SEIKOM ELECTRONIC RLSW5A Instruction Manual

June 13, 2024
SEIKOM ELECTRONIC

SEIKOM ELECTRONIC RLSW5A Instruction Manual
SEIKOM ELECTRONIC RLSW5A

Attention!

Connection and commissioning must be performed by properly authorized and qualified personnel!
Connections to mains supply (L, N) must be made by means of a protected isolating switch with usual fuses. As a matter of principle, the General VDE regulations must be complied with (VDE 0100, VDE 0113, VDE 0160). If the potential-free contact is connected to an extra-low safety voltage, sufficient insulation must be provided for the connecting cables up to the terminal, since otherwise the double insulation to the mains voltage side may be impaired. The current load capacity of the potential-free contact is limited to 6A.
Therefore, the electrical circuit of the potential-free contact must be protected by a 6.3A fuse.

Installation Conditions RLSW5A

To avoid malfunctions the following points should be observed:

  • Install the monitoring device as described in the “Installation Conditions”.
  • Connect the supply voltage.
  • Switch on the flow generator.
  • With potentiometer “Gain” adapt the output signal to the flow.
  • The current is set automatically.
  • The flow monitor is now operational

What to do if the monitoring device does not work properly

Problem cause solution
device does not work in any way no or wrong suplly voltage check supply

voltage and connection
device does not recognice flow| sensor is not installed properly| check the sensor’s installation
| flow is out of range| change the tube’s diameter
device reacts in a different way| sensor is highly polluted| maintain the sensor
device reacts in fast media tepmerature changes| temperature gradient is out of range| check the temp. gradient of your installation

General Information

The RLSW5A is a compact unit including a flow sensor as well as the monitoring device. It provides a analogue output with the range of 0-10V and 0-20mA. To adapt the output to your normal flow the RLSW5A provides a potentiometer to set the maximum flow to the requested voltage.

Proper use

The flow controllers of the series RLSW5 are intended to be used in monitoring of flow speeds of gaseous media within the specified technical data. A main area of application is heating, ventilating and air conditioning in the field of automated building systems.

Function principle

The flow controllers of the series RLSW5 function according to the calorimetric principle. The units are switched when a certain pre-selected threshold value is reached. In the calorimetric measuring principle a tempera turesensitive resistor is heated. The heating procedure is achieved by a separate heating resistor. Flow in the medium dissipates heat from the precision resistor, the temperature of the resistor changes and thus its resistance value. This change is evaluated by the unit. However, not only the flow speed of the medium has an influence of the dissipated amount of heat, but also its temperature, therefore a relation between flow and temperature must be established. This is achieved by a second, temperature-dependent precision resistor near the first one. The second precision resistor (temperature compensation) is not heated and serves to measure the temperature only.

Flow>= threshold value

|

Signal output switched

|

Yellow LED “Airflow” enlightened

---|---|---

Flow< threshold value

|

Signal output not switched

|

Yellow LED “Airflow darkened

Technical Data

Article-No. 81448/10 80448/10
Operating Voltage 24V AC/DC 230V AC 50/60Hz
Voltage tolerance ±5% ±6%
Over voltage category
Signal lamp, voltage Green LED Green LED
Power consumption 4VA 4VA
Ambient temperature -20…+60°C -20…+60°C
Signal output voltage 0-10V (Ra=10kOhm), relatively 0-10V (Ra=10kOhm),
Signal output current 0-20mA (Ra=0.2kOhm), relatively 0-20mA (Ra=0.2kOhm),
Output accuracy +/- 10% measured value +/- 10% measured value
Reproducablity of output +/- 1% upper range value +/- 1% upper range value
Media temperature range 0…70°C 0…70°C
Temperature gradient 15K/min 15K/min
Airflow range 0.1-30m/s 0.1-30m/s
Sensor integrated integrated
Immersion depth 130mm 130mm
Process connection PG7, Mounting flange PG7, Mounting flange
Sensor material MS58, nickel-plated MS58, nickel-plated
Pressure resistance 10bar 10bar
Electrical connection 6 terminals, 2.5mm² 6 terminals, 2.5mm²
protection category, housing IP65 IP65
protection category, terminals IP67 IP67
conatimation class 2 2
Housing dimensions L=56mm, W=84mm, H=80mm L=56mm, W=84mm,
Accessory Mounting flange Mounting flange

Installation Instruction

To avoid malfunctions, please refer to the following points:

  • The tip of the sensor should be as close as possible to the centre of the pipe. The traverse hole in the shaft of the sensor must be within the full of the gaseous medium.
  • The marking is intended as an assembly aid.
  • In case of vertical pipes, the direction of flow should be upwards.
  • The sensor needs at least 5xD (inside pipe diameter) of free inlet and 3xD (inside pipe diameter) of outlet path.
  • Maintain the flow controller by means of the hexagon of the senor housing only.
  • The flow controller can be installed any position.
  • Perfect measuring results need a perfect installation!

Electrical Connection

Attention: Main Ground and output ground are not be bridged as it can destroy the electronics!
Electrical Connection

Dimensions

Dimensions

Mistakes and misprints are not to be excluded. All information „without guarantee“. 03/2022

SEIKOM-Electronic GmbH & Co. KGFortunastr.20D-42489 Wülfrath
Telefon: +49(0) 20 58/20 44  Fax: +49(0) 20 58 / 79 111
E-Mail: [email protected]
Internet: http://www.seikom-electronic.de

SEIKOM ELECTRONIC Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SEIKOM ELECTRONIC User Manuals

Related Manuals