your system
conducts the automatic monthly and annual tests. Refer to “Program Functions”
in the “Front Panel Display” chapter of the system user’s Guide for a
description of each test.
Starting the Unit
Before you can set the parameters, you must start the system.
WARNING
Verify that the system AC Input Circuit Breaker and Installation Switch are
off.
- Turn on the AC input at the building service panel; ensure that the systems input breaker (CB2) is off.
- Turn on the Battery Circuit Breaker (CB1).
- Turn on the System AC input circuit breaker (CB2).
- Turn on the Installation Switch (S1). Leave the loads (protected equipment) off. Unit will run on batteries, then transfer to normal mode.
FRONT PANEL DISPLAY
The Front Panel Display consists of a 2 x 20 alpha numeric LCD display with
LED back lighting, 5 status LED indicators and a 4 x 4 keypad for user
interface.
Control Panel Keypads
Meter Functions
Meter functions are available by pressing the METER keypad to get to the Meter
Menu and then pressing the desired function keypad. (See figure 7.3)
Table 7.2 Meter Functions
Function | Description | Keypad Text |
---|---|---|
Voltage Input | Measures the AC Input Voltage to the Inverter | V IN |
Voltage Output | Measures the AC Output Voltage from the Inverter | V OUT |
Current Output | Measures the AC Output Current from the Inverter. If optional |
Normally Off loads are connected, it will read the sum of Normally On and
Normally Off outputs.| I OUT
Battery Voltage| Measures Battery Voltage| V BATT
Battery Current| Measures the Battery Current. When in charge mode, the
current will be positive. When in Inverter mode, the current will be
negative.| I BATT
VA Output| Multiplication of the output voltage and output current| VA OUT
Inverter Watts| Multiplication of the battery voltage and the battery current|
INV. WATTS
Inverter Minutes| Total minutes the system has run on inverter| INV. MIN
Temperature| Measures the ambient temperature of the electronics enclosure.|
TEMP
System Days| Total days the system has been in service.| SYS. DAYS
Program Functions
All program functions are password protected. The password for user level is
1234. When the PROGRAM Keypad is pressed, the display will prompt the user for
the password. After the password is entered (1234 + ENTER key), the user can
change the Date, Time, Month Test Date, Month Test Time, Yearly Test Date and
Yearly Test Time, Load Reduction Fault, Low VAC Alarm, High VAC Alarm, Ambient
Temp Alarm and Near Low Battery settings. Time is always in the 24 hour
standard. Example 4:00 PM is 16:00.
Table 7.3 Program Functions
Parameter | Format | Factory Default |
---|---|---|
Date | MM/DD/YY (Month, Date, Year) | Current Date |
Time | HH/MM (Hours, Minutes) | Eastern Stand Time |
Monthly Test Date | DD (Date) | 15th of the Month |
Monthly Test Time | HH/MM (Hours, Minutes) | 5:00 |
Yearly Test Date | MM (Month) | 01 |
Yearly Test Time | HH/MM (Hours, Minutes) | 8:00 |
Load Reduction | AAAA (AMPS) | 0.0A |
Low VAC Alarm | VVVV (Volts) | 1.0V |
High VAC Alarm | VVVV (Volts) | 999.9V |
Ambient Temp Alarm | DDD (Degrees Centigrade) | 70°C |
Near Low Battery | VVVV (Volts) | 43VDC |
The Day of the Automatic Tests
Table 7.5 shows the purpose of each parameter and its factory setting.
Table 7.5 Factory Setting for Automatic Test Parameter
Parameter | Determines… | Factory Default |
---|---|---|
Monthly Test | The time and the day of the month for the monthly tests. | 15th @ |
5:00 AM
Yearly Test| The time and the date for the yearly test.| (January) 1 @
8:00 AM
The Length of the Automatic Tests
Parameters Monthly Test and Yearly Test determine how long the battery test
is. Table 7.6 shows the purpose of each parameter.
Table 7.6 Factories Setting for Automatic Test Parameters
Parameter | Purpose | Factory Default for 90 minute systems |
---|---|---|
Monthly Test | Monthly battery test. | 5 Minutes |
Yearly Test | Yearly battery test. | 90 Minutes |
The factory can only reprogram these parameters
If you would like to change the setting of any of the above parameters, (see
table 7.3) follow these steps: (i.e. setting the Time). See Figure 7.3 for
Keypad location.
- Press the PROGRAM keypad, enter the user password (1234), press theENTER keypad.
- Press the ► arrow keypad (◄ or ► keypads are used for scrolling through themenu) to the Time parameter (HH/MM) to set the time. NOTE: Factory default isEastern Standard Time and with 24 hour formats. (i.e. 1:00 PM = 1300 hours)
- Enter correct time for your time zone using the NUMBER keypads, and thenpress the PROGRAM keypad to exit.
Completing the Installation
Install the cover to the Inverter and Battery Module(s). You have finished
installing the system. Now turn on the output circuit breaker(s).
Keep the System Installation Guide and the User’s Guide for future reference.
Notes:
DIRECTIONS FOR WALL MOUNTING USING STRUT CHANNEL
SYSTEMS WITH ONE BATTERY CABINET
Refer to Figure 8.1.
- Battery Cabinet mounting requires (4) Spring Clamp-nuts, (4) ¼-20 Bolts and (4) ¼-20 Flat Washers.
- Electronics Cabinet mounting requires (2) Spring Clamp-nuts, (2) ¼-20 Bolts and (2) ¼-20 Flat Washers.
- Mount Strut Channels to wall vertically (hardware not included), 16” apart on center. (NOTE: Strut Channels are long enough for four Battery Cabinets and maybe cut to desire length; Do Not cut strut channels shorter than 21 inches.)
- Place one spring clamp-nut on each strut channel 2.5” from the bottom of the strut channels.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nuts placed in step #2.
- Place the next spring clamp-nuts 14.37” on center above the spring clamp-nuts placed in step #3.
- Remove cover from Electronics Cabinet and Battery Cabinet.
- Line up the four holes on the back of the Battery Cabinet with the spring clamp-nuts from steps #2 and #3. Secure the Battery Cabinet to the spring clamp-nuts using (4) ¼-20 bolts and (4) flat washers.
- Remove the top left front knockout from the Battery Cabinet.
- Remove the bottom left front knockout from the Electronics Cabinet.
- Place Electronics Cabinet on top of the Battery Cabinet. Line up the two holes on the back of the Electronics Cabinet with the top two spring clamp-nuts. Secure the Electronics Cabinet to the spring clamp-nuts using (2) ¼-20 bolts and (2) flat washers. (Verify that the two knockouts from steps #7 and #8 line up.)
Return to Chapter 4 “Inverter Module and Battery Module Assembly”
DIRECTIONS FOR WALL MOUNTING USING STRUT CHANNEL
SYSTEMS WITH TWO BATTERY CABINETS Refer to Figure 8.2
- Two Battery Cabinet mounting requires (8) Spring Clamp-nuts, (8) ¼-20 Bolts and (8) ¼-20 Flat Washers.
- Electronics Cabinet mounting requires (2) Spring Clamp-nuts, (2) ¼-20 Bolts and (2) ¼-20 Flat Washers.
- Mount Strut Channels to wall vertically (hardware not included), 16” apart on center. (NOTE: Strut Channels are long enough for four Battery Cabinets and maybe cut to desire length; Do Not cut strut channels shorter than 32 inches.)
- Place one spring clamp-nut on each strut channel 2.5” from the bottom of the strut channels.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nuts placed in step #2.
- Place the next spring clamp-nuts 4.683” on center above the spring clamp-nuts placed in step #3.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nuts placed in step #4.
- Place the next spring clamp-nuts 14.37” on center above the spring clamp-nuts placed in step #5.
- Remove cover from Electronics Cabinet and Battery Cabinets.
- Line up the four holes on the back of Battery Cabinet #1 with the spring clamp-nuts from steps #2 and #3. Secure Battery Cabinet #1 to the spring clamp-nuts using (4) ¼-20 bolts and (4) flat washers.
- Remove the top left front knockout from Battery Cabinet #1 and Battery Cabinet #2.
- Remove the bottom left front knockout from Battery Cabinet #2.
- Place Battery Cabinet #2 on top of Battery Cabinet #1. Line up the four holes on the back of Battery Cabinet #2 with the spring clamp-nuts from steps #4 and #5. Secure Battery Cabinet #2 to the spring clamp-nuts using (4) ¼-20 bolts and (4) flat washers.
- Remove the bottom left front knockout from the Electronics Cabinet.
- Place Electronics Cabinet on top of Battery Cabinet #2. Line up the two holes on the back of the Electronics Cabinet with the top two spring clamp-nuts. Secure the Electronics Cabinet to the spring clamp-nuts using (2) ¼-20 bolts and (2) flat washers. (Verify that the knockout from each cabinet line up with the other cabinet.)
Return to Chapter 4 “Inverter Module and Battery Module Assembly”
DIRECTIONS FOR WALL MOUNTING USING STRUT CHANNEL
SYSTEMS WITH THREE BATTERY CABINETS
Refer to Figure 8.3.
- Three Battery Cabinet mounting requires (12) Spring Clamp-nuts, (12) ¼-20 Boltsand (12) ¼-20 Flat Washers.
- Electronics Cabinet mounting requires (2) Spring Clamp-nuts, (2) ¼-20 Bolts and (2)¼-20 Flat Washers.
- Mount Strut Channels to wall vertically (hardware not included), 16” apart on center.(NOTE: Strut Channels are long enough for four Battery Cabinets and maybe cut todesire length; Do Not cut strut channels shorter than 43 inches.)
- Place one spring clamp-nut on each strut channel 2.5” from the bottom of the strutchannels.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nutsplaced in step #2.
- Place the next spring clamp-nuts 4.683” on center above the spring clamp-nutsplaced in step #3.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nutsplaced in step #4.
- Place the next spring clamp-nuts 4.683” on center above the spring clamp-nutsplaced in step #5.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nutsplaced in step #6.
- Place the next spring clamp-nuts 14.37” on center above the spring clamp-nutsplaced in step #7.
- Remove cover from Electronics Cabinet and Battery Cabinets.
- Line up the four holes on the back of Battery Cabinet #1 with the spring clamp-nutsfrom steps #2 and #3. Secure Battery Cabinet #1 to the spring clamp-nuts using (4)¼-20 bolts and (4) flat washers.
- Remove the top left front knockout from Battery Cabinets #1, #2 and #3.
- Remove the bottom left front knockout from Battery Cabinets #2 and #3.
- Place Battery Cabinet #2 on top of Battery Cabinet #1. Line up the four holes on theback of Battery Cabinet #2 with the spring clamp-nuts from steps #4 and #5. SecureBattery Cabinet #2 to the spring clamp-nuts using (4) ¼-20 bolts and (4) flatwashers.
- Place Battery Cabinet #3 on top of Battery Cabinet #2. Line up the four holes on theback of Battery Cabinet #3 with the spring clamp-nuts from steps #6 and #7. SecureBattery Cabinet #3 to the spring clamp-nuts using (4) ¼-20 bolts and (4) flatwashers.
- Remove the bottom left front knockout from the Electronics Cabinet.
- Place Electronics Cabinet on top of Battery Cabinet #3. Line up the two holes on theback of the Electronics Cabinet with the top two spring clamp-nuts. Secure theElectronics Cabinet to the spring clamp-nuts using (2) ¼-20 bolts and (2) flatwashers. (Verify that the knockout from each cabinet line up with the othercabinet.)
Return to Chapter 4 “Inverter Module and Battery Module Assembly”
SYSTEMS WITH FOUR BATTERY CABINETS
Refer to Figure 8.4.
- Four Battery Cabinet mounting requires (16) Spring Clamp-nuts, (16) ¼-20 Bolts and (16) ¼-20 Flat Washers.
- Electronics Cabinet mounting requires (2) Spring Clamp-nuts, (2) ¼-20 Bolts and (2) ¼-20 Flat Washers.
- Mount Strut Channels to wall vertically (hardware not included), 16” apart on center.
- Place one spring clamp-nut on each strut channel 2.5” from the bottom of the strut channels.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nuts placed in step #2.
- Place the next spring clamp-nuts 4.683” on center above the spring clamp-nuts placed in step #3.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nuts placed in step #4.
- Place the next spring clamp-nuts 4.683” on center above the spring clamp-nuts placed in step #5.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nuts placed in step #6.
- Place the next spring clamp-nuts 4.683” on center above the spring clamp-nuts placed in step #7.
- Place the next spring clamp-nuts 5.438” on center above the spring clamp-nuts placed in step #8.
- Place the next spring clamp-nuts 14.37” on center above the spring clamp-nuts placed in step #9.
- Remove cover from Electronics Cabinet and Battery Cabinets.
- Line up the four holes on the back of Battery Cabinet #1 with the spring clamp-nuts from steps #2 and #3. Secure Battery Cabinet #1 to the spring clamp-nuts using (4) ¼-20 bolts and (4) flat washers.
- Remove the top left front knockout from Battery Cabinets #1, #2, #3 and #4.
- Remove the bottom left front knockout from Battery Cabinets #2, #3 and #4.
- Place Battery Cabinet #2 on top of Battery Cabinet #1. Line up the four holes on the back of Battery Cabinet #2 with the spring clamp-nuts from steps #4 and #5. Secure Battery Cabinet #2 to the spring clamp-nuts using (4) ¼-20 bolts and (4) flat washers.
- Place Battery Cabinet #3 on top of Battery Cabinet #2. Line up the four holes on the back of Battery Cabinet #3 with the spring clamp-nuts from steps #6 and #7. Secure Battery Cabinet #3 to the spring clamp-nuts using (4) ¼-20 bolts and (4) flat washers.
- Place Battery Cabinet #4 on top of Battery Cabinet #3. Line up the four holes on the back of Battery Cabinet #4 with the spring clamp-nuts from steps #8 and #9. Secure Battery Cabinet #4 to the spring clamp-nuts using (4) ¼-20 bolts and (4) flat washers.
- Remove the bottom left front knockout from the Electronics Cabinet.
- Place Electronics Cabinet on top of Battery Cabinet #4. Line up the two holes on the back of the Electronics Cabinet with the top two spring clamp-nuts. Secure the Electronics Cabinet to the spring clamp-nuts using (2) ¼-20 bolts and (2) flat washers. (Verify that the knockout from each cabinet line up with the other cabinet.)
Return to Chapter 4 “Inverter Module and Battery Module Assembly