PULS FPT500.247-064-102 3-Phase 24V Power Supply Instruction Manual
- June 9, 2024
- PULS
Table of Contents
FPT500.247-064-102 3-Phase 24V Power Supply
Instruction Manual
FPT500.247-064-102 3-Phase 24V Power Supply
Read this first!
Before operating this device, please read this manual thoroughly and retain
this manual for future reference! This device may only be installed and put
into operation by qualified personnel. If damage or malfunction should occur
during operation, immediately turn power off and send device to the factory
for inspection. The device does not contain serviceable parts. The information
presented in this document is believed to be accurate and reliable and may
change without notice. For any clarifications the English translation will be
used.
**Warning**
Risk of electrical shock, fire, personal injury, or death:
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Do not open, modify or repair the device.
- Do not touch during power-on and immediately after power-off. Hot surfaces may cause burns.
Product Description
The FPT500.247-064-102 is a stand-alone power supply for single phase mains
systems, which provides a stabilized and galvanically separated PELV/ES1
output voltage at 3 outputs.
The negative potential of the outputs is permanently connected to PE within
the unit.
The housing is rated as IP65 and IP67 according IEC60529 and provides
protection against electrical, mechanical and fire hazards.
One output fulfills the requirements for a limited power source according to
NEC Class2.
The device is equipped with an IO-Link Interface V1.1 to parameterize and
access data.
Intended Use
This indoor use device is intended for commercial use, such as in
industrial control, process control, monitoring, measurement or the like. Do
not use this device in equipment, where malfunctioning may cause severe
personal injury or threaten human life, without additional appropriate safety
devices, that are suited for the end-application.
If used in a manner outside of its specification, the protection provided by
the device may be impaired.
Installation Instructions
Install the device with the terminals on the bottom of the device. Other
mounting orientations require a reduction in output current. When installing
watch out for the risk of injury from sharp edges and assure that when
installed any sharp edges on the back cannot be accessed and cannot cause
injury.
Use 4 screws ( 2 on top and 2 on bottom mounting holes) suitable for the
underground and a strength comparable to M4 or UNC 8-32 screws.
The device is designed for pollution degree 3 areas in controlled
environments.
The enclosure of the device provides a degree of ingress protection of IP65
and IP67 when installed with all mating connectors firmly connected. Assure
that during installation no moisture or dirt gets into the connections.
Operation in areas where moisture or condensation can be expected is possible.
The device is designed as “Class of Protection I” equipment according to IEC
61140. Do not use without a proper PE (Protective Earth) connection.
For TN,TT mains systems with earthed neutral and IT star mains systems with
insulation monitoring the device is designed for overvoltage category III
zones up to 2000m (6560ft) and for overvoltage category II zones up to 5000m
(16400ft). For TN, TT, IT delta mains systems or IT star mains systems without
insulation monitoring the device is intended for overvoltage category II zones
up to 2000m (6560ft). The device is designed to be safe in case of a single
phase loss and does not require an external protection.
The device is designed for convection cooling without a fan. Do not obstruct
airflow. The device is designed for altitudes up to 5000m (16400ft). Above
2000m (6560ft) a reduction in output current is required and the operation is
limited according the mains systems description above.
Keep the following minimum installation clearances: 50mm on top and bottom,
10mm on the front, the left and the right side.
The device is designed, tested and approved for branch circuits up to 20A (UL)
and 32A (IEC) without additional protection device. If an external fuse is
utilized, do not use circuit breakers smaller than 6A B- or C-characteristic
to avoid a nuisance tripping of the circuit breaker.
Make sure that you only use plugs and cables rated for the device output
current and the required temperature range. Follow all local and national
codes for installation.
WARNING: Risk of fire or electric shock. Do not connect outputs or
devices in parallel for higher output currents. Do not connect the negative
potential of any output to PE.
The maximum permissible ambient air temperature is +70°C (+158°F). The
operational temperature is the same as the ambient or ambient air temperature
and is defined 2cm below the device. Cleaning only with a damp cloth.
Functional Description
The output is electronically protected against no-load, overload and short
circuit and can supply any kind of loads, including inductive and capacitive
loads. If capacitors with a capacitance >20mF are connected to one output,
this output might switch off after turning the unit or the output on or
connecting the load. Do not apply return voltages from the load to the output
terminals higher than 35V. Feed-back energy from a load must be below 2.5J.
The green Status LED reports an output above 90% of the adjusted voltage of a
running device and no output tripped due to overcurrent or overtemperature and
all three phase voltages are present. The device has an internal
overtemperature protection. If the temperature is too high the unit shuts down
and starts automatically again after cooling off. Each output will get the
same state as before the shutdown.
In case of an internal defect, a redundant circuit limits the maximum output
voltage to 32.5V. The output shuts down and automatically attempts to restart.
IO-Link gives access to internally measured parameters and can be used to
change settings. For IODD files and additional descriptions please visit
www.pulspower.com.
LED bargraph and push-buttons:
The LED bar normally displays the actual output power as percentage value.
100% equals an output power of 500W. LEDs up to and including 100% are green,
the LEDs above 100% are orange. With pressing the up / down buttons you can
see the percentage of each output. The orange LED indicates the selected
output.
If you press the “Set Mode” button for 3 seconds all LEDs light up briefly and
one LED stays on, showing the actual output voltage. With pressing the up or
down button you can change the set voltage to the values indicated by the
green LED. All orange LEDs are dark. The voltage is set immediately and the
value stored until the next change. If you press the “Set Mode” button again
you can set the output current limit for the selected channel indicated by the
orange LED. With the up / down buttons the current limit is changed to the
values indicated by the single lit green LED. The value is stored until the
next change. Select other outputs with the “Set Mode” button. Without further
pressing of push-buttons, the LED bar will return from any other mode to
normal mode after 15s. With the buttons at each channel the channel can turned
on/off manually by pressing for at least 1s. The current limit for the NEC
Class2 output cannot be changed.
Mating connectors:
Use a 4 Pin 7/8” double coded female plug to connect to the input voltage
connector (X1). Pin assignment: Pin 1 for L1, Pin 2 for L2, Pin 3 for L3; Pin
4 for PE.
Use a standard M12 A-coded 5 pin female plug for the IO Link.
Use a standard M12 A-coded 5 pin male plug to connect to the output connector
(X3). Pin assignment: Pin 1 and 4 for plus; Pin 2 and 3 for minus; Pin5: FE
(functional earth).
Use 5 Pin 7/8” male plugs for the output voltage connectors(X4, X5). Pin
assignment: Pin 4 and 5 for plus; Pin 1 and 2 for minus; Pin 3: FE (functional
earth).
Technical Data
All values are typical figures specified at 3x 400Vac 50Hz input voltage, symmetrical phase voltages, 24V, 500W output load, 25°C ambient temperature and after a 5 minutes run-in time unless otherwise noted.
Output voltage | DC 24V | Nominal |
---|---|---|
Adjustment range | 24 – 28Vdc | Factory setting 24.5V |
Output power | Continuous: |
600W
500W
350W
Derate linearly between| At +45°C ambient
At +55°C ambient
At +70°C ambient
+45°C and +70°C
Output currents| Settable per output;| up to 10A
Input voltage AC| 3AC 380 – 480V| ±15%
Mains frequency| 50 – 60Hz| ±6%
Input current AC| 0.8 / 0.66A| At 3×400 / 480Vac
Power factor| 0.94 / 0.95| At 3×400 / 480Vac
Input inrush current| 1.9 / 1.8A pea| At 3×400 / 480Vac, temp. independent
Efficiency| 95.8 / 95.6%| At 3×400 / 480Vac
Losses| 22.0 / 23.0W| At 3×400 / 480Vac
Hold-up time| 24 / 24ms| At 3×400 / 480Vac
Temperature range| -25 to +70°C|
Size (WxHxD)| 181x183x59mm| Without connectors
Weight| 1200g / 2.7lb|
Headquarters: PULS GmbH, Elektrastr.
6, 81925 Munich, Germany,
www.pulspower.com
Germany +49 89 9278 0
China +86 512 62881820
France +33 478 668 941
North America +1 630 587 9780
Austria +43 2764 3213
Singapore +65 6684 2310
Switzerland +41 56 450 18 10
United Kingdom +44 1525 841001
The information in this document is believed to be accurate and reliable and
may change without notice.