Qubino Flush 1D relay GOAEZMNHND1 Manual

June 8, 2024
QUBINO

Qubino

Flush 1D relay

SKU: GOAEZMNHND1

Quickstart

This is a ****

On/Off Power Switch
for
Europe
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
Press service button S for more than 2 second or
Press push button I1 three times within 3s (3 times change switch state within 3 seconds).

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

Qubino Flush 1D relay with voltage free (dry contact) output contact.
This Z-Wave module is used for switching on or off the electrical device (e.g. light, fan, etc …). The module can be controlled either through Z-wave network or through the wall switch.
The module is designed to be mounted inside a “flush mounting box”, hidden behind a traditional wall switch.
Module supports connection of digital temperature sensor. It is designed to act as repeater in order to improve range and stability of Z-wave network.

Output contact is voltage free (dry contact), so also loads with different power supply can be connected to the module.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

If the service button S is pressed for more than 6 seconds the module will be reset to the factory defoult state.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Installation

“· To prevent electrical shock and/or equipment” damage, disconnect electrical power at the” main fuse or circuit breaker before installation” or any servicing.

“· Make sure, that no voltage is present in the” installation.

“· Prevent the disconnecting device from being” switched on accidentally.

“· Connect the module according to electrical” diagram.

“· Locate the antenna far from metal elements” (as far as possible).

“· Do not shorten the antenna.

Electrical diagram 230VAC

Option for different load power supply – DPLS:

Electrical diagram 24VDC

Option for different load power supply – DPLS:

NOTE!

Output contact is voltage free (dry contact), so also” loads with different power supply can be” connected to the module.

Service button (used to add or remove module” from the Z-Wave” network in case of 24 V” SELV power supply).

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Press service button S for more than 2 second or
Press push button I1 three times within 3s (3 times change switch state within 3 seconds).

Exclusion

Press service button S for more than 6 second or
Press push button I1 five times within 3s (5 times change switch state within 3 seconds) in the first 60 seconds after the module is connected to the power supply.

Auto-Inclusion

Beside the standard inclusion this devices supports the so called auto inclusion.
Right after powering up the device remains in inclusion state and can be included by
(any) gateway without further actions on the device itself. The auto inclusion mode will
time out after some time.

Product Usage

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 1| Lifeline group (reserved for communication with the main controller), 1 node allowed.
---|---|---
2| 16| basic on/off (triggered at change of the output state and reflecting its state) up to 16 nodes.
3| 16| basic on/off (triggered at change of the input I2 state and reflecting its state) up to 16 nodes.
4| 16| Binary Sensor Report (triggered at change of the input I2 state and reflecting its state) up to 16 nodes.
5| 16| Notification Report (triggered at change of the input I2 state and reflecting its state) up to 16 nodes.
6| 16|

multilevel sensor report (triggered at” change of temperature sensor)

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Input 1 switch type

Defines the type of switch connected to Input 1
Size: 1 Byte, Default Value: 1

SettingDescription

0 mono-stable switch type (push button)
1 bi-stable switch type

Parameter 2: Input 2 contact type

Defines the type of switch connected to Input 2
Size: 1 Byte, Default Value: 0

SettingDescription

0 NO (normally open) input type
1 NC (normally close) input type

Parameter 10: Activate / deactivate functions ALL ON/ALL OFF

Support to activate / deactivate functions ALL ON/ALL OFFFlush 1D relay module responds to commands ALL ON / ALL OFF that may be sent by the main controller or by other controller belonging to the system.
Size: 2 Byte, Default Value: 255

SettingDescription

0 ALL ON is not active ALL OFF is not active
1 ALL ON is not active ALL OFF active
2 ALL ON active ALL OFF is not active
255 ALL ON active, ALL OFF active

Parameter 11: Automatic turning off output after set time

Support automatic turning off output after set time.When relay is ON it goes automatically OFF after time defined by this parameter. Timer is reset to zero each time the module receive ON command regardless from where it comes (push button, associated module, controller,..).
Size: 2 Byte, Default Value: 0

SettingDescription

0 Auto OFF disabled
1 – 32535 1 – 32535 = 1second (0,01s) – 32535 seconds (325,35s) Auto OFF

enabled with define time, step is 1s or 10ms according to parameter nr.15

Parameter 12: Automatic turning on output after set time

Support automatic turning on output after set time When relay is OFF it goes automatically ON after time defined by this parameter. Timer is reset to zero each time the module receive OFF command regardless from where it comes (push button, associated module, controller,..).
Size: 2 Byte, Default Value: 0

SettingDescription

0 Auto ON disabled
1 – 32535 1 – 32535 = 1second (0,01s) – 32536 seconds (325,35s) Auto ON

enabled with define time, step is 1s or 10ms according to parameter nr.15

Parameter 15: Automatic turning off / on seconds or milliseconds

selection

Support automatic turning off / on seconds or milliseconds selectionNOTE: This parameter is valid for both, turning on and turning off parameters.
Size: 1 Byte, Default Value: 0

SettingDescription

0 seconds selected
1 milliseconds selected

Parameter 30: Saving the state of the relay after a power failure

Support saving the state of the relay after a power failure
Size: 1 Byte, Default Value: 0

SettingDescription

0| Flush 1D relay module saves its state before power failure (it returns to the last position saved before a power failure)
---|---
1| Flush 1D relay module does not save the state after a power failure, it returns to "off" position.

Parameter 63: Output Switch selection

Support output Switch selectionSet value means the type of the device that is connected to the output. The device type can be normally open (NO) or normally close (NC).
Size: 1 Byte, Default Value: 0

SettingDescription

0 When system is turned off the output is 0V (NC).
1 When system is turned off the output is 230V or 24V (NO).

Parameter 100: Enable / Disable Endpoint I2 or select Notification Type

and Event

Support Enable / Disable Endpoint I2 or select Notification Type and EventEnabling I2, means that Endpoint (I2) will be present on UI. Disabling it will result in hiding the endpoint according to the parameter set value. Additionally, a Notification Type and Event can be selected for the endpoint. NOTE: After parameter change module has to be reincluded into the network for the setting to take effect!
Size: 1 Byte, Default Value: 1

SettingDescription

0 Endpoint, I2 disabled
1 Home Security; Motion Detection, unknown location
2 Carbon Monoxide; Carbon Monoxide detected, unknown location.
3 Carbon Dioxide; Carbon Dioxide detected, unknown location.
4 Water Alarm; Water Leak detected, unknown location.
5 Heat Alarm; Overheat detected, unknown location.
6 Smoke Alarm; Smoke detected, unknown location.

Parameter 110: Temperature sensor offset settings

Defines temperature sensor offset settingsSet value is added or subtracted to actual measured value by sensor.
Size: 2 Byte, Default Value: 32536

SettingDescription

1 – 100 value from 0.1C to 10.0C is added to actual measured temperature.
1001 – 1100 value from -0.1C to -10.0C is subtracted to actual measured

temperature.
32536| offset is 0.0C

Parameter 120: Digital temperature sensor reporting

Defines the digital temperature sensor reportingIf digital temperature sensor is connected, module reports measured temperature on temperature change defined by this parameter.
Size: 1 Byte, Default Value: 5

SettingDescription

0 Reporting disabled
1 – 127 0,1C – 12,7C, step is 0,1C

Technical Data

Dimensions 41x36x15 mm
Weight 27 gr
Hardware Platform ZM5202
EAN 3830062070072
IP Class IP 20
Voltage 230 V
Load 2300 W
Device Type On/Off Power Switch
Network Operation Always On Slave
Z-Wave Version 6.51.06
Certification ID ZC10-15070017
Z-Wave Product Id 0x0159.0x0002.0x0053
Frequency Europe – 868,4 Mhz
Maximum transmission power 5 mW

Supported Command Classes

  • Switch All
  • Association
  • Association Group Information
  • Basic
  • Sensor Binary
  • Configuration
  • Device Reset Locally
  • Manufacturer Specific
  • Multi Channel
  • Multi Channel Association
  • Sensor Multilevel
  • Notification
  • Powerlevel
  • Switch Binary
  • Version
  • Zwaveplus Info

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals