Nortek GoControl Z-Wave Plus Battery Powered Smart Thermostat GC-TBZ48L Manual
- June 8, 2024
- NORTEK
Table of Contents
- Nortek
- GoControl Z-Wave Plus Battery Powered Smart Thermostat
- SKU: GC-TBZ48L
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: System Type
- Parameter 10: Setpoint H/C Delta
- Parameter 11: H Delta Stage 1 ON
- Parameter 12: H Delta Stage 1 OFF
- Parameter 13: H Delta Stage 2 ON
- Parameter 14: H Delta Stage 2 OFF
- Parameter 15: H Delta Aux ON
- Parameter 16: H Delta Aux OFF
- Parameter 17: C Delta Stage 1 ON
- Parameter 18: C Delta Stage 1 OFF
- Parameter 186: 0xBA
- Parameter 187: 0xBB
- Parameter 19: C Delta Stage 2 ON
- Parameter 2: Fan Type
- Parameter 20: C Delta Stage 2 OFF
- Parameter 21: Mechanical Status
- Parameter 22: SCP Status
- Parameter 23: Autosend Enable Bits
- Parameter 24: Display Lock
- Parameter 26: Backlight Timer
- Parameter 3: Change Over Type
- Parameter 33: Max Heat Setpoint
- Parameter 34: Min Cool Setpoint
- Parameter 38: Schedule Enable
- Parameter 39: Run/Hold Mode
- Parameter 4: 2nd Stage Heat Enable
- Parameter 40: Setback Mode
- Parameter 41: Un-Occupied HSP
- Parameter 42: Un-Occupied HSP
- Parameter 43: Remote Sensor 1 Node Number
- Parameter 46: Remote Sensor 1 Temperature
- Parameter 48: Internal Sensor Temp Offset
- Parameter 49: R1 Sensor Temp Off set
- Parameter 5: Aux Heat Enable
- Parameter 52: Filter Timer (hours)
- Parameter 53: Filter Timer Max (hrs)
- Parameter 54: Heat Timer (hours)
- Parameter 55: Cool Timer (hours)
- Parameter 6: 2nd Stage Cool Enable
- Parameter 61: Fan Purge Heat
- Parameter 62: Fan Purge Cool
- Parameter 7: C/F Type
- Parameter 8: MOT
- Parameter 9: MRT
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Nortek
GoControl Z-Wave Plus Battery Powered Smart Thermostat
SKU: GC-TBZ48L
Quickstart
This is a ****
HVAC-Thermostat
for
U.S. / Canada / Mexico.
Please make sure the internal battery is fully charged.
To add this device to your network execute the following action:
Inclusion is started by putting the controller into add node state and
performing the General Programming Procedure. As part of the process, the
thermostat sends a node information frame at normal power. Low power inclusion
is not possible.General Programming Procedure (for controllers supporting the
thermostat device class):1. Set your primary controller to Include, add or
Install mode, to add the thermostat as a node on your network (see your
controllers user manual for detailed instructions).2. Press any button to take
thermostat out of sleep mode.3. Press and hold FAN button for 5 seconds. SETUP
will be displayed in the status display line.4. Scroll to Z-Wave usingbuttons.
Press SELECT.5. When prompted by your Z-Wave controller, Press the YES button
in the Z-Wave Install screen.6. Press SELECT (mode button) to add thermostat
to network.7. Display line should fl ash WAIT then SUCCESS if Z-Wave
connection is made.8. If Z-Wave does not connect to controller, WAIT, then
FAIL will flash in status display line.9. If thermostat fails to connect,
repeat Steps three (3) thru (7) to re-try connecting.Your controller will
indicate the thermostat was successfully added to its network (see your
controllers user manual for details). Also, you can check if the thermostat
was successfully added to the network by checking the ZHID (Home ID) and ZNID
(Node ID) located in the Thermostat Info screen.For other specific tasks such
as adding the thermostat to Scenes or Groups, or deleting the thermostat from
an existing network, refer to the Z-Wave controller instructions.
Please refer to the
Manufacturers
Manual for more information.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
The GC-TBZ48 Z-Wave Plus Thermostat is a programmable, Z-Wave communicating thermostat. It can be powered using 24VAC, or using four (4) AA batteries. Using Z-Wave technology, end users have the ability to use most compatible Z-Wave hubs/controllers to operate and animate the thermostat, configure programming settings, as well as to display current conditions in the home or office.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
Factory ResetWARNING: Please use this procedure only when the Z-Wave Primary Controller is missing or otherwise inoperable.To reset the TBZ48L’s Z-Wave parameters to Factory Settings (both Z-Wave and HVAC settings):1. Remove power from the TBZ48L.2. Hold down the MODE and FAN buttons simultaneously while powering up.3. Release when RESET appears on the Status Line.4. Once the TBZ48 resets the Z-Wave and HVAC settings, a DONE confirmation message will appear on the screen before the thermostat self-reboots.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
Inclusion is started by putting the controller into add node state and performing the General Programming Procedure. As part of the process, the thermostat sends a node information frame at normal power. Low power inclusion is not possible.General Programming Procedure (for controllers supporting the thermostat device class):1. Set your primary controller to Include, add or Install mode, to add the thermostat as a node on your network (see your controllers user manual for detailed instructions).2. Press any button to take thermostat out of sleep mode.3. Press and hold FAN button for 5 seconds. SETUP will be displayed in the status display line.4. Scroll to Z-Wave usingbuttons. Press SELECT.5. When prompted by your Z-Wave controller, Press the YES button in the Z-Wave Install screen.6. Press SELECT (mode button) to add thermostat to network.7. Display line should fl ash WAIT then SUCCESS if Z-Wave connection is made.8. If Z-Wave does not connect to controller, WAIT, then FAIL will flash in status display line.9. If thermostat fails to connect, repeat Steps three (3) thru (7) to re-try connecting.Your controller will indicate the thermostat was successfully added to its network (see your controllers user manual for details). Also, you can check if the thermostat was successfully added to the network by checking the ZHID (Home ID) and ZNID (Node ID) located in the Thermostat Info screen.For other specific tasks such as adding the thermostat to Scenes or Groups, or deleting the thermostat from an existing network, refer to the Z-Wave controller instructions.
Exclusion
Exclusion is started by putting the controller into remove node state and performing the General Programming Procedure. As part of the process, the thermostat sends a node information frame at normal power. Low power exclusion is not possible.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 5| Z-Wave Plus LifelineGroup 1 Association is the default status report
channel in Z-Wave+ lifeline requirements. Group 1 Alerts are to notify an
associated device of a thermostat generated change. Thermostat
generatedchanges are those changes that originate at or by the thermostat. The
following Command Classes can be sent to the lifeline: BATTERY_REPORT
DEVICE_RESET_LOCALLY_NOTIFICATION SENSOR_MULTILEVEL_REPORT
THERMOSTAT_SETPOINT_REPORT THERMOSTAT_SETPOINT_MODE THERMOSTAT_FANMODE_REPORT
THERMOSTAT_FANSTATE_REPORT THERMOSTAT_OPERATINGSTATE_REPORT
THERMOSTAT_CONFIGURATION_REPORT
---|---|---
2| 5| Group 2 Association Alerts will send a BASIC_SET 0xFF when a Cool Call
starts and a BASIC_SET 0x00 when the Cool Call ends.
3| 5| Group 3 Association Alerts will send a BASIC_SET 0xFF when a Heat Call
starts and a BASIC_SET 0x00 when the Heat Call ends.
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: System Type
Sets the system type. Standard or Heat Pump
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Standard |
---|---|
1 | Heat Pump |
Parameter 10: Setpoint H/C Delta
Sets the minimum separation between heating and cooling setpoints. NOTE:
Attempts to lower cooling setpoint below the heating setpoint will PUSH the
heating setpoint down to maintainthis separation. The same applies to setting
the heating setpoint above the cooling setpoint, it will PUSH the cooling
setpoint up to maintain the setpoint delta separation.
Size: 1 Byte, Default Value: 3
SettingDescription
3 – 15 | Degrees |
---|
Parameter 11: H Delta Stage 1 ON
Sets the delta from setpoint that stage 1 heating starts
Size: 1 Byte, Default Value: 1
SettingDescription
1 – 6 | Degrees |
---|
Parameter 12: H Delta Stage 1 OFF
Sets the delta from setpoint that stage 1 heating stops.Stage 1 turns off at
setpoint + Delta Stage 1.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 5 | Degrees |
---|
Parameter 13: H Delta Stage 2 ON
Sets the delta from setpoint that stage 2 heating starts
Size: 1 Byte, Default Value: 2
SettingDescription
2 – 7 | Degrees |
---|
Parameter 14: H Delta Stage 2 OFF
Sets the delay from setpoint that stage 2 heating stops.Stage 2 turns off at
setpoint + Delta Stage 2.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 6 | Degrees |
---|
Parameter 15: H Delta Aux ON
Sets the delta from setpoint that stage 3 heating starts
Size: 1 Byte, Default Value: 3
SettingDescription
3 – 8 | Degrees |
---|
Parameter 16: H Delta Aux OFF
Sets the delta from setpoint that stage 3 heating stops.Stage 3 turns off at
setpoint + Delta Stage 3
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 7 | Degrees |
---|
Parameter 17: C Delta Stage 1 ON
Sets the delta from setpoint that stage 1 cooling starts.
Size: 1 Byte, Default Value: 1
SettingDescription
1 – 6 | Degrees |
---|
Parameter 18: C Delta Stage 1 OFF
Sets the delta from setpoint that stage 1 cooling stops.Stage 1 turns off at
setpoint – Delta Stage 1
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 5 | Degrees |
---|
Parameter 186: 0xBA
Temperature Delta Autosend Threshold (how many degree change from last
autosend). 1 to 5 degrees.
Size: 1 Byte, Default Value: 2
SettingDescription
1 – 5 | Degrees |
---|
Parameter 187: 0xBB
Periodic Temperature Send Interval (min). 0=Disabled. 1-120 minutes.
Size: 1 Byte, Default Value: 0
SettingDescription
1 – 120 | Minutes |
---|
Parameter 19: C Delta Stage 2 ON
Sets the delta from setpoint that stage 2 cooling starts.
Size: 1 Byte, Default Value: 2
SettingDescription
2 – 7 | Degrees |
---|
Parameter 2: Fan Type
Sets the fan type. Electric (Fan w/Heat) or Gas (no Fan w/Heat)
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Gas (no fan w/Heat |
---|---|
1 | Electric (Fan w/Heat |
Parameter 20: C Delta Stage 2 OFF
Sets the delta from setpoint that stage 2 cooling stops.Stage 2 turns off at
setpoint – Delta Stage 2.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 6 | Degrees |
---|
Parameter 21: Mechanical Status
_Thermostat Mechanical status config parameters.MECH_H1 0x0001MECH_H2
0x0002MECH_H3 0x0004MECH_C1 0x0008MECH_C2 0x0010PHANTOM_F 0x0020MECH_F
0x0040MANUALF 0x0080reserved 0x0100
Size: 2 Byte, Default Value: 0
SettingDescription
1 | MECH_H1 |
---|---|
2 | MECH_H2 |
4 | MECH_H3 |
8 | MECH_C1 |
16 | MECH_C2 |
32 | PHANTOM_F |
64 | MECH_F |
128 | MANUAL_F |
256 | reserved |
Parameter 22: SCP Status
_Thermostat State Config ParametersSTATE_HEAT 0x01STATE_COOL 0x02STATE_2ND
0x04STATE_3RD 0x08STATE_FAN 0x10STATE_LAST 0x20STATE_MOT 0x40STATEMRT 0x80
Size: 1 Byte, Default Value: 0
SettingDescription
1 | STATE_HEAT |
---|---|
2 | STATE_COOL |
4 | STATE_2ND |
8 | STATE_3RD |
16 | STATE_FAN |
32 | STATE_LAST |
64 | STATE_MOT |
128 | STATE_MRT |
Parameter 23: Autosend Enable Bits
_When set, the corresponding report is sent out unsolicited when a changed
node is detected to the nodes in the association list.TEMPERATURE
(CC_SENSOR_MULTILEVEL) 0x0001SETPOINT H (CC_THERMOSTAT_SETPOINT)
0x0002SETPOINT C (CC_THERMOSTAT_SETPOINT) 0x0004MODE (CC_THERMOSTATMODE)
0x0008FANMODE (CC THERMOSTAT_FAN_MODE) 0x0010FANSTATE
(CC_THERMOSTAT_FAN_STATE) 0x0020OPERATING STATE (CC_THERMOSTAT_OPERATING
STATE) 0x0040SCHEDENABLE (CCCONFIGURATION #38) 0x0080SETBACK (CC
CONFIGURATION #40) 0x0100RUNHOLD (CC_CONFIGURATION #39) 0x0200DISPLAYLOCK
(CC_CONFIGURATION #24) 0x0400BATTERY 6 (CC_BATTERY) 0x2000MECH STATUS
(CC_CONFIGURATION # 21) 0x4000SCP STATUS (CCCONFIGURATION # 22) 0x8000
Size: 2 Byte, Default Value: 8223
SettingDescription
1 | TEMPERATURE (CC_SENSOR_MULTILEVEL) |
---|---|
2 | SETPOINT H (CC_THERMOSTAT_SETPOINT) |
4 | SETPOINT C (CC_THERMOSTAT_SETPOINT) |
8 | MODE (CC_THERMOSTAT_MODE) |
16 | FANMODE (CC_ THERMOSTAT_FAN_MODE) |
32 | FANSTATE (CC_THERMOSTAT_FAN_STATE) |
64 | OPERATING STATE (CC_THERMOSTAT_OPERATING STATE) |
128 | SCHEDENABLE (CC_CONFIGURATION #38) |
256 | SETBACK (CC_ CONFIGURATION #40) |
512 | RUNHOLD (CC_CONFIGURATION #39) |
1024 | DISPLAYLOCK (CC_CONFIGURATION #24) |
8192 | BATTERY 6 (CC_BATTERY) |
16384 | MECH STATUS (CC_CONFIGURATION # 21) |
32768 | SCP STATUS (CC_CONFIGURATION # 22) |
Parameter 24: Display Lock
Sets locking and unlocking of control of the display screen.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Unlocked |
---|---|
1 | Locked |
Parameter 26: Backlight Timer
Sets the time the thermostat backlight will go out after no button presses
to conserve battery power.
Size: 1 Byte, Default Value: 20
SettingDescription
10 – 30 | Seconds |
---|
Parameter 3: Change Over Type
Sets change over type. Change over with cool or change over with heat.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | CO w/Cool |
---|---|
1 | CO w/Heat |
Parameter 33: Max Heat Setpoint
Sets the maximum heating setpoint value.Will not ramp or accept setpoints
higher than this maximum. 30F – 109F
Size: 1 Byte, Default Value: 90
SettingDescription
30 – 109 | Degrees |
---|
Parameter 34: Min Cool Setpoint
Sets the minimum cooling setpoint value. 33F – 112F
Size: 1 Byte, Default Value: 60
SettingDescription
33 – 112 | Degrees |
---|
Parameter 38: Schedule Enable
Enables or disables the use of schedules.
Size: 1 Byte, Default Value: 0
SettingDescription
1 | Enabled |
---|---|
0 | Disabled |
Parameter 39: Run/Hold Mode
Sets hold and run functionality. Hold locks the current temperature
indefinitely. Run resumes the preprogrammed schedule.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Hold |
---|---|
1 | Run |
Parameter 4: 2nd Stage Heat Enable
Enables or disables the second stage heat operation.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disabled |
---|---|
1 | Enabled |
Parameter 40: Setback Mode
Enables setback or Un-Occupied mode. Temperature setback reduces how often
the heating or cooling system operates by allowing the temperature in a home
to drift to a lower (heating mode) or higher (cooling mode) temperature.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | No Setback |
---|---|
2 | Un-Occupied Mode |
Parameter 41: Un-Occupied HSP
Sets thermostat heating setpoint temperature when un-occupied. 30F – 109F
Size: 1 Byte, Default Value: 62
SettingDescription
30 – 109 | Degrees |
---|
Parameter 42: Un-Occupied HSP
Sets thermostat cooling setpoint temperature when un-occupied. 33F – 112F
Size: 1 Byte, Default Value: 80
SettingDescription
33 – 112 | Degrees |
---|
Parameter 43: Remote Sensor 1 Node Number
Sets remote sensor 1 node number. 0=disabled.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 252 | node number |
---|
Parameter 46: Remote Sensor 1 Temperature
Displays remote sensor 1 Temperature.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | N/A |
---|
Parameter 48: Internal Sensor Temp Offset
Sets Internal Sensor Temp Offset. -7 to 7
Size: 1 Byte, Default Value: 0
SettingDescription
-7 – 7 | Degrees |
---|
Parameter 49: R1 Sensor Temp Off set
Sets R1 Sensor Temp Offset. -7 to 7 degrees
Size: 1 Byte, Default Value: 0
SettingDescription
-7 – 7 | Degrees |
---|
Parameter 5: Aux Heat Enable
Enables or disables aux heat operation.
Size: 1 Byte, Default Value: 1
SettingDescription
0 | Disabled |
---|---|
1 | Enabled |
Parameter 52: Filter Timer (hours)
Sets Filter Timer (hours). 0 to 4000
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 4000 | Hours |
---|
Parameter 53: Filter Timer Max (hrs)
Sets Filter Timer Max (hrs). 0 to 4000.
Size: 2 Byte, Default Value: 300
SettingDescription
0 – 4000 | Hours |
---|
Parameter 54: Heat Timer (hours)
Sets Heat Timer (hours). 0 to 4000.
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 4000 | Hours |
---|
Parameter 55: Cool Timer (hours)
Sets Cool Timer (hours). 0 to 4000.
Size: 2 Byte, Default Value: 0
SettingDescription
0 – 4000 | Hours |
---|
Parameter 6: 2nd Stage Cool Enable
Enables or disables the second stage cool operation.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Disabled |
---|---|
1 | Enabled |
Parameter 61: Fan Purge Heat
Sets Fan Purge Heat. Sets the system blower delay off time after a heat call
ends (fan purge). 0 to 90 Seconds.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 90 | Seconds |
---|
Parameter 62: Fan Purge Cool
Sets Fan Purge Cool. Sets the system blower delay off time after a cool call
ends (fan purge). 0 to 90 Seconds
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 90 | Seconds |
---|
Parameter 7: C/F Type
Enables changing from Centigrade to Fahrenheit or vice versa.
Size: 1 Byte, Default Value: 1
SettingDescription
0 | Centigrade |
---|---|
1 | Fahrenheit |
Parameter 8: MOT
Sets the Minimum Off Time (MOT) delay before another heating/cooling cycle
can begin. Provides compressor short cycle protection. Wait is displayed on
screen when active.
Size: 1 Byte, Default Value: 5
SettingDescription
5 – 9 | Minutes |
---|
Parameter 9: MRT
Sets the Minimum Run Time (MRT) delay before a heating/cooling cycle can
turn off. Sets heating/cooling cycle time. Prevents rapid on/off cycling.
Size: 1 Byte, Default Value: 3
SettingDescription
3 – 9 | Minutes |
---|
Technical Data
Hardware Platform | ZM5202 |
---|---|
Device Type | Thermostat – HVAC |
Network Operation | Listening Sleeping Slave |
Firmware Version | HW: 1 FW: 1.00:02.06 |
Z-Wave Version | 6.51.06 |
Certification ID | ZC10-17055590 |
Z-Wave Product Id | 0x014F.0x5442.0x5436 |
Color | White |
Thermostat Modes | AutoAuxiliary/Emergency HeatCoolFan OnlyHeat |
Thermostat HVAC Systems Supported | Cool OnlyHeat OnlyHeat PumpMulti Stage |
Thermostat Power Source | BatteryPower Stealing (hard-wired 24V) |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Supported Command Classes
- Association Grp Info
- Association V2
- Basic
- Battery
- Clock
- Configuration
- Device Reset Locally
- Firmware Update Md V2
- Manufacturer Specific
- Multi Cmd
- Powerlevel
- Scene Activation
- Scene Actuator Conf
- Sensor Multilevel
- Thermostat Fan Mode
- Thermostat Fan State
- Thermostat Mode
- Thermostat Operating State
- Thermostat Setpoint V2
- Version V2
- Zwaveplus Info V2
Controlled Command Classes
- Basic
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>