BROAN LP510RF Selectable CFM Bathroom Exhaust Fan Finish Pack Installation Guide

June 8, 2024
Broan

BROAN LP510RF Selectable CFM Bathroom Exhaust Fan Finish Pack

WARNING

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

a). Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
b). Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switching on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
c). Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
d). Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdating. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASH RAE), and the local code authorities.
e). When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
f ). Ducted fans must always be vented to the outdoors.
g). Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) – protected branch circuit (ceiling installation only).
h). This unit must be grounded.
i). Not for Use in Kitchens.
j). To reduce risk of fire and to properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces within walls or ceilings or into attics, crawl spaces, or garages.
k). WARNING: To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Fan With Any Solid-State Speed Control Device.
I). The fan must not be installed in a ceiling thermally insulated to a value greater than R40.

CAUTION

  1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
  2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.
  3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
  4. Please read specification label on product for further information and requirements.

CLEANING & MAINTENANCE

For quiet and efficient operation, long life, and attractive appearance – lower or remove grille and vacuum interior of unit with the dusting brush attachment.
The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the blower assembly (includes motor and impeller).

READ AND SAVE THESE INSTRUCTIONS Installer: Leave this manual with the homeowner.

PLAN THE INSTALLATION

  1. Do not use in a cooking area.

  2. Two ways to connect ductwork to a factory-shipped unit.

ASSEMBLY INSTRUCTIONS

  1. Before installation, you need to know:
  • Screw A ST4.2*13 mm

  • Screw B ST4.2*25 mm

  • Hanger bar 13 3/8 in. (340 mm)

When installing contractor packs, make sure to install any optional modules such as speed controls or humidity sensors with the fan housing to ensure wiring is completed properly. Module and grille plugs come packaged with the optional accessory and must be installed with the fan housing.

Ceiling installation
Mount with mounting holes Hold housing in place so that the housing contacts the bottom of the joist. Screw housing to joist through the hole A and hole B.

Mount with hanger bar
Slide one hanger bar into the channel on the housing and adjust as needed to fit between framing. Hold housing in place so that the housing contacts the bottom of the joist. Screw housing to joist through the hole A and hole B. Screw the hanger bar onto the other side of joist through its hole. Screw hanger bar to housing with screw A.

Mount to I-joist
Slide hanger bar into the channel on the housing and adjust as needed to fit I-joist. Hold housing in place so that the housing contacts the bottom of joist. Screw housing to joist through the hole A and hole B. Screw the hanger bar onto the joist through its hole.
Screw hanger bar to housing with screw A.

Wall installation
When the product is installed on the wall, the adaptor shall be faced upward.

Slide hanger bar into the channel on the housing. Hold housing in place so that the housing contacts the bottom of stud. Screw housing to stud through the hole A and hole B on the same side. Screw the hanger bar onto the opposite stud through its hole. Screw hanger bar to housing with screw A.
The minimum installation distance between studs is 13 3/8 in. (340mm.)

Install round ductwork
Connect the 4 in. round flexible ductwork (not included) to the damper/duct connector, and run the ductwork to a roof or wall cap (not included).
Using metal foil tape (not included), secure all the ductwork connections so that they are air tight. The ducting from this fan to the outside of building has a strong effect on the air flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible for best performance, and avoid installing the fan with smaller ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve their rated air flow.

CONNECT ELECTRICAL WIRING

  • Run 120V AC house wiring to the location of the fan. Use only UL-approved connectors and UL-approved wire strain relief (not included) to attach the house wiring to the wiring plate. Refer to the wiring diagram, and connect the wires as shown.

OPERATION

See “Connect Wiring” for details.

The control box, located inside the fan housing, has three separate adjustments:

  1. The low airflow knob adjusts the continuous run lower airflow from 30 CFM up to the air flow rate of the high fan speed determined by the toggle switch setting. The low speed is de-activated when set between OFF-30 CFM (factory set to OFF).
  2. The time delay knob is adjustable from 3 to 30 minutes and will switch the fan to the low speed setting after the Boost Switch is turned off for the set period of time. The time delay setting is de-activated when set between OFF-3 mins (factory set to OFF).
  3. The toggle switch will adjust the upper fan speed setting from 50 to 100 CFM (factory set to 100 CFM).

To Turn Fan ON

Turn the Control Switch (according to the following “CONNECT ELECTRICAL WIRING”) ON.

  • Fan will run at the certified high airflow rate if the Boost Switch is ON.
  • Fan will run at the continuous run low airflow rate if the Boost Switch is OFF.

To Use Fan Time Delay Airflow Rate Change

  1. Turn the Control Switch ON.
  2. Turn the Boost Switch ON – fan will run at the certified high airflow rate.
  3. When the Boost Switch is turned OFF, fan will continue to run at the certified high airflow rate until the time delay has elapsed (the delay time is user-adjustable from 3-30 minutes), and then will automatically change to the continuous run low airflow rate.

To Turn Fan OFF

Turn the Control Switch OFF.

  • Scan QR code for quick start guide.

READ AND SAVE THESE INSTRUCTIONS
Installer: Leave this manual with the homeowner.

INSTALL GRILLE

Install ceiling material to complete the ceiling construction. Then, cut around inside the fan housing.
To attach the grille assembly to the fan housing, pinch the grille springs on the sides of the grille assembly, and position the grille into the housing with the grille springs in the appropriate slots. Push the grille assembly towards the ceiling to secure.

SERVICE PARTS

No. Part No. Name Description
1 S1110513 Grilie Assembly Grille and springs
2 S1110515 Duct Reducer 411   Oval to 311
3 S1110516 Duct Connector Plastic
4 S1110521 Blower Assembly Motor plate, motor, wheel, blower scroll and

controller
5| S1110517| Wire Panel/Harness Assembly| Including wire
6| S1110519| Hanger Bar| 1 piece
7| S1110520| Parts Bag| 1 screw and 1 wiring plate

WARRANTY

This warranty covers all defects in workmanship or materials for:
The mechanical and electrical parts contained in this product, for a period of 12 months, from the date of purchase. You must keep and be able to provide your original sales receipt as proof of the date of purchase. This warranty covers the original retail purchaser of this product. The manufacturer will repair or replace, in your home, any mechanical or electrical part which proves defective in normal household use for a period of 12 months.
THIS WARRANTY DOES NOT COVER:

  • Damages from improper installation
  • Damages from shipping
  • Damages from misuse, abuse, accident, alteration, lack of proper care and maintenance
  • Damages from service by persons other than an authorized dealer or service center.
  • Labor, service, transportation and shipping charges for the removal of defective parts and for installation of a replacement part, beyond the initial 12-month period.

This warranty does not extend to fluorescent lamp starters and tubes.
THIS LIMITED WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy provided in this warranty is exclusive and is granted in lieu of all other remedies. This warranty does not cover incidental or consequential damages. Some states do not allow the exclusion of incidental or consequential damages, so this limitation may not apply to you. Some states do not allow limitations on how long an implied warranty lasts, so this limitation may not apply to you. This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals