resideo Braukmann TS131 Installation Guide
- June 9, 2024
- resideo
Table of Contents
TS131 Braukmann
Installation instructions
Strandvejen 42
Saksild
8300 Odder 86 62 63 64
www.automatikcentret.dk
info@automatikcentret.dk
Safety Guidelines
-
Follow the installation instructions.
-
Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger. -
Note that the appliance is exclusively for use in the applications detailed in these installation instructions (see 2 Technical Data). Any other use will not be considered to comply with requirements and would invalidate the warranty.
-
Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
-
Immediately rectify any malfunctions which may influence safety.
Technical Data
Media
Medium:| Drinking water
Connections/Sizes
Connection sizes:| Rp 3/4″ (DIN EN 10226)
Pressure values
Max. operating pressure:| 10 bar
Operating temperatures
Operating temperatures: TS131-3/4 A+B
TS131-3/4ZAx| ** 95 °C
x =50 / 100 / 110 °C
Max. ambient temperature:| 70 °C
Specifications**
Heating system capacity:| max. 100 kW
Capacity:| 2800 kg/h water at the pressure drop D p=1 bar (Inlet pressure 5
bar; Outlet pressure 4 bar; 110°C medium temperature) (1 capillary tube)
Mode of operation:| 2 Kp Solid/dual-fuel boilers with integrated water heater
or cooling coil in closed heating systems according to EN 12828
Options
For Options visit homecomfort.resideo.com/europe
Assembly
4.1 Installation Guidelines
• The valve and the sensor must be installed carefully to avoid any damage to
the capillary tube
• The opening on the blow-out line must be clear and easy to monitor
• Ensure no persons are in danger when blowing off the valve
• A sufficiently dimensioned discharge line must be provided
kVS value: p = 1 bar
3 m3/h: with 2 intact sensor systems (with a media temperature of 110 °C)
2.1 m3/h: with one sensor system (with a media temperature of 110 °C)
CAUTION!
Installation of the thermal discharge safety valve does not replace the
diaphragm relief value in the cold water supply line to the water heater.
4.2 Assembly instructions
-
Install a thermal discharge safety valve according to the installation diagram
• Flow direction is indicated by an arrow -
Push the heat sensor into the immersion pipe up to the stop point and secure with a round screw to stop it being pulled out
Start-up
CAUTION!
On commissioning the heating system, the person preparing the system must
check that the thermal discharge safety valve is functioning perfectly.
Maintenance
**** In order to comply with EN 806-5, water fixtures must be inspected and
serviced on an annual basis.
As all maintenance work must be carried out by an installation company, it is
recommended that a servicing contract should be taken out.
In accordance with EN 806-5, the following measures must be taken:
6.1 Inspection and Maintenance
**** Do not use any cleansers that contain solvents and/or alcohol for
cleaning the plastic parts, because this can cause damage to the plastic
components – water damage could result.
Detergents must not be allowed to enter the environment or the sewerage
system!
- According to the requirements of EN 12828, the system operator is obliged to have the thermal discharge safety valve checked by a professional at least once a year to ensure its functional readiness.
-
Check whether water is escaping from the housing
• if water is escaping, the seals (entire piston guide) must be replaced, or it may be necessary to replace the unit -
Operate the check valve and first check whether water is escaping and the valve then closes again
• if no water is escaping or the valve does not close, the unit may have to be replaced
Disposal
Observe the local requirements regarding correct waste recycling/disposal!
Spare Parts
For Spare Parts visit homecomfort.resideo.com/europe
Manufactured for and on behalf of
Pittway Sàrl, Z.A., La Pièce 4,
1180 Rolle, Switzerland
by its authorised representative
Ademco 1 GmbH
For more information
homecomfort.resideo.com/europe
Ademco 1 GmbH, Hardhofweg 40,
74821 MOSBACH, GERMANY
Phone: +49 6261 810
Fax: +49 6261 81309
© 2020 Resideo Technologies, Inc. All rights reserved.
Subject to change. MU1H-1543GE23 R0420
Documents / Resources
|
resideo Braukmann
TS131
[pdf] Installation Guide
Braukmann TS131, Braukmann, TS131
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>