SPECTRACOOL
Air Conditioner
n16 Model
INSTRUCTION MANUAL
N16 SpectraCool Air Conditioner
NOTE: Some of the information in this manual may not apply if a special unit was ordered. If additional drawings for a special unit are necessary, they have been inserted. Contact nVent Equipment Protection if further information is required.
WARRANTY AND RETURN POLICY
https://hoffman.nvent.com/en/hoffman/warranty-information
RECEIVING THE AIR CONDITIONER
Inspect the air conditioner. Check for concealed damage that may have occurred
during shipment. Look for dents, scratches, loose assemblies, evidence of oil,
etc. Damage evident upon receipt should be noted on the freight bill. Damage
should be brought to the attention of the delivering carrier — NOT to nVent
Equipment Protection — within 15 days of delivery. Save the carton and packing
material and request an inspection. Then file a claim with the delivering
carrier.
nVent Equipment Protection cannot accept responsibility for freight damages;
however, we will assist you in any way possible.
HANDLING AND TESTING THE AIR CONDITIONER
If the air conditioner has been in a horizontal position, be certain it is
placed in an upright, vertical or mounting position for a minimum of five (5)
minutes before operating.
CAUTION Do not attempt to operate the air conditioner while it is
horizontalor on its side, back or front. The refrigeration compressor is
filled with lubricating oil. This will cause permanent damage to the air
conditioner and also voids the warranty.
TEST FOR FUNCTIONALITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE.
Refer to the nameplate for proper electrical current requirements, and then
connect the power cord to a properly grounded power supply. Minimum circuit
ampacity should be at least 125% of the amperage shown in the design data
section for the appropriate model. No other equipment should be connected to
this circuit to prevent overloading.
Operate the air conditioner for five (5) to ten (10) minutes. No excessive
noise or vibration should be evident during this run period. The condenser
blower (ambient air), the evaporator blower (enclosure air), and the
compressor should be running.
Condenser air temperatures should be warmer than normal room temperatures
within a few minutes.
The compressor is provided with automatic reset thermal overload protection.
This thermoswitch is located and mounted inside the plastic enclosure clipped
to the compressor. The switch operates when the compressor overheats due to
clogged or dirty inlet air filter or if ambient air temperatures exceed
nameplate rating or if enclosure dissipated heat loads exceed the rated
capacity of the air conditioner. The thermal overload switch will actuate and
stop compressor operation. The blowers will continue to operate and the
compressor will restart after it has cooled to within the thermal overload
cut-in temperature setting.
INSTALLATION INSTRUCTIONS
- Inspect the air conditioner and verify correct functionality before mounting the air conditioner. See HANDLING AND TESTING THE AIR CONDITIONER on page 3.
- Using the cutout dimensions shown page 6 in this manual, prepare the air “IN” and air “OUT” openings, and mounting bolt hole pattern for the enclosure.
- Using the gasket kit provided, install gaskets to air conditioner.
- Mount air conditioner on enclosure using mounting bolts and screws provided. “EZ” mount tabs can be used to hold unit on enclosure while mounting in place. Allow unit to remain upright for a minimum of five (5) minutes before starting. Caution! Air conditioner must be in upright position during operation.
- To avoid cross-threading mounting inserts, start bolts by hand before tightening with a wrench or ratchet driver.
- When routing the drain tube, caution should be taken to keep it from kinking or being elevated above the exit point of the air conditioner. The drain tube must be on a continuous downward slope. A slight elevation of the tube could result in secondary trap. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN.
- Refer to top of nameplate for electrical requirements. Connect the power cord to a properly grounded power supply. Use of an extension cord is not recommended. Electrical circuit should be fused with slow blow or HACR circuit breaker.
DESIGN DATA
Model| Voltage| Hz| Phase| Cooling
BTU/Hr
@ 131 F/131 F| Cooling
BTU/Hr
@ 95 F/95 F| Max
Amps| Max Amb
Temp
°F/°C| Min. Amb
Temp
°F/°C| Max.
Enclosure
Temp °F/°C| Unit
Weight
---|---|---|---|---|---|---|---|---|---|---
N160116GXXX| 115| 50/60| 1| 800/900| 800/900| 4.0/3.8| 131/55| -40/-40|
131/55| 27/12.3
N160126GXXX| 230| 50/60| 1| 800/900| 800/900| 1.5/1.6| 131/55| -40/-40|
131/55| 27/12.3
DIMENSIONAL DRAWING MOUNTING CUTOUT DIMENSIONS
Cutout Instructions (As viewed from outside of enclosure)
NOTE: Phantom lines represent air conditioner.
COMPONENTS LIST
Part Description | Part Number |
---|---|
115V | 230V |
Fan, Condenser | 12101201SP |
Fan, Evaporator | 13101501SP |
Capacitor, Compressor | 52603209SP |
Coil, Condenser, Coated | 89092846SP |
Coil, Evaporator | 15100103SP |
Compressor | 10101682SP |
Filter, Air, Reusable | 89057626SP |
Filter/Dryer | 52602803SP |
Freeze stat (thermostat unit only) | 89097856SP |
Power Block | 89122933SP |
Terminal Block (thermostat unit only) | 10100303SP |
Overload, Compressor | 10100767SP |
Thermostat, SPST, 55-100F | 10106116SP |
Optional Heater | 10200423SP |
Optional Malf Switch | 89090313SP |
C/E Heater | 10103041SP |
Optional Remote Digital Controller | 89206050SP |
Optional Cool Relay(Controller unit only) | 10-1005-62SP |
Optional Heat Relay(Controller unit only) | 10-1005-36SP |
Optional Transformer(Controller unit only) | 10-1006-94SP |
Optional Controller Fuse(Controller unit only) | 89085114SP |
WIRE DIAGRAM
MECHANICAL THERMOSTAT UNIT SCHEMATIC
MECHANICAL THERMOSTAT UNIT WIRE DIAGRAM
REMOTE DIGITAL CONTROLLER UNIT SCHEMATIC
REMOTE DIGITAL CONTROLLER UNIT
TEMPERATURE CONTROL FOR MECHANICAL THERMOSTAT UNIT
NOTE: For Remote Digital Controller Unit, see instruction manual included with
Remote Digital Controller Box.
The electromechanical thermostat is factory preset to 75 F/23 C. To change the
temperature setting, remove the nylon plug from the front face of the unit.
Use a standard screwdriver to adjust thermostat. For cooler temperatures turn
clockwise, for warmer temperatures turn counterclockwise. Setpoint
differential is 6 F.
UNITS WITH HEAT
With a dial setting of 75 F, heat will turn on @ 70 F and turn off @ 75 F.
Cooling will turn on @ 85 F and turn off at 80 F.
There is a 10 F difference between the heater off setpoint and cooling on
setpoint to prevent both from operating at the same time.
The dial range of the thermostat is 50-95 F.
PRINCIPLES OF OPERATION
If electrical power to the air conditioner is interrupted and reapplied
immediately, (within 3 to 5 seconds), the compressor may not restart due to
the high back pressure of the compressor. It takes a minimum of one (1) minute
after shut-down for the compressor suction and discharge pressures to equalize
in order for the air conditioner to restart.
Operating the air conditioner below the minimum ambient temperature or above
the maximum ambient temperatures indicated on the nameplate voids all
warranties.
It is recommended that the warranty section of this manual be read in order to
familiarize yourself with parameters of restricted operation.
The moisture that the enclosure air can contain is limited. If moisture flows
from the drain tube continuously this can only mean that ambient air is
entering the enclosure. Be aware that frequent opening of the enclosure’s door
admits humid air, which the air conditioner must then dehumidify.
Units with the optional malfunction switch have a normally open connection
between the red & yellow wires and normally closed with the red and blue
wires. During alarm the red and yellow wires will be closed and the blue and
red wires will be open.
Maximum electrical ratings for the switch are 13A for 120 VAC and 10A for 240
VAC.
MAINTENANCE
COMPRESSOR
The compressor requires no maintenance. It is hermetically sealed, properly
lubricated at the factory and should provide years of satisfactory operating
service.
Should the refrigerant charge be lost, recharging ports (access fittings) on
the suction and discharge sides of the compressor are provided for recharging
and/or checking suction and discharge pressures.
Under no circumstances should the access fitting covers be loosened, removed
or tampered with.
Breaking of seals on compressor access fittings during warranty period will
void warranty on hermetic system.
Recharging ports are provided for the ease and convenience of reputable
refrigeration repair service personnel for recharging the air conditioner.
INLET AIR FILTER
Proper maintenance of the inlet air filter, located behind the front cover,
will assure normal operation of the air conditioner. If filter maintenance is
delayed or ignored, the maximum ambient temperatures under which the unit is
designed to operate will be decreased.
If the compressor’s operating temperature increases above designed conditions
due to a dirty or clogged filter (or plugged condenser coil), the air
conditioner’s compressor will stop operating due to actuation of the thermal
overload cut-out switch located on the compressor housing. As soon as the
compressor temperature has dropped to within the switch’s cut-in setting, the
compressor will restart automatically. However, the above condition will
continue to take place until the filter or coil has been cleaned. It is
recommended that power to the air conditioner be interrupted intentionally
when abnormally high compressor operating temperature causes automatic shut-
down of the unit. The above described shutdown is symptomatic of a clogged or
dirty filter, thus causing a reduction in cooling air flow across the surface
of the compressor and condenser coil.
Do not run the air conditioner for extended periods of time with the filter
removed. Particles of dust, lint, etc., can plug the fins of the condenser
coil which will give the same reaction as a plugged filter. The condenser coil
is not visible through the filter opening, so protect it with a filter.
Continued operation under the above conditions can and will damage and shorten
compressor life. The air conditioner is available with an easily removable
inlet filter to facilitate necessary cleaning. There should be no reason to
neglect this necessary maintenance.
HOW TO REMOVE, CLEAN OR INSTALL A NEW INLET AIR FILTER
RP aluminum washable air filters are designed to provide excellent filtering
efficiency with a high dust holding capacity and a minimum amount of
resistance to air flow. Because they are constructed entirely of aluminum they
are lightweight and easy to service. Optimum filter performance is maintained
by recoating the filters after washing with RP Super Filter Coat adhesive. To
achieve maximum performance from your air handling equipment, air filters
should be cleaned on a regular basis.
The inlet air filter is located behind the front cover. To access filter, pull
ring protruding from slot in side of front cover. The filter may now be
cleaned or new filter installed.
Cleaning Instructions:
- Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS.
- After flushing, allow filter to drain. Placing it with a corner down will assure complete drainage.
- Recoat the filters with RP Super Filter Coat adhesive. When spraying filter do so from both sides for maximum concentration of adhesive.
CONDENSER AND EVAPORATOR AIR MOVERS
Fan motors require no maintenance. All bearings, shafts, etc. are lubricated
during manufacturing for the life of the fan.
CAUTION
Operation of the air conditioner in areas containing airborne caustics or
chemicals can rapidly deteriorate filters, condenser coils, blowers and
motors, etc. Contact nVent Equipment Protection for special recommendations.
REFRIGERANT LOSS
Each air conditioner is thoroughly tested prior to leaving the factory to
insure against refrigeration leaks. Shipping damage or microscopic leaks not
found with sensitive electronic refrigerant leak detection equipment during
manufacture may require repair or recharging of the system. This work should
only be performed by qualified professionals, generally available through a
local, reputable air conditioning repair or service company.
Refer to the data on the nameplate which specifies the type of refrigerant and
the charge size in ounces.
Before recharging, make sure there are no leaks and that the system has been
properly evacuated into a deep vacuum.
TROUBLE SHOOTING
BASIC AIR CONDITIONING TROUBLE SHOOTING CHECK LIST
- Check manufacturer’s nameplate located on the unit for correct power supply.
- Turn on power to the unit. The evaporator (Enclosure or “COLD” air) fan should come on. Is there airflow?
YES, proceed to step 3.NO, possible problem:
• Open motor winding
• Stuck fan motor
• Obstructed blades| | Repair or Replace defective part
---|---|--- - Check thermostat setting and adjust thermostat to the lowest setting. This should turn the condenser fan and the compressor on. Did condenser fan and compressor come on when the thermostat was turned on?
YES, proceed to step 4.NO, possible problem:
• Defective thermostat| | Replace part
---|---|--- - Are both fans and the compressor running? If not the unit will not cool properly.
- Check condenser (Ambient or “HOT” air) fan for airflow. Is there airflow?
YES, proceed to step 6.NO, possible problem:
• Defective thermostat
• Open motor winding
• Stuck fan motor
• Obstructed blades| | Repair or Replace defective part
---|---|--- - Carefully check the compressor for operation – motor should cause slight vibration, and the outercase of the compressor should be warm. Is the compressor showing signs of this?
YES, wait 5 minutes, then proceed to step 7.NO, possible problem:
• Defective thermostat
• Defective capacitor
• Defective overload
• Defective relay| | Repair or Replace defective part
---|---|--- - Make sure the coils are clean. Then check evaporator “air in” and “air out” temperatures. If the temperatures are the same:
• Possible loss of refrigerant
• Possible bad valves in the compressor| | Repair or Replace defective part
---|---|--- - To check for a bad thermostat, turn power to the unit off. Remove the control box cover and place both thermostat wires onto one terminal (replace control box cover for safety). This will activate the switch in the thermostat. Turn the power on and if both fans and the compressor come on, the thermostat needs to be replaced.
SYMPTOMS AND POSSIBLE CAUSES:
SYMPTOM | POSSIBLE CAUSE |
---|---|
Unit won’t cool | Clogged fins on coil(s) |
Dirty filter
Fans not running
Compressor not running
Compressor runs, but has bad valves
Loss of refrigerant
Compressor tries to start but won’t run| Low line voltage at start. Should be
+1-10% rated voltage.
Compressor motor stuck
Bad contactor
Bad overload switch
Bad run/start capacitor
Unit blows breakers| Undersized breaker/fuse or not time delayed
Short in system
Getting water in enclosure| Drain plugged
Drain tube kinked
Enclosure not sealed (allowing humidity in)
Mounting gasket damaged
For additional technical information (i.e., amp draw, pressures, temperatures) , contact nVent Equipment Protection at 800-896-2665.
F-GAS INFORMATION
| N1 6011 6GXXX| N1 60126GXXX
---|---|---
Refrigerant| R134a| R134a
GWP| 1430| 1430
Factory Charge| 113 Grams| 107 Grams
CO2 Equivalent| 0.16 Tons| 0.15 Tons