LED FSIR-100 Remote Programmer Tool User Manual
- June 8, 2024
- LED
Table of Contents
LED FSIR-100 Remote Programmer Tool
USING THE FSIR -100 CONFIGURATION TOOL
The FSIR-100 Wireless IR Configuration Tool is a handheld tool for changing
defaults and testing of WattStopper devices.It provides wireless access to the
devices for parameter changes and testing.
The FSIR-100 display shows menus and prompts to lead you through each process.
The navigation pad provides a simple way to navigate through the customization
fields.
Within a certain mounting height of the sensor, the FSIR100 allows
modification of the system without requiring ladders or tools; simply with a
touch of a few buttons.
The FSIR-100 IR transceiver allows bi-directional communication between the
device and the FSIR-100 configuration tool . Simple menu screens let you see
the current status of the sensor and make changes. It can change device
parameters such as high/low mode, sensitivity, time delay, cut off and more.
With the FSIR-100 you can also establish and store device parameter profiles.
BATTERIES
The FSIR-100 operates on three standard 1.5V AAA Alkaline batteries or three rechargeable AAA NiMH batteries. The battery status displays in the upper right corner of the display. Three bars next to BAT= indicates a full battery charge. A warning appears on the display when the battery level falls below a minimum acceptable level. To conserve battery power, the FSIR-100 automatically shuts off 10 minutes after the last key press.
- If communication is not successful, (if possible) move closer to the sensor.
- If still not successful, there may be too much IR interference from other sources. Programming the unit at night when there is no daylight available may be the only way to communicate with the sensor.
NAVIGATION
Navigate from one field to another using (up) or (down) arrow keys. The active field is indicated by flashing (alternates) between yellow text on black background and black text on yellow background.
Once active, use the Select button to move to a menu or function within the
active field. Value fields are used to adjust parameter settings. They are
shown in “less-than/ greater-than” symbols:
IR COMMUNICATION
IR communication can be a ected by the mounting height of the sensor and high ambient lighting such as direct daylight or electric light such as floodlights, and some halogen, fluorescent lamps, LED’s. When trying to communicate with the device, be sure to be positioned under the sensor without any obstructions. Every time the commissionng tool establishes communication with the device, the controlled load will cycle.
- Distance may vary depending on the lighting environment
FSP-211
The FSP-211 is a motion sensor that dims lighting from high to low based on
movement. This slim, low-profile sensor is designed for installation inside
the bottom of a light fixture body. The PIR lens module connects to the
FSP-211 through a 1.30″ diameter hole in the bottom of the fixture.
The sensors use passive infrared (PIR) sensing technology that reacts to
changes in infrared energy (moving body heat) within the coverage area. Once
the sensor stops detecting movement and the time delay elapses lights will go
from high to low mode and eventually to an OFF position if it is desired.
Sensors must directly “see” motion of a person or moving object to detect
them, so careful consideration must be given to sensor luminaire placement and
lens selection. Avoid placing the sensor where obstructions may block the
sensor’s line of sight.
COMPONENTS
FSP-211 SCREEN
Home Menu
The Home (or Main) menu displays after the powerup process completes. It contains information on the battery status and sensor menu choices. Press the up or down buttons to highlight the desired sensor then press Select.
New Settings
New Settings allow you to select the different sensor parameters such as: High/ Low Mode, Time Delay, Cut Off, Sensitivity, Setpoint and Ramp/Fade rates.
High Mode
When the sensor detects motion the dimming control output ramps up to the
selected HIGH light level (default is 10V).
Range: 0 V to 10 V Increments: 0.2 V
To program the FSP-211 with the selected parameters go to SEND and press the Select button. The controlled load should cycle once the sensor is updated.
Low Mode
After the sensor stops detecting motion and the time delay expires the dimming
control output fades down to the selected LOW light level (default is 1V).
Range: OFF, 0 V to 9.8 V Increments: 0.2 V
Time Delay
The time period that must elapse after the last time the sensor detects motion
for the lights to fade to LOW mode (default is 5 min).
Range: 3 0 sec, 1 min to 30 min Increments: 1 min
Cut Off
The time period that must elapse after the lights fade to Low Mode and the
sensor detects no motion for the lights to turn OFF (default is 1 hour).
Range: Disable (No cut off, lights will stay in low mode) 1 min to 59
min, 1 hr to 5 hr (press and hold should cause to move faster through the
increments)
Increments: 1 min or 1 hr
Sensitivity
The response of the PIR detector to motion within the sensor’s coverage area
(default is max).
Range and Sequence: On-Fix, Off-Fix, Low, Med, Max
(On-Fix: relay closed, occupancy detection disabled; Off-Fix, relay open,
occupancy detection disabled.
Hold Off Setpoint
The selectable ambient light level threshold that will hold the lights off or
at LOW level when the sensor detects motion (default is Disable).
Range: Auto, Disable, 1 fc to 250 fc
Increments: 1 fc (press and hold should cause to move faster thru the
increments) Sequence: Disable, 1 fc to 250 fc
The Auto option invokes an automatic calibration procedure to establish an appropriate setpoint based upon the contribution of the electric light. As part of this procedure, the controlled load is turned on to warm up the lamp, and then it is switched off and on eight times, terminating in an off state. After this process, a new setpoint value is automatically calculated. During this time, communication to the FSP-211 is disabled.
Next
To view more settings go to NEXT and press the Select button.
Time period for light level to increase from LOW to HIGH (default is Disable;
light/load switches instantly).
Range: Disable, 1 sec to 60 sec Increments: 1 sec
Ramp Up
Time period for light level to decrease from HIGH to LOW (default is Disable;
light/load switches instantly).
Range: Disable, 1 sec to 60 sec Increments: 1 sec
Fade Down
Time period for light level to decrease from HIGH to LOW (default is Disable;
light/load switches instantly).
Range: Disable, 1 sec to 60 sec Increments: 1 sec
Photocell On/Off
When the light level exceeds this setting, the lights will turn off even when the space is occupied. Once the light level exceeds this setting, the sensor will wait and monitor for a short period of time in order to confirm the light level increase is not temporary before forcing the lights to go off. When light level goes below the settings, the light will turn on even without motion detection. This feature is disabled by default. If using this setting in combination with the Hold Off setpoint, there must be at least 10fc of dead band between the two settings. The Photocell setpoint is automatically set to maintain at least10fc of dead band above the Hold Off setpoint to help avoid load cycling.
Prior
To go back to previous settings go to PRIOR and press the Select button.
Send
To program the FSP-211 with the selected parameters go to SEND and press the Select button. The controlled load should cycle once the sensor is updated.
Save
To Save these New Settings parameters as one of the profiles go to SAVE and press the Select button
Current Settings
Current Settings
Current Settings allow you to recall the parameters for a specific sensor. These are read only parameters.
View Current Settings
Highlight and press Select to view the Current Settings.
To go back to previous settings go to PRIOR and press the Select button.
Light Level
Displays the light level at the FSP-211. The light level reading can be used as a reference for setpoint adjustments.
Done
To go to the FSP-211 Home screen go to DONE and press the Select button
Test Mode
Enable/Disable
Test Mode shortens timeouts for High/Low and Cut Off, to allow quick verification of settings. Test Mode disables automatically after 5 minute
Recall Profiles
Recall Profiles allow the user to select the saved parameter profiles. This feature is used when programming multipleFSP-211’s with the same parameters.
Selecting a specific profile allow the user to also change the parameters such as: High/Low Mode, Time Delay, Cut Off, Sensitivity, Setpoint and Ramp/Fade rates.
Lock Settings
IR communication locks to prevent unauthorized changes of FSP-211 parameters.
To view more sensor configuration settings go to NEXT and press the Select button.
FSP-211 default settings communicate with the FSIR-100; however, this security feature limits communication only for authorized installers who have access to main power supply to the FSP-211 sensor. Press Select to set Lock Delay or press PRIOR to go back.
Factory default Lock Delay setting is disabled and FSP-211 parameter can
change with any FSIR-100 at anytime. To enable Lock Delay with time, select
lock delay time and press SEND to set delay time in the FSP-211. Its parameter
changes with the FSIR-100 will be locked after the specified timerexpires from
the last message. At the end of the specified time the FSP-211 will be locked
unless there is a power cycle. Any locked sensor needs power cycling to
initiate any configuration through the FSIR-100. To permanently disable Lock
Delay after power cycling, select Disable and press SEND.
Range: 10 min – 240 min
Increments: 1 min
Highlight SEND and press Select to enable lock settings.
This screen will appear if the FSP-211 is locked. If it is locked, cycle the power.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>