PULS FPT500.241-010-108 3-Phase IP54-67 Power Supply Instruction Manual

June 4, 2024
PULS

FPT500.241-010-108 Installation Manual
Power Supply, 3-Phase, 24V, 500W

FPT500.241-010-108 3-Phase IP54-67 Power Supply

Read this first!
Before operating this device, please read this manual thoroughly and retain this manual for future reference! This device may only be installed and put into operation by qualified
personnel. If damage or malfunction should occur during operation, immediately turn the power off and send the device to the factory for inspection. The device does not contain serviceable parts. The information presented in this document is believed to be accurate and reliable and may change without notice. For any clarifications, the English translation will be used.
**WARNING
Risk of electrical shock, fire, personal injury, or death:
**

  • Turn the power off before working on the device. Protect against inadvertent re-powering.
  • Do not open, modify or repair the device.
  • Do not use it in wet locations or in areas where moisture or condensation can be expected.
  • Do not touch during power-on and immediately after power-off. Hot surfaces may cause burns.

Product Description
The FPT500.241-010-108 is a stand-alone power supply for three-phase mains systems, which provides a stabilized and galvanically separated PELV/ES1 output voltage. The negative potential of the outputs is permanently connected to PE within the unit.
The device is incorporated in a housing rated for IP65 and IP67, which provides protection against electrical, mechanical, and fire hazards.

Installation Instructions

Install the device onto a flat surface with the terminals on the bottom of the device. Other mounting orientations require a reduction in output current.
The device is designed for pollution degree 3 areas in controlled environments.
Install the device on a large enough flat surface so that any sharp edges on the back cannot cause injury.
The power supply is mounted on a bracket with 4 screws of size M4. For mounting the bracket use screws of equal or higher strength.
The enclosure of the device provides a degree of ingress protection of IP65 and IP67 when installed with all mating connectors firmly connected.
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use without a proper PE (Protective Earth) connection.
For TN, TT mains systems with earthed neutral and IT star mains systems with insulation monitoring the device is designed for overvoltage category III zones up to 2000m (6560ft) and for overvoltage category II zones up to 5000m (16400ft). For TN, TT, IT delta mains systems or IT star mains systems without insulation monitoring the device is intended for overvoltage category II zones up to 2000m (6560ft).
The device is designed to be safe in case of a single-phase loss and does not require external protection.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation fins!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in output current is required and the operation is limited according to the mains systems described above.
Keep the following minimum installation clearances: 50mm on top and bottom, 10mm on the front, and 10mm left and right sides.
The device is designed, tested, and approved for branch circuits up to 20A (UL) and 32A (IEC) without additional protection devices. If an external fuse is utilized, do not use circuit breakers smaller than 6A B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient or surrounding air temperature and is defined as 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Cleaning only with a damp cloth.

Functional Description

The output is electronically protected against no-load, overload, and short circuits and can supply any kind of load, including unlimited inductive and capacitive loads. If capacitors with a capacitance >100mF are connected, the unit might charge the capacitor in an intermittent mode.
Do not apply return voltages from the load to the output terminals higher than 35V.
The green DC-OK LED reports an output above 90% of the adjusted voltage of a running device.
The DC OK relay monitors the output voltage and the contact is closed when the DC-OK LED is on.
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads.
The device is equipped with over-temperature protection. In case of a high temperature, the output shuts down and starts automatically again after cooling off.
Do not parallel devices for higher output currents.
Do not connect the outputs of multiple devices in a series connection for higher output voltages.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32.5V. The output shuts down and automatically attempts to restart.
LED bar graph and push-buttons:
The LED bar has two functions included. In normal operation, the LED bar displays the actual output power as a percentage value. 100% equals an output power of 500W. LEDs up to and including 100% are green, and the LEDs above 100% are orange.
The second function of the LED bar is to display the set point of the output voltage. Therefore, press the “Set Mode” button for 3s. All LEDs will be on for a short period of time and the one, which equals the output voltage, remains on.
To change the output voltage, press the “Set Mode” button for 1s and change the output voltage by pressing the up or down buttons. The voltage can be set to the following predefined values: 24V,
24.5V, 25V, 25.5V, 26V, 26.5V, 27V, and 28V as indicated by the LEDs. The DC- OK LED means 24V.
The voltage is set immediately and the value is stored until the next change.
Without further pressing of push-buttons, the LED bar will return to output power mode after 15s.
Mating connectors:
For the mating input voltage connector (X1) use the connector HANQ4/2 from Harting consisting of four parts. Use order numbers 19 12 008 0429 (1x housing), 09 12 006 3141 (1x insert), 09 32 000 6204 (4x crimp contacts) and 19 12 000 5156 (1x cable gland). Pin assignment for the input connector
(X1): Pin 1 for L1, Pin 2 for L2, Pin 3 for L3, and the Pin with the PE symbol for PE.
For the mating DC OK signal connector (X2) use a standards M12 A-coded 5-pin female connector.
Pin assignment for the DC OK connector (X2): Pin 1 and Pin 4 for relay contact.
The output voltage terminal (X3) utilizes the connector HAN Q2/0 from the company Harting consisting of three parts. Use order number 6104401263900 for the set of all necessary parts.
Pin assignment for the output connector (X3): Pin 1 for the positive output pole, Pin 2 for the negative output pole.

Technical Data

All values are typical figures specified at 3x 400Vac 50Hz input voltage, symmetrical phase voltages, 24V, 500W output load, 25°C ambient temperature and after a 5 minutes run-in time unless otherwise noted.

Output voltage
Adjustment range| DC 24V
24 – 28Vdc| Nominal
Factory setting 24.5V
---|---|---
Output power| Continuous: 600W 500W 350W
Short-term, up to 5 1000W 700W| Below +45°C ambient
At +55°C ambient
At +70°C ambient
Input voltage AC
Mains frequency
Input current AC
Power factor| 3AC 380 – 480V
50 – 60Hz
1.1 / 0.9A
0.94 / 0.95| ±15%
±6%
At 3×400 / 480Vac
At 3×400 / 480Vac
Input inrush current| 1.5 / 1.5A peak| At 3×400 / 480Vac,
temp. independent
Efficiency
Losses| 95.8 / 95.6%
20.8 / 23.0W| At 3×400 / 480Vac
At 3×400 / 480Vac
Hold-up time| 24 / 24ms| At 3×400 / 480Vac
Temperature range| -25 to +70°C
Size (WxHxD)
Weight| 182x212x70mm
1550g / 3.4lb| Without connectors

Functional Diagram

PULS FPT500 241 010 108 3 Phase IP54 67 Power Supply - Functional
Diagram

Output Characteristic

PULS FPT500 241 010 108 3 Phase IP54 67 Power Supply - Output
Characteristic

Temperature Range

PULS FPT500 241 010 108 3 Phase IP54 67 Power Supply - Output Characteristic
1

Hole Pattern for Mounting

PULS FPT500 241 010 108 3 Phase IP54 67 Power Supply - Hole
Pattern

PULS FPT500 241 010 108 3 Phase IP54 67 Power Supply -
Icon PU-451.015.28-xxA
Doc. ID: PU-451.015.28-xxi (2021-06-17 HE1)
Headquarters: PULS GmbH, Elektrastr. 6, 81925 Munich, Germany, www.pulspower.com
Germany +49 89 9278 0
China +86 512 62881820
France +33 478 668 941
North America +1 630 587 9780
Austria +43 2764 3213
Singapore +65 6684 2310
Switzerland +41 56 450 18 10
United Kingdom +44 1525 841001
The information in this document is believed to be accurate and reliable and may change without notice.