Installation Instructions
STEP 1
Thoroughly clean the pipe where the clamp will be installed. Be sure to remove
any scale, dirt, or debris that could affect the gasket seal.
STEP 2
Mark the pipe in both directions a measured distance from the center of the
break or damaged area.
STEP 3
Lubricate the pipe surface and gasket(s) using a soap and water solution
(antifreeze may be required). All lubricant solutions should meet the
requirements of the water/gas and pipe supplier.
STEP 4
Back off nut, disengage bolt head from lug and open clamp enough to install
the band assembly on the pipe.
STEP 5
Remove the gasket cartridge from the band assembly, open at split and snap
around pipe. Center gasket over leak. Gasket split should be 180° from damaged
section.
STEP 6
Center bridge plate as shown in image by rotating band assembly so the
location dimples are centered between the open and closed lugs. Engage bolt
head in open lug.
STEP 7
Tighten the nut sufficiently to stop leak using recommended torque values
listed below.
NOTE: Use of a calibrated torque wrench is recommended!
Recommended Torque Values
Bolt Size| Torque
3/8”| 25 ft-lb
7/16”| 30 ft-lb
Do not exceed recommended torque
Notice for Full Breaks
DO NOT USE 244 OR 247 FOR JOINING PIPE ON GAS LINES When used to repair or connect separated pipes, the 244 clamp can act as an insulator. Where conductivity is required in installations (such as electrically grounded power or corrosion protected systems), a jumper wire may have to be installed, connecting the two pipes together. When a jumper is required, it should be installed meeting all applicable electrical codes.
WARNING
THIS PRODUCT DOES NOT RESTRAIN PIPE MOVEMENT.
Proper anchoring is required to prevent pipe pull out. Failure to anchor or
improper anchoring can result in dangerous pipe content escape, property
damage, serious injury, and/or death. Read the product installation
instructions prior to installing this product.
Installation Instructions
STEP 1
Thoroughly clean the pipe where the clamp will be installed. Be sure to
remove any scale, dirt, or debris that could affect the gasket seal.
STEP 2
Mark the pipe in both directions a measured distance from the center of the
break or damaged area.
STEP 3
Lubricate the pipe surface and gasket(s) using a soap and water solution
(antifreeze may be required). All lubricant solutions should meet the
requirements of the water/gas and pipe supplier.
STEP 4
Back off nut, disengage bolt head from lug and open clamp enough to install
the band assembly on the pipe.
STEP 5
Install on pipe, making certain leak location is centered on, and properly
covered by gasket. Use reference marks from Step 2 for aligning axially.
Engage bolt head in open lug.
STEP 6
Tighten the nut sufficiently to stop leak using recommended torque values
listed below.
NOTE: Use of a calibrated torque wrench is recommended!
Recommended Torque Values
Bolt Size| Torque
3/8”| 25 ft-lb
7/16”| 30 ft-lb
5/8”| 70 ft-lb
Do not exceed recommended torque
WARRANTY
Smith-Blair, Inc. warrants its products to be free of defects in materials and
workmanship for a period of one (1) year from the date of shipment by Smith-
Blair, Inc. (the “Warranty Period”). Dated proof of purchase, such as a bill
of sale, is required to establish warranty eligibility. If a product fails to
perform due to a defect in materials or workmanship during the Warranty
Period, Smith-Blair, Inc. will repair or, at Smith Blair, Inc.’s option,
replace the product with the same or comparable item. In the event that the
product cannot be repaired and a suitable replacement item is not available,
Smith-Blair, Inc. will refund the original purchase price shown on the proof
of purchase. In all cases, the customer is responsible for returning the
allegedly defective product to the factory or warehouse designated by Smith-
Blair, Inc.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ANY EXPRESS OR IMPLIED
WARRANTY OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, OR OTHER
WARRANTY OF QUALITY, OR THOSE ARISING FROM A COURSE OF DEALING, CUSTOM, OR
USAGE OF TRADE. THE REMEDIES PROVIDED IN THIS LIMITED WARRANTY STATEMENT ARE
THE CUSTOMER’S SOLE AND EXCLUSIVE REMEDIES. IN NO EVENT SHALL SMITH-BLAIR,
INC. BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL
DAMAGES, WHETHER BASED ON CONTRACT, TORT, OR ANY OTHER LEGAL THEORY, AND
WHETHER ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.
CORROSION & PRODUCT SELEACTION NOTICE
Metal products are subject to corrosion, particularly when used outdoors and/or underground. A large number of factors and local conditions af the rate of corrosion. Consult a local corrosion expert determine the life expectancy of this product when used with your pipeline content, soil, and environment. Also, consult your system designer to determine the suitability of this product in your piping system. Failure to determine the suitability of this product in your application, soil, and/or environment can result in premature product failure. Smith-Blair will provide additional information about this product’s material specifications at your request. You may also obtain product information at www.smith-blair.com
Questions: Call 1-800-643-9705 or visit www.smith-blair.com
Sheet 2 of 2 Rev 08/26/21
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>