SPLIT SYSTEM AIR CONDITIONER
INSTALLATION INSTRUCTIONS
SA3BE4M Split System Air Conditioner
*SA3BE4M – 1SN18K, 1SN24K, 1SN30K, 1SN36K, 1SN42K, 1SN48K, & 2SN60K (1.5, 2, 2.5, 3, 3.5, 4, & 5 TON) SERIES – SINGLE PHASE MODELS
IMPORTANT
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This
includes being able to install the product according to strict safety
guidelines and instructing thecustomer on how to operate and maintain the
equipment for the life of the product. Safety should always be the deciding
factor when installing this product and using ommon sense plays an important
role as well. Pay attention to all safety warnings and any other special notes
highlighted in the manual. Improper installation of the unit or ailure to
follow safety warnings could result in serious injury, death, or property
damage. These instructions are primarily intended to assist qualified
individuals experienced in he proper installation of this appliance. Some
local codes require licensed installation/service personnel for this type of
equipment. Please read all instructions carefully efore starting the
installation. Return these instructions to the customer’s package forfuture
reference.
DO NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE
REFERENCE.
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing this equipment.
Pay attention to all safety warnings and any other special notes highlighted
in the manual. Safety markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not be ignored.
WARNING indicates a potentially hazardous situation that if not avoided,
could result in personal injury or death.
CAUTION indicates a potentially hazardous situation that if not avoided,
may result in minor or moderate injury or property damage.
WARNING: Shut off all electrical power to the unit before performing any
maintenance or service on the system. Failure to comply may result in personal
injury or death.
WARNING: Unless noted otherwise in these instructions, only factory
authorized parts or accessory kits may be used with this product. Improper
installation, service, adjustment, or maintenance may cause explosion, fire,
electrical shock or other hazardous conditions which may result in personal
injury or property damage
WARNING: *SA3BE4M split system air conditioners are shipped charged with
R410A refrigerant and ready for installation. If repairs make it necessary for
evacuation and charging, it should only be attempted by qualified trained
personnel thoroughly familiar with this equipment. Under no circumstances
should the owner attempt to install and/or service this equipment. Failure to
comply with this warning could result in property damage, personal injury, or
death.
WARNING: The information listed in this manual must be followed during
the installation, service, and operation of this unit. Unqualified individuals
should not attempt to interpret these instructions or install this equipment.
Failure to follow safety recommendations could result in possible damage to
the equipment, serious personal injury or death.
CAUTION: This unit uses refrigerant R-410A. DO NOT use any other refrigerant in this unit. Use of another refrigerant will damage the unit.
- The installer must comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
- All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1.
- This equipment contains liquid and gaseous refrigerant under high pressure. DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.Installation or servicing should only be performed by qualified trained personnel thoroughly familiar with this type equipment.
- Fully annealed, refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
- Installation of equipment may require brazing operations. Installer must comply with safety codes and wear appropriate safety equipment (safety glasses, work gloves, fire extinguisher, etc.) when performing brazing operations.
- Follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
- Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water from leaking into the structure.
- This unit is designed for outdoor installations only and should be positioned as shown on page 3.
AIR CONDITIONER INSTALLATION
General Information
The *SA3BE4M series air conditioner is designed only for outdoor rooftop or
ground level installations. This unit has been tested for capacity and
efficiency in accordance
with AHRI Standards and will provide many years of safe and dependable
comfort, providing it is properly installed and maintained. Abuse, improper
use, and/or improper maintenance can shorten the life of the appliance and
create unsafe hazards.
To achieve optimum performance and minimize equipment failure, it is
recommended that periodic maintenance be performed on this unit. The ability
to properly perform
maintenance on this equipment requires certain mechanical skills and tools.
Before You Install this Unit
√ The cooling load of the area to be conditioned must be calculated and a
system of the proper capacity selected.
It is recommended that the area to be conditioned be completely insulated and
vapor sealed.
√ Check the electrical supply and verify the power supply is adequate for unit
operation. The system must be wired and provided with circuit protection in
accordance with
local building codes. If there is any question concerning the power supply,
contact the local power company.
√ The indoor section (air handler, furnace, etc) should be installed before
routing the refrigerant tubing. Refer to the indoor unit’s installation
instructions for installation details.
√ All units are securely packed at the time of shipment and upon arrival
should be carefully inspected for damage prior to installing the equipment at
the job site. Verify coil fins are straight. If necessary, comb fins to remove
flattened or bent fins. Claims for damage (apparent or concealed) should be
filed immediately with the carrier.
√ Please consult your dealer for maintenance information and availability of
maintenance contracts. Please read all instructions before installing the
unit.
Locating the Air Conditioner
- Survey the job site to determine the best location for mounting the outdoor unit.
- Sufficient clearance for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance. See Figure 1 for minimum clearances to obstructions.
- Overhead obstructions (Figure 1), poorly ventilated areas, and areas subject to accumulation of debris should be avoided.
- Consideration should be given to availability of electric power, service access, noise, and shade.
NOTE: Units require full perimeter clearances.
Installer must maintain 18” between two units or 12” between single unit and
structure.
Figure 1. Clearance Requirements
Packaging Removal
NOTE : To prevent damage to the tubing connections, carefully remove the
carton and user’s manual from the equipment.
Discard the shipping carton. Ground Level Ground level installations must be
located according to local building codes or ordinances and these
requirements:
- Clearances must be in accordance with those shown in Figure 1.
- A suitable mounting pad (Figure 1) must be provided and separate from the building foundation. The pad must be level and strong enough to support the weight of the unit.The slab height must be a minimum of 2” (5 cm) above grade and with adequate drainage.
Roof Mount
- The method of mounting should be designed so that it does not overload roof structures or transmit noise to the interior of the structure. The roof must be structurally capable of handling the weight of the unit.
- Full perimeter support is required under the unit. Support must be made of weather resistant materials and installed prior to unit installation.
- The support must be built to raise the unit 6″ above the roof.
Connecting Refrigerant Tubing Between the Indoor & Outdoor Unit
CAUTION:
When servicing, cover or seal openings to minimize the exposure of the
refrigerant system to air to prevent accumulation of moisture and other
contaminants.
After outdoor and indoor unit placement has been determined, route refrigerant
tubing between the equipment in accordance with sound installation practices.
- When connecting refrigerant linesets together, it is recommended that dry nitrogen be flowing through the joints during brazing to prevent internal oxidation and scaling.
- Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. If precise forming of refrigerant lines is required, a copper tubing bender is recommended. Avoid sharp bends and contact of the refrigerant lines with metal surfaces.
- Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation.
- Tubing should be kept clean of foreign debris during installation.
- Every effort should be made by the installer to ensure that the field installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity.
- The maximum recommended interconnecting refrigerant line lengths is 75 ft. and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 ft.
- A filter dryer is provided with the unit and must be installed in the liquid line of the system. If the installation replaces a system with a filter dryer already present in the liquid line, the filter dryer must be replaced with the one supplied with the unit. The filter dryer must be installed in strict accordancewith the manufacturer’s installation instructions.
- Optional equipment such as liquid line solenoid valves, low ambient, etc., should be installed in strict accordance with the manufacturer’s installation instructions.
ELECTRICAL WIRING
WARNING:
ELECTRICAL SHOCK OR FIRE HAZARD
To avoid risk of electrical shock, personal injury, or death, disconnect all
electrical power to the unit before performing any maintenance or service. The
unit may have more than one electrical supply. Label all wires prior to
disconnection when servicing the unit. Wiring errors can cause improper and
dangerous operation.
-
All electrical connections must be in compliance with all applicable local codes and ordinances, and with the current revision of the National Electric Code ANSI/NFPA 70).
-
For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist
√ Verify that the voltage, frequency, and phase of the supply source match the specifications on the unit rating plate.
√ Verify that the service provided by the utility is sufficient to handle the additional load imposed by this equipment.
Refer to the unit wiring label for proper voltage wiring.
√ Verify factory wiring is in accordance with the unit wiring diagram. See Figure 4, (page 8). Inspect for loose connections.
Line Voltage -
A wiring diagram is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram before making
any electrical connections to the outdoor unit. -
An electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the outdoor unit.
-
Line voltage to the unit should be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit. Incoming field wiring and minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label. Any other wiring methods must be acceptable to authority having jurisdiction.
-
The outdoor unit requires both power and control circuit electrical connections. Refer to the wiring diagram / schematic for identification and location of outdoor unit
field wiring interfaces. See Figure 4, (page 8). Make all electrical connections in accordance with all applicable codes and ordinances. -
Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes. See the unit rating plate for minimum circuit ampacity and maximum overcurrent protection limits.
-
Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate. Connect the line-voltage leads to the terminals on the contactor inside the control compartment.
-
Use only copper wire for the line voltage power supply to this unit in strict accordance of the NEC (ANSI/NFPA 70), applicable local codes, and the instructions provided with the equipment. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended.
-
208/230 Volt units are shipped from the factory wired for 230 volt operation. For 208V operation, remove the lead from the transformer terminal marked 240V and onnect it to the terminal marked 208V.
-
Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC (ANSI/NFPA 70), applicable local codes, and the instructions provided with the equipment.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or unbroken electrical ground to
minimize personal injury if an electrical fault should occur. Do not use gas
piping as an electrical ground!
This unit must be electrically grounded in accordance with local codes or, in
the absence of local codes, with the National Electrical Code (ANSI/NFPA 70)
or the CSA C22.1 Electrical Code. Use the grounding lug provided in the
control box for grounding the unit.
Thermostat Connections
- Thermostat connections should be made in accordance with the instructions supplied with the thermostat and the indoor equipment.
- The outdoor unit is designed to operate from a 24 VAC Class II control circuit. The control circuit wiring must comply with the current provisions of the NEC (ANSI/NFPA 70) and with applicable local codes having jurisdiction.
- The low voltage wires must be properly connected to the units low voltage terminal block.
- The thermostat should be mounted about 5 feet above the floor on an inside wall. DO NOT install the thermostat on an outside wall or any other location where its operation may be adversely affected by radiant heat from fireplaces, sunlight, or lighting fixtures, and convective heat from warm air registers or electrical appliances. Refer to the thermostat manufacturer’s instruction sheet for detailed mounting and installation information.
START UP & ADJUSTMENTS
Pre-Start Check List
√ Verify the indoor unit is level and allows proper condensate drainage.
√ Verify the outdoor coil and top of the unit are free from obstructions and
debris, and all equipment access/control panels are in place.
√ Verify air filters are cleaned and properly installed.
√ Verify duct work is sealed to prevent air leakage.
√ Verify line voltage power leads are securely connected and the unit is
properly grounded.
√ Verify low voltage wires are securely connected to the correct leads on the
low voltage terminal strip.
√ Verify power supply branch circuit overcurrent protection is sized properly.
√ Verify the thermostat is wired correctly.
Start-Up Procedures
The thermostat’s function mode should be set to OFF and the fan mode should be
set to AUTO. Close all electrical disconnects to energize the system.
Air Circulation – Indoor Blower
- Set the thermostat system mode on OFF and the fan mode to ON.
- Verify the blower runs continuously. Check the air delivery at the supply registers and adjust register openings for balanced air distribution. If insufficient air is detected, examine ductwork for leaks or obstructions.
- Set the thermostat fan mode to AUTO and verify the blower stops running.
System Cooling
- Set the thermostat’s system mode to COOL and the fan mode to AUTO. Gradually lower the thermostat temperature setpoint below room temperature and verify the outdoor unit and indoor blower energize.
- Verify blower wheel is spinning in direction indicated by arrow. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
- Verify HI and LO refrigerant pressures.
- Allow the system to operate for several minutes and then set the temperature selector above room temperature. Verify the fan and compressor cycle off with the hermostat.
NOTE: The blower should also stop unless fan mode is set to the ON
position.
System Heating (optional)
- Set the thermostat’s system mode to HEAT and the temperature mode above room temperature.
- Verify the optional heating equipment (furnace or electric heat) and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is warmer
than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
AIR CONDITIONER MAINTENANCE
WARNING:
To prevent electrical shock, personal injury, or death, disconnect all
electrical power to the unit before performing any maintenance or service.
The unit may have more than one electrical supply.
Proper maintenance is important to achieve optimum performance from the air
conditioner. The ability to properly perform maintenance on this equipment
requires certain
mechanical skills and tools. If you do not possess these skills, contact your
dealer for maintenance. Consult your local dealer about the availability of
maintenance contracts.
Routine maintenance should include the following:
- Inspect and clean or replace air filters at the beginning of each heating and cooling season, or more frequently if required.
- Inspect the condensate drain and outdoor coil at the beginning of each cooling season. Remove any debris. Clean the outdoor coil and louvers as necessary using a mild detergent and water. Rinse thoroughly with water.
- Inspect the electrical connections for tightness at the beginning of each heating and cooling season. Service as necessary.
**CAUTION:**
The unit should never be operated without a filter in the return air system.
Replace disposable filters with the same type and size.
- Do not attempt to add additional oil to motors unequipped with oil tubes. The compressor is hermetically sealed at the factory and does not require lubrication.
- To access the internal compnents of the unit, refer to Figure 2, (page 6) for panel removal and Figure 3,(page 6) for panel installation.
Panel Removal
- Remove screws securing the panel.
- Slide the panel up towards the top pan in order to clear the bottom flange from the base pan. See Figure 2.
- Swing the bottom of the panel out and pull the panel down to remove it from the unit.
Panel Installation
- Insert the top corners of side panel flanges into the corner post channels as shown in Detail A in Figure 3.
- Slide the panel up into the top pan. (You may need to push on the center of the panel at the top in order to clear the top pan edge).
- Swing the panel in and push down until the panel is resting on the top edge of the base pan wall as shown in Detail B.
- Insert screws into the panel to secure it to the unit.
REFRIGERANT CHARGING
**WARNING:*
SA3BE4M Split System Air Conditioners are shipped charged with R410A refrigerant and ready for installation. If repairs make it necessary for evacuation and charging, it should only be attempted by qualified trained personnel thoroughly familiar with this equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.
After refrigerant line connections are completed, it is required that you leak
check and evacuate the indoor section and all line connections (using proper
methods) before finalizing the full system refrigerant charge.
- Refer to the Quick Reference Data sheet for additional charging information. Outdoor units with non-AHRI listed indoor coils are not recommended and deviations from ated airflows or non-listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation.
- *SA3BE4M outdoor units with non-AHRI listed indoor coils are not recommended. Deviations from rated airflows or non-listed combinations may require modification to the expansion device and refrigerant charging procedures for proper and efficient system operation.
- The refrigerant charge can be checked and adjusted through the service ports provided external to the outdoor unit. Use only gage line sets which have a “Schrader” depression device present to actuate the valve.
- A high-pressure switch is factory-installed and located in the liquid line internal to the outdoor unit. The switch is designed to protect the system when very high pressures occur during abnormal conditions. Under normal conditions, the switch is closed. If the liquid pressure rises above 575 psig, then the switch will open and de-energize the outdoor unit. The switch will close again once the liquid pressure decreases to 460 psig. Please note that the switch interrupts the thermostat inputs to the unit. Thus, when the switch opens and then closes, there may be a 5 minute short cycling delay before the outdoor unit will energize.
- A low-pressure switch (select models only) is factoryinstalled and located in the suction line internal to the outdoor unit. The switch is designed to protect the compressor from a loss of charge. Under normal conditions, the switch is closed. If the suction pressure falls below 20 psig, then the switch will open and de-energize the outdoor unit. he switch will close again once the suction pressure increases above 35 psig. Please note that the switch interrupts the thermostat inputs to the unit. When the switch opens nd then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize.
Charging the Unit in AC mode
If the outdoor temperature is 65 degrees F or higher:
After completing the refrigerant line connections, leak checking the system,
and evacuating the indoor section and all line connections (using proper
methods), perform the following steps:
- Determine the recommended charge addition (if applicable) for the system being installed. This information is in the unit’s QRD (Quick Reference Data sheet).
- Calculate the amount of additional refrigerant needed for the line set length of the actual installation. This information is on the first page of the unit’s QRD (Quick Reference Data sheet).
- Weigh in the additional charge amounts determined by step 1 and 2 above.
- Adjust the charge to match the superheat (for fixed orifice systems) or subcooling (for TXV systems). There are three different resources for doing this:
a.) The chargecalculator.com website. This will walk you through the charging process step by step.
b.) The charging tables on the inside of the outdoor unit’s electrical box cover panel. These tables provide superheat targets for fixed orifice systems and subcooling targets for TXV systems. The system should be charged so that the measured superheat/ subcooling are within 1 degree F of the target listed in the table.
For fixed orifice systems:
- If your measured superheat at the suction valve is LESS THAN the recommended superheat value in the table then REMOVE refrigerant.
- If your measured superheat at the suction valve is GREATER THAN the recommended superheat value in the table then ADD refrigerant. For TXV systems:
- If your measured subcooling at the liquid valve is LESS THAN the recommended subcooling value in the table then ADD refrigerant.
- If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the table then REMOVE refrigerant.
c.) The charging tables in the Supplemental Charging Information, can be found
online in the literature library. The tables can also be accessed by scanning
the QR code on the unit’s electrical panel. The pressures listed in these
tables are for reference only and are to be used in troubleshooting a system.
The system should be charged to match the superheat or subcooling targets as
previously noted and not to match the system pressures.
Follow the same procedure described in 4b above.
If the outdoor temperature is below 65 degrees F:
After completing the refrigerant line connections, leakchecking the system,
and evacuating the indoor section and all line connections (using proper
methods), perform
the following steps:
- Determine the recommended charge addition (if applicable)for the system being installed. This information is in the unit’s QRD (Quick Reference Data sheet).
- Calculate the amount of additional refrigerant needed for the line set length of the actual installation. This information is on the first page of the unit’s QRD (Quick Reference Data sheet).
- Weigh in the additional charge amounts determined by step 1 and 2 above.
- Return to the system when the outdoor temperature is 65 degrees F or higher and follow the steps defined in step 4 of the “If the outdoor temperature is 65 degrees F or higher” section above.
WIRING DIAGRAM
Split System Air Conditioner (Outdoor Section)
NOTES:
- Disconnect all power before servicing.
- For supply connections use copper conductors only.
- Not suitable on systems that exceed 150 volts to ground.
- For replacement wires use conductors suitable for 105 deg C.
- For ampacities and overcurrent protection, see unit rating plate.
- Connect to 24 VAC/40VA/class 2 circuit. See furnace/airhandler installation instructions for control circuit and optional relay/transformer kits.
- Caution: The Low Voltage wiring shall not be grounded to this unit.
Single Phase
- Couper le courant avant de faire letretien.
- Employez uniquement des conducteurs en cuivre.
- Ne convient pas aux installations de plus de 150 volt a la terre.
*Figure 4. Wiring Diagram for SA3BE4M (1.5 – 4 Ton Units)**
INSTALLATION CHECKLIST
INSTALLATION ADDRESS:
CITY:| STATE:
UNIT MODEL ft
UNIT SERIAL ft
INSTALLER NAME:
CITY| STATE
Unit Installed Minimum clearances shown on page 3?| YES| NO
Has the owner’s information been reviewed with the customer?| YES| NO
Has the Literature Package been left with the unit?| YES| NO
REFRIGERATION SYSTEM
Was unit given 24 hr warm up period for crankcase heaters?| YES| NO
Stage-1 Liquid Pressure (high side):
Stage-1 Suction Pressure (low side):
ELECTRICAL SYSTEM
Electrical connections tight?| YES| NO
Line voltage polarity correct?| YES| NO
Rated Voltage:
Max. deviation of voltage from avg. volts:
Has the thermostat been calibrated?| YES| NO
Is the thermostat level?| YES| NO
Is the heat anticipator setting correct? (If Applicable)| YES| NO
REPLACEMENT PARTS
Replacement parts are available through your distributor.
Please have the complete model and serial number of the unit when ordering
replacement parts.
ELECTRICAL:
- Capacitors
- Compressors
- Contactors
- Pressure Switches
- Relays
- Temperature Limit Switches
- Thermostats
- Time Delay Relays
- Transformers
MOTORS:
- Blower Motor
- Fan Motor
COMPONENTS:
- Blower Assembly
- Cabinet Panels
- Expansion Valves
- Fan Grille
- Filter/Driers
Specifications & illustrations subject to change without notice or incurring obligations (09/21). O’Fallon, MO, © Nortek Global HVAC LLC 2021. All Rights Reserved.
10401680
(NEW)
www.ahridirectory.org
Documents / Resources
|
Nortek SA3BE4M Split System Air
Conditioner
[pdf] Instruction Manual
SA3BE4M, 1SN18K, 1SN24K, 1SN30K, 1SN36K, 1SN42K, 1SN48K, 2SN60K, SA3BE4M Split
System Air Conditioner, Split System Air Conditioner, Air Conditioner
---|---
|
Nortek SA3BE4M Split System Air
Conditioner
[pdf] Instruction Manual
SA3BE4M Split System Air Conditioner, SA3BE4M, Split System Air Conditioner,
Air Conditioner
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>