Q-light Z-Wave Zerodim 2pol 1400441 Manual
- June 8, 2024
- Q-light
Table of Contents
- Q-light
- Z-Wave Zerodim 2pol
- SKU: 1400441
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: Minimum brightness level
- Parameter 2: Maximum brightness level
- Parameter 3: Automatic control – dimming step size
- Parameter 4: Automatic control – time of a dimming step
- Parameter 5: Manual control – dimming step size
- Parameter 6: Manual control – time of a dimming step
- Parameter 7: Memory function after power failure
- Parameter 8: Scene ID set
- Parameter 9: Timer functionality (auto – off)
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Q-light
Z-Wave Zerodim 2pol
SKU: 1400441
Quickstart
This is a
secure
Light Dimmer
for
.
To run this device please connect it to your mains power supply.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
Zerodim Z-Wave 2pol by Q-light is a wireless smart home device.Features:- breaks both phases (L and N)- 0-99% dimming range- 2-180W LED load- Compatible with any Z-Wave or Z-Wave Plus Controller- There is memorized function at power off- OverLoad protection- Soft start function- SmartStart- This device is a security enable Z-Wave Plus product that is able to use encrypted Z-Wave Plus messages to communicate to other security enable Z-Wave Plus products.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 1| Lifeline group supports the following command classes:1.Device Reset
Locally: triggered upon reset.2.Switch Multilevel Report: triggered by local
light level change.3.Notification Report: triggered by Notification.
---|---|---
2| 5| Mirror of endpoint 1, group 2.
3| 5| Mirror of endpoint 1, group 3.
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: Minimum brightness level
This parameter refers to the minimum brightness that the dimmer can achieve.
This parameter cannot exceed the Maximum brightness level. The default value
is 12.
Size: 1 Byte, Default Value: 12
SettingDescription
1 – 98| Set the desired value from 1 to 98% for the minimum dim level that the
dimmer is restricted to; the dimmer will not go lower than the value set here.
---|---
Parameter 2: Maximum brightness level
This parameter refers to the maximum brightness that the dimmer can achieve
Size: 1 Byte, Default Value: 99
SettingDescription
2 – 99| Set the desired value from 2 to 99% for the maximum dim level that the
dimmer is restricted to; the dimmer will not go higher than the value set
here.
---|---
Parameter 3: Automatic control – dimming step size
This parameter defines the percentage value of dimming step during the
automatic control.
Size: 1 Byte, Default Value: 1
SettingDescription
1 – 99| Set the desired value from 1 to 99% for dim step size;The dimmer is
dimmed up or down based on the percentage of the value set here for each step
during the automatic control.
---|---
Parameter 4: Automatic control – time of a dimming step
This parameter defines the time of single dimming step set in parameter 3
during the automatic control.Available settings:1-255(10ms-2.55s,in 10ms
steps).Default value:1(10ms)
Size: 2 Byte, Default Value: 1
SettingDescription
1 – 255| Set the desired value from 1 to 255(10ms-2.55s,in 10ms steps) for the
time of a dimming step. The amount of time the dimmer takes to adjust each
step during the automatic control is the value set here.
---|---
Parameter 5: Manual control – dimming step size
This parameter defines the percentage value of dimming step during the
manual control.
Size: 1 Byte, Default Value: 1
SettingDescription
1 – 99| Set the desired value from 1 to 99% for dim step size;The dimmer is
dimmed up or down based on the percentage of the value set here for each step
during the manual control.
---|---
Parameter 6: Manual control – time of a dimming step
This parameter defines the time of single dimming step set in parameter 5
during the manual control.Available settings:1-255(10ms-2.55s,in 10ms
steps).Default value:5(50ms)
Size: 2 Byte, Default Value: 5
SettingDescription
1 – 255| Set the desired value from 1 to 255(10ms-2.55s,in 10ms steps) for the
time of a dimming step. The amount of time the dimmer takes to adjust each
step during the manual control is the value set here.
---|---
Parameter 7: Memory function after power failure
If this parameter is set to 1,the Device will restore its brightness before
power failure.
Size: 1 Byte, Default Value: 1
SettingDescription
0 – 1| Set the desired value from 0 to 1 to turn on/off the memory
function.Setting this value to 0 turns off the dimmer’s Memory
fucntion.Setting this value to 1 truns on the dimmer’s Memory function.
---|---
Parameter 8: Scene ID set
_Scene ID is set by this configuration.Note: The actual action of each SCENE
ID are set by SCENE_ACTUATORCONF(0x26) command.
Size: 2 Byte, Default Value: 1
SettingDescription
1 – 255| Set the desired number from 1 to 255 as current scene ID.The dimmer
will drive the load lamp based on the brightness stored in the scene ID set
here,when the scene function is triggered.But the brightness value stored in
each scene ID is set by the SCENE_ACTUATOR_CONF(0X26) command
---|---
Parameter 9: Timer functionality (auto – off)
This parameter allows to automatically switch off the device after specified
time from switching on the light source. It may be useful when the Zerodim
Z-Wave is installed in the stairway.Available settings:0 – Function
disabled1-32767 – time to turn off measured in seconds(1s-9.1h)
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 32767| Set the desired value from 0 to 32767(0–Function disable,1-32767
–1s-32767s) fas the time at which the dimmer will automatically turn
off.Setting this value to 0 will disable the dimmer’s countdown function.Set
this value to 1-32767 and the dimmer will turn off when the dimmer countdown
reaches the set value.
---|---
Technical Data
Hardware Platform | ZM5202 |
---|---|
Device Type | Light Dimmer Switch |
Network Operation | Always On Slave |
Firmware Version | HW: 255 FW: 4.03 |
Z-Wave Version | 6.81.06 |
Certification ID | ZC10-20056914 |
Z-Wave Product Id | 0x0433.0x0003.0x000E |
Color | White |
Firmware Updatable | Not Updatable |
Z-Wave Scene Type | Central Scene |
Neutral Wire Required | ok |
Security V2 | S2_UNAUTHENTICATED |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Supported Command Classes
- Association Grp Info
- Association V2
- Basic V2
- Configuration
- Device Reset Locally
- Firmware Update Md V4
- Manufacturer Specific V2
- Multi Channel Association V3
- Multi Channel V4
- Notification V8
- Powerlevel
- Scene Activation
- Scene Actuator Conf
- Security
- Security 2
- Supervision
- Switch Multilevel V4
- Transport Service V2
- Version V3
- Zwaveplus Info V2
Controlled Command Classes
- Basic V2
- Switch Multilevel V4
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>