Schneider Electric GV4P07N6 TeSys Power Deca Motor Circuit Breakers Frame 4 User Guide

June 8, 2024
Schneider Electric

Schneider logo

Safety device for use in Explosive Atmospheres

GV4P07N6 TeSys Power Deca Motor Circuit Breakers Frame 4

TeSys Power –
Deca Motor Circuit Breakers Frame 4
II (2) GD – Zones 1 – 2, 21 – 22
I (M2)
EU-Type Examination Certificate Number: INERIS 18ATEX0020X
UK-Type Examination Certificate Number: CML 21UKEX7329X

Introduction

Tesys Deca motor circuit breakers frame 4 can be used to protect motors in explosive atmospheres when they bear the following marking:Schneider
Electric GV4P07N6 TeSys Power Deca Motor Circuit Breakers Frame 4 -
fig

The reference numbers of the motor circuit breakers affected are:Schneider
Electric GV4P07N6 TeSys Power Deca Motor Circuit Breakers Frame 4 - fig
3

General Rules of Use

These products MUST be installed outside Ex zones.
They are qualified for the protection of motors that are protected against explosions and placed in Zones 1-2 or 21-22.
Use of these products must be limited to the electric motor overload protection function for which they are designed.
These products must be installed, used and maintained in accordance with the standards and regulations applicable within the country of installation, for example:

  • directive 99/92/EC
  • EN/IEC standards: 60079-14, 60079-17, 60364
  • harmonised / designated standard: EN 50495
  • established practice for installation in the zone or zones for which they have been designed.

We accept no responsibility in the event of failure to comply with these standards and regulations.
This product must be installed, configured, started up and maintained by qualified, authorized personnel.
Responsibility for manufacturer traceability (serial number on the certification label) is at the first known delivery destination.
These products MUST be used to provide protection against motor overloads:
b for increased safety motors, in the context of standard IEC 60079-7, or b when required by the EU-type or UK-type examination certificate of the motor installed in the Ex zone.

Startup

  • Before startup, check that the product has not been damaged (do not startup a damaged product).

  • Check that the information marked on the product is compatible with the permitted conditions for the Ex zone of the site at which it is to be used:

  • Ex II (2) GD:
    – Group II: Surface industries
    – Category 2: High protection level
    – D: Dust
    – G: Gas

  • Ex I (M2):
    – Group I: Devices used in mines susceptible to firedamp
    – Category M2: High protection level

  • Store products in their original packaging, in a dry place, T : -50 °C… +85 °C

  • On startup: Connect, assemble and configure the product in accordance with the manufacturer’s instructions.

  • All other information required for setting up the products (including dimensions, connection diagrams, mounting and configuration) can be found in the following
    documents, which serve as instructions for use:

  •  instruction sheets supplied with Tesys Deca motor circuit breakers frame 4

  • Schneider Electric TeSys catalog – Control and Protection Components.
    These documents can be downloaded from www.se.com.

Configuration and Use

The following conditions MUST be met in order to guarantee the level of safety required in an explosive atmosphere.
WARNING
RISK OF INADEQUATE MOTOR PROTECTION

  • Tesys Deca motor circuit breakers frame 4 must be configured by qualified, trained service personnel.
  • The thermal class and motor current of the Tesys Deca motor circuit breakers frame 4 must be adapted in accordance with the motor to be protected. Failure to follow these instructions can result in death, serious injury, or equipment damage.
    Please also note that in the event of a trip following a motor overload, an emergency restart is not permitted until the motor has cooled down completely.

Maintenance

In accordance with the maintenance rules for any electrical installation, check the following once a year:

  • the correct tightening of cables, by conducting thermographic testing
  • the mechanical operation of the product, by manually operating the test button
  • the correct operation of the trip unit (the READY LED is flashing)
  • the correct set up of the overload function of the installation.

EU Declaration of Conformity
N°/Nr: SC17022402C
Products identification :
Type of products : Motor cicuit-breaker

Models:TeSys GV4P / GV4PE
References:GV4P02 to GV4P115 and GV4PE02 to GV4PE115 and its accessories : MX shunt trip : GV4AS027, GV4AS057, GV4AS137, GV4AS287, GV4AS487
MN undervoltage release :GV4AU027, GV4AU057, GV4AU137, GV4AU247, GV4AU286, GV4AU415, GV4AU486
Front extended rotary handle : GV4APN01, GV4APN02, GV4APN04
We undersigned SCHNEIDER ELECTRIC INDUSTRIES SAS declare that Schneider Electric branded products, when subject to correct installation, maintenance and use conforming to their intended purpose, according to applicable regulations and standards in the country where they are installed, to the supplier’s instructions and to accepted rules of the art comply with Essential Requirements of following European Directives.
This declaration of conformity is issued under the sole responsibility of the manufacturer.
Directive Basse Tension : 2014/35/UE
Directive CEM : 2014/30/UE
Directive ATEX : 2014/34/UE
Directive RoHS : 2011/65/UE : 2015/863/UE
Low Voltage Directive : 2014/35/EU
EMC Directive : 2014/30/EU
ATEX Directive : 2014/34/EU
RoHS Directive: 2011/65/EU : 2015/863/EU
Based on following standards : – EN 60947-4-1:2010 +A1: 2012 in conjunction with EN 60947-1:2007 +A1:2011 +A2:2014
– EN 60947-2:2017 in conjunction with EN 60947-1:2007 +A1:2011 +A2:2014
– EN 50495:2010
– EN IEC 63000:2018
Marquage ATEX / ATEX Marking :  and / or 0080 I (M2) [Ex e] QMS audited and products certified by notified body INERIS (identification number : 0080)
Parc Technologique Alata BP 2, F-60550 Verneuil en Halatte
EU type examination certificate n° INERIS 18ATEX0020X
The CE marking on the product(s) and/or its(their) packaging signifies that Schneider Electric holds the reference technical file(s) available to the European authorities.
CE marking application year: 2017

Marie-Christine Martinez
Customer Satisfaction & Quality
VPIssuance date : JNovember, 2 nd , 2021
Schneider Electric Industries SAS
Postal address / Adresse postale : ELECTROPOLE
http://www.schneider-electric.com
EU DoC – v4
EU Declaration of Conformity

UK Declaration of Conformity
Nr: SC17022402-UK

Products identification : Type of products : Motor Circuit Breaker
Models : TeSys GV4P, GV4PE
References: GV4P02 to GV4P115 and GV4PE02 to GV4PE115 and its accessories :
MX shunt trip : GV4AS027, GV4AS057, GV4AS137, GV4AS287, GV4AS487 MN undervoltage release :GV4AU027, GV4AU057, GV4AU137, GV4AU247, GV4AU286, GV4AU415, GV4AU486
Front extended rotary handle : GV4APN01, GV4APN02, GV4APN04
We undersigned SCHNEIDER ELECTRIC INDUSTRIES SAS declare that Schneider Electric branded products, when subject to correct installation, maintenance and use conforming to their intended purpose, according to applicable regulations and standards in the country where they are installed, to the supplier’s instructions and to accepted rules of the art comply with Essential Requirements of following United Kingdom Legislations
This declaration of conformity is issued under the sole responsibility of the manufacturer.
Electrical Equipment Regulations 2016 – UK SI 2016 No 1101
Electromagnetic Compatibility Regulations 2016 – UK SI 2016 No 1091
Equipment and Protective Systems Intended for use in Potentially Explosive Atmospheres Regulations 2016 – UK SI 2016 No 1107
The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012 – UK SI 2012 No 3032
Based on following standards : BS EN IEC 60947-4-1: 2010 + A1: 2012 and BS EN 60947-2:2017 in conjunction with BS EN
60947-1: 2007 + A1: 2011 + A2: 2014 EN 50495:2010 (SIL1) BS EN IEC 63000: 2018
QMS audited and products certified by Eurofins E&E CML Limited (number : 2503)
Newport Business Park | New Port Road | Ellesmere Port | CH65 4LZ | United Kingdom
UKEX type examination certificate n° CML 21UKEX7329X
The UKCA marking on the product(s) and/or its(their) packaging signifies that Schneider Electric holds the reference technical file(s) available to the UK authorities.
UKCA marking application year: 2021

Issued by :
David Williams – VP Marketing UK&I On behalf of :
Schneider Electric Limited Date (yyyy-mm-dd) : 2021 – 11 – 02
Place : Telford, United Kingdom
Schneider Electric Limited
Postal address: Stafford Park 5
Telford
TF3 3BL
United Kingdom
http://www.schneider-electric.com
UKCA DoC – v2 Power Products

Schneider Electric Industries SAS
35, rue Joseph Monier 92500 Rueil-Malmaison France
www.se.com
http://www.schneider-electric.co
DOCA0137EN-02 07/2021
Due to possible changes in standards and equipment,
the features described in this document in the form of text and images are subject to confirmation by Schneider Electric.
Design, production: Schneider Electric
© 2021 – Schneider Electric – All rights reserved
www.se.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals