ABUS Nexello 3I/3O Hybrid Module PLHA10100 Manual

June 8, 2024
ABUS

ABUS

Nexello 3I/3O Hybrid Module

SKU: PLHA10100

Quickstart

This is a
secure
Alarm Sensor
for
.

Please make sure the internal battery is fully charged.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The module is mounted via a bracket, it is tamper protected and has a back-up battery.Three Inputs for the connection of: Analogue sensors with voltage 0~12VDigital sensors with voltage 0~12VPotential-free outputs NC/NOOpen Collector Outputs OCThree Outputs for connecting actuators with a maximum of 24VDCSPDT (Single Pole, Double Throw) relay (toggle switch)functions:Configurable timer that automatically switches off after a preset period of time (default is 500 ms)The output can be set to activate automatically when the input terminals (see configuration setting)

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| The Lifeline Association is automatically established between the Z-Wave controller and the device at inclusion and defines what information is exchanged between the Z-Wave controller and the device.
---|---|---
2| 5| When a signal input is triggered, the unit first sends a BASIC Set ON. When the preset timer expires, it sends a BASIC Set OFF.
3| 5| When a signal input is triggered, the unit first sends a BASIC Set ON. When the preset timer expires, it sends a BASIC Set OFF.
4| 5| When a signal input is triggered, the unit first sends a BASIC Set ON. When the preset timer expires, it sends a BASIC Set OFF.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Signal input 1 – Mode

Several settings of the signal input and its triggering behaviour.
Size: 1 Byte, Default Value: 0

SettingDescription

0 No Relay is triggered, No Voltage is present, triggers below lowthreshold
2 – 0 Relay 1 is triggered, No Voltage is present, triggers below

lowthreshold
4 – 0| Relay 2 is triggered, No Voltage is present, triggers below lowthreshold
6 – 0| Relay 1 and 2 are triggered, No Voltage is present, triggers below lowthreshold
8 – 0| Relay 3 is triggered, No Voltage is present, triggers below lowthreshold
10 – 0| Relay 1 and 3 are triggered, No Voltage is present, triggers below lowthreshold
14 – 0| Relay 1, 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold
64 – 0| No Relay is triggered, 3,3V is present, triggers below lowthreshold
66 – 0| Relay 1 is triggered, 3,3V is present, triggers below lowthreshold
68 – 0| Relay 2 is triggered, 3,3V is present, triggers below lowthreshold
70 – 0| Relay 1 and 2 are triggered, 3,3V is present, triggers below lowthreshold
72 – 0| Relay 3 is triggered, 3,3V is present, triggers below lowthreshold
74 – 0| Relay 1 and 3 are triggered, 3,3V is present, triggers below lowthreshold
78 – 0| Relay 1, 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold
128 – 0| No Relay is triggered, No Voltage is present, triggers above highthreshold
130 – 0| Relay 1 is triggered, No Voltage is present, triggers above highthreshold
132 – 0| Relay 2 is triggered, No Voltage is present, triggers above highthreshold
134 – 0| Relay 1 and 2 are triggered, No Voltage is present, triggers above highthreshold
136 – 0| Relay 3 is triggered, No Voltage is present, triggers above highthreshold
138 – 0| Relay 1 and 3 are triggered, No Voltage is present, triggers above highthreshold
142 – 0| Relay 1, 2 and 3 are triggered, No Voltage is present, triggers above highthreshold
192 – 0| No Relay is triggered, 3,3V is present, triggers above highthreshold
194 – 0| Relay 1 is triggered, 3,3V is present, triggers above highthreshold
196 – 0| Relay 2 is triggered, 3,3V is present, triggers above highthreshold
198 – 0| Relay 1 and 2 are triggered, 3,3V is present, triggers above highthreshold
200 – 0| Relay 3 is triggered, 3,3V is present, triggers above highthreshold
202 – 0| Relay 1 and 3 are triggered, 3,3V is present, triggers above highthreshold
206 – 0| Relay 1, 2 and 3 are triggered, 3,3V is present, triggers above highthreshold
12 – 0| Relay 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold
76 – 0| Relay 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold
140 – 0| Relay 2 and 3 are triggered, No Voltage is present, triggers above highthreshold
204 – 0| Relay 2 and 3 are triggered, 3,3V is present, triggers above highthreshold

Parameter 10: Signal input 2 – voltage low-threshold

Setting of the voltage drop below which the signal input is triggered
Size: 1 Byte, Default Value: 10

SettingDescription

0 – 255 Adjustable from 0 – 255 in 100mV steps (10 = 1000mV = 1.0V)

Parameter 11: Signal input 3 – Mode

Same as Parameter 1, but applies to Signal Input 3
Size: 1 Byte, Default Value: 64

SettingDescription

0 No Relay is triggered, No Voltage is present, triggers below lowthreshold
2 – 0 Relay 1 is triggered, No Voltage is present, triggers below

lowthreshold
4 – 0| Relay 2 is triggered, No Voltage is present, triggers below lowthreshold
6 – 0| Relay 1 and 2 are triggered, No Voltage is present, triggers below lowthreshold
8 – 0| Relay 3 is triggered, No Voltage is present, triggers below lowthreshold
10 – 0| Relay 1 and 3 are triggered, No Voltage is present, triggers below lowthreshold
12 – 0| Relay 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold
14 – 0| Relay 1, 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold
64 – 0| No Relay is triggered, 3,3V is present, triggers below lowthreshold
66 – 0| Relay 1 is triggered, 3,3V is present, triggers below lowthreshold
68 – 0| Relay 2 is triggered, 3,3V is present, triggers below lowthreshold
70 – 0| Relay 1 and 2 are triggered, 3,3V is present, triggers below lowthreshold
72 – 0| Relay 3 is triggered, 3,3V is present, triggers below lowthreshold
74 – 0| Relay 1 and 3 are triggered, 3,3V is present, triggers below lowthreshold
76 – 0| Relay 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold
78 – 0| Relay 1, 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold
128 – 0| No Relay is triggered, No Voltage is present, triggers above highthreshold
130 – 0| Relay 1 is triggered, No Voltage is present, triggers above highthreshold
132 – 0| Relay 2 is triggered, No Voltage is present, triggers above highthreshold
134 – 0| Relay 1 and 2 are triggered, No Voltage is present, triggers above highthreshold
136 – 0| Relay 3 is triggered, No Voltage is present, triggers above highthreshold
138 – 0| Relay 1 and 3 are triggered, No Voltage is present, triggers above highthreshold
140 – 0| Relay 2 and 3 are triggered, No Voltage is present, triggers above highthreshold
142 – 0| Relay 1, 2 and 3 are triggered, No Voltage is present, triggers above highthreshold
192 – 0| No Relay is triggered, 3,3V is present, triggers above highthreshold
194 – 0| Relay 1 is triggered, 3,3V is present, triggers above highthreshold
196 – 0| Relay 2 is triggered, 3,3V is present, triggers above highthreshold
198 – 0| Relay 1 and 2 are triggered, 3,3V is present, triggers above highthreshold
200 – 0| Relay 3 is triggered, 3,3V is present, triggers above highthreshold
202 – 0| Relay 1 and 3 are triggered, 3,3V is present, triggers above highthreshold
204 – 0| Relay 2 and 3 are triggered, 3,3V is present, triggers above highthreshold
206 – 0| Relay 1, 2 and 3 are triggered, 3,3V is present, triggers above highthreshold

Parameter 12: Relay output 3 – switching time

Setting for the duration of the switching time when the relay output is switched.
Size: 1 Byte, Default Value: 5

SettingDescription

0 relay output is permanently switched
1 – 255 Adjustable duration from 1 – 255 in 100ms steps

Parameter 13: Signal input 3 – switching time at association group 4

Setting for the duration of the switching time at association group 4 when signal input is triggered.
Size: 1 Byte, Default Value: 180

SettingDescription

0 Switched permanently
1 – 255 Adjustable duration from 1 – 255 in seconds

Parameter 14: Signal input 3 – voltage high-threshold

Setting, from which voltage rise the signal input is triggered
Size: 1 Byte, Default Value: 25

SettingDescription

0 – 255 Adjustable from 0 – 255 in 100mV steps (25 = 2500mV = 2.5V)

Parameter 15: Signal input 3 – voltage low-threshold

Setting of the voltage drop below which the signal input is triggered
Size: 1 Byte, Default Value: 10

SettingDescription

0 – 255 Adjustable from 0 – 255 in 100mV steps (10 = 1000mV = 1.0V)

Parameter 16: Voltage Report (time)

The interval time of the voltage report for signal input 1-3
Size: 1 Byte, Default Value: 30

SettingDescription

1 – 255 Adjustable from 1 – 255 in minutes

Parameter 17: Sabotage Alarm Relay output

Setting whether a relay output must be switched in case of a sabotage alarm.
Size: 1 Byte, Default Value: 0

SettingDescription

0 No Relays are triggered
2 – 0 Relay 1 is triggered
4 – 0 Relay 2 is triggered
6 – 0 Relay 1 and 2 are triggered
8 – 0 Relay 3 is triggered
10 – 0 Relay 1 and 3 are triggered
12 – 0 Relay 2 and 3 are triggered
14 – 0 Relay 1, 2 and 3 are triggered

Parameter 18: Signal input – Activate arm / disarm message

Setting whether a signal input should send an armed and an unarmed message instead of a trigger signal.
Size: 1 Byte, Default Value: 0

SettingDescription

0 0 = No signal input sends arm/disarm message
1 1 = Signal input 1 sends arm/disarm message
2 2 = Signal input 2 sends arm/disarm message
3 3 = Signal input 3 sends arm/disarm message

Parameter 2: Relay output 1 – switching time

Setting for the duration of the switching time when the relay output is switched.
Size: 1 Byte, Default Value: 5

SettingDescription

0 relay output is permanently switched
1 – 255 Adjustable duration from 1 – 255 in 100ms steps

Parameter 3: Signal input 1 – switching time at association group 2

Setting for the duration of the switching time at association group 2 when signal input is triggered.
Size: 1 Byte, Default Value: 180

SettingDescription

0 Switched permanently
1 – 255 Adjustable duration from 1 – 255 in seconds

Parameter 4: Signal input 1 – voltage high-threshold

Setting, from which voltage rise the signal input is triggered
Size: 1 Byte, Default Value: 25

SettingDescription

0 – 255 Adjustable from 0 – 255 in 100mV steps (25 = 2500mV = 2.5V)

Parameter 5: Signal input 1 – voltage low-threshold

Setting of the voltage drop below which the signal input is triggered
Size: 1 Byte, Default Value: 10

SettingDescription

0 – 255 Adjustable from 0 – 255 in 100mV steps (10 = 1000mV = 1.0V)

Parameter 6: Signal input 2 – Mode

Same as Parameter 1, but applies to Signal Input 2
Size: 1 Byte, Default Value: 64

SettingDescription

0 No Relay is triggered, No Voltage is present, triggers below lowthreshold
2 – 0 Relay 1 is triggered, No Voltage is present, triggers below

lowthreshold
4 – 0| Relay 2 is triggered, No Voltage is present, triggers below lowthreshold
6 – 0| Relay 1 and 2 are triggered, No Voltage is present, triggers below lowthreshold
8 – 0| Relay 3 is triggered, No Voltage is present, triggers below lowthreshold
10 – 0| Relay 1 and 3 are triggered, No Voltage is present, triggers below lowthreshold
12 – 0| Relay 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold
14 – 0| Relay 1, 2 and 3 are triggered, No Voltage is present, triggers below lowthreshold
64 – 0| No Relay is triggered, 3,3V is present, triggers below lowthreshold
66 – 0| Relay 1 is triggered, 3,3V is present, triggers below lowthreshold
68 – 0| Relay 2 is triggered, 3,3V is present, triggers below lowthreshold
70 – 0| Relay 1 and 2 are triggered, 3,3V is present, triggers below lowthreshold
72 – 0| Relay 3 is triggered, 3,3V is present, triggers below lowthreshold
74 – 0| Relay 1 and 3 are triggered, 3,3V is present, triggers below lowthreshold
76 – 0| Relay 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold
78 – 0| Relay 1, 2 and 3 are triggered, 3,3V is present, triggers below lowthreshold
128 – 0| No Relay is triggered, No Voltage is present, triggers above highthreshold
130 – 0| Relay 1 is triggered, No Voltage is present, triggers above highthreshold
132 – 0| Relay 2 is triggered, No Voltage is present, triggers above highthreshold
134 – 0| Relay 1 and 2 are triggered, No Voltage is present, triggers above highthreshold
136 – 0| Relay 3 is triggered, No Voltage is present, triggers above highthreshold
138 – 0| Relay 1 and 3 are triggered, No Voltage is present, triggers above highthreshold
140 – 0| Relay 2 and 3 are triggered, No Voltage is present, triggers above highthreshold
142 – 0| Relay 1, 2 and 3 are triggered, No Voltage is present, triggers above highthreshold
192 – 0| No Relay is triggered, 3,3V is present, triggers above highthreshold
194 – 0| Relay 1 is triggered, 3,3V is present, triggers above highthreshold
196 – 0| Relay 2 is triggered, 3,3V is present, triggers above highthreshold
198 – 0| Relay 1 and 2 are triggered, 3,3V is present, triggers above highthreshold
200 – 0| Relay 3 is triggered, 3,3V is present, triggers above highthreshold
202 – 0| Relay 1 and 3 are triggered, 3,3V is present, triggers above highthreshold
204 – 0| Relay 2 and 3 are triggered, 3,3V is present, triggers above highthreshold
206 – 0| Relay 1, 2 and 3 are triggered, 3,3V is present, triggers above highthreshold

Parameter 7: Relay output 2 – switching time

Setting for the duration of the switching time when the relay output is switched.
Size: 1 Byte, Default Value: 5

SettingDescription

0 relay output is permanently switched
1 – 255 Adjustable duration from 1 – 255 in 100ms steps

Parameter 8: Signal input 2 – switching time at association group 3

Setting for the duration of the switching time at association group 3 when signal input is triggered.
Size: 1 Byte, Default Value: 180

SettingDescription

0 Switched permanently
1 – 255 Adjustable duration from 1 – 255 in seconds

Parameter 9: Signal input 2 – voltage high-threshold

Setting, from which voltage rise the signal input is triggered
Size: 1 Byte, Default Value: 25

SettingDescription

0 – 255 Adjustable from 0 – 255 in 100mV steps (25 = 2500mV = 2.5V)

Technical Data

Hardware Platform SD3502
Device Type Notification Sensor
Network Operation Always On Slave
Firmware Version HW: 1 FW: 1.00:00.04
Z-Wave Version 6.81.06
Certification ID ZC10-20076949
Z-Wave Product Id 0x0403.0x0003.0x0007
Security V2 S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Basic
  • Battery
  • Configuration V4
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Multi Channel Association V3
  • Multi Channel V4
  • Notification V8
  • Powerlevel
  • Security
  • Security 2
  • Sensor Multilevel V5
  • Supervision
  • Switch Binary
  • Transport Service V2
  • Version V3
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals