Carrier OnGuard v1.1 Integration Owner’s Manual
- June 8, 2024
- Carrier
Table of Contents
- Carrier OnGuard v1.1 Integration
- What is the OnGuard Integration?
- Requirements
- When upgrading to i-Vu® Pro v8.0
- Running the OnGuard add-ons with i-Vu® Pro v8.0 or later
- BIP installation and configuration details
- IT considerations
- Configuring the Server
- Setting up the Data Connector add-on
- Setting zone properties
- Associating macroblocks with a zone
- Associating badge readers with a zone
- Setting up the Advanced Occupancy Scheduling add-on
- Setting scheduling properties of a zone
- Associating schedulable items to a zone
- Setting up the Integrated Alarm Management add-on
- Setting up alarms from the i-Vu® Pro system to OnGuard
- Setting up the alarm transfer schedule
- Troubleshooting
- Document revision history
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Carrier OnGuard v1.1 Integration
Verify that you have the most current version of this document from
www.hvacpartners.com, the Carrier Partner
Community website, or your local Carrier office.
Important changes are listed in Document revision history at the end of this
document.
Carrier© 2022. All rights reserved.
The content of this guide is furnished for informational use only and is
subject to change without notice.
Carrier assumes no responsibility or liability for any errors or inaccuracies
that may appear in the informational content contained in this guide.
What is the OnGuard Integration?
The OnGuard® Integration consists of a collection of add-ons that allow the i-Vu® Pro building automation system and an OnGuard® security system to work together. The OnGuard® Integration enables the i-Vu® Pro system to utilize actual occupancy data in control program logic by monitoring entry and exit events.
-
Included in the .zip file… Purpose
-
Data Connector (page 6) (onguard. addon)
- You must install the OnGuard® Data Connector add-on before installing any of the other OnGuard® .add-on files.
The i-Vu® Pro application can track Occupancy through the security system.
- You must install the OnGuard® Data Connector add-on before installing any of the other OnGuard® .add-on files.
-
Advanced Occupancy Scheduling (on guard -scheduling .addon)
- Based on historical occupancy trends, the add-on will write predicted scheduling to the i-Vu® Pro system which will allow for optimized energy usage.
-
Integrated Alarm Management (page 11) (on guard-alarms. addon)
- Facility staff and security staff can monitor each other’s alarms so that either team can dispatch appropriate personnel regardless of who is currently on shift. It also enables OnGuard® Action Groups to initiate control of the i-Vu® Pro system equipment.
-
Integration Helper Files (page 11) (OnGuardIntegrationHelper.zip)
This zip file includes:- alarm-manager. logic-script – Snap script that is used to add configured alarm points to your program.
- on guard-alarms. logic symbol – Logic symbol that is used by the script above. It includes a template for the macroblocks to be added to your program.
See “Installing an Add-on User Guide” for more information on the following:
- Installing an add-on
- Applying a license
- Running an add-on
- Upgrading an add-on
Requirements
- Carrier i-Vu® Pro v7.0 or later system with the latest cumulative patch
- Carrier hardware, if your application requirements include running logic for the transference of data to or from the OnGuard® system
- OnGuard® system with Administrator privilege:
- v7.5 or v7.6 ONLY, using Open Access interface – versions later then 7.6 are not certified compatible at this time
- Appropriate license applied for Open Access (Please see Lenel® phrasebook)
- Single sign-on configured and enabled
- Building Integration Platform (v1.11) (see the Building Integration Platform’s installation guide):
- Building Integration Platform Service installed
- OnGuard® Connector Service installed
- Username, password, and port number for the Building Integration Platform
- Network connectivity between the i-Vu® Pro Server, OnGuard® server, and Building Integration Platform server
When upgrading to i-Vu® Pro v8.0
If you are running the OnGuard Integration with a pre-v8.0 version of i-Vu® Pro, perform the following steps when you upgrade to i-Vu® Pro v8.0:
- During the upgrade to i-Vu® Pro v8.0, choose to keep your existing add-ons. Add-on configurations will be saved.
- Uninstall Building Integration Platform (BIP) v1.10, following the instructions in the Building Integration Platform Installation Manual.
- Install BIP v1.11, following the instructions in the Building Integration Platform Installation Manual.
Running the OnGuard add-ons with i-Vu® Pro v8.0 or later
When running the OnGuard add-ons with i-Vu® Pro v8.0 or later, it may appear
that your server is using more memory than it should. This occurs because v8.0
uses a newer version of Java, and most of the memory it reports as used is
actually free.
If you would like to see a more accurate report of memory usage, perform the
steps below on your i-Vu® Pro server:
- Go to the i-Vu Pro<x.x>\bin\launchers folder.
- Open the i-Vu Pro server.launch file in Notepad.
- Add this line: cjgreen.monitoredapp.config.gcimpl=-XX:+UseParallelGC Save the file.
- Open the i-Vu Pro service.launch file in Notepad.
- Add the same line of text as above, and save the file.
- Restart i-Vu Pro. Memory usage should now display as significantly lower.
BIP installation and configuration details
To enable communication between the WebCT and OnGuard servers, the Building Integration Platform (BIP) must be installed on a server that can connect to both application servers. Refer to the following documents to install and configure the BIP:
- Building Integration Platform Installation Guidelines
- Building Integration Platform Commissioning User Manual
The BIP is designed to support multiple integrations. This section describes the steps needed specifically for the OnGuard Integration.
BIP Installation
See the Building Integration Platform Components section of the BIP Installation Manual for which BIP services must be installed for the OnGuard Integration. Follow the instructions in that document to install each of the indicated services.
BIP Configuration
Refer to the BIP Commissioning User Manual to perform the following steps:
- Refer to the BIP Commissioning Access section to log in as the default web admin user using the default credentials, then change the password for the default web admin user.
- To set up additional web admin users:
- If the new user will not be authenticated with Active Directory or Single Sign-On, refer to the Local Database User Creation section to create the user in the BIP database.
- Refer to the User Management section to register the user with the role Admin with Web Login.
- Register your Lenel-OnGuard System
- Refer to the System Configuration > Add System Configuration section to add a system. Select “Lenel-OnGuard” as your System Type.
- Refer to the Register Lenel-OnGuard System sub-section to complete the registration.
- The Configuring the Server section of this document explains how to connect to a BIP Resource. Refer to the Resource Registration > Add Resource section to create a BIP Resource for this purpose with:
- Resource IDs: aaa, disservice
- Grant Type: service
- Scopes: read, write
- Access Token Time: 1 month
IT considerations
The following information may be useful to network administrators.
- The Building Integration Platform server ports default to 8443 and 8444, but can be customized in the field.
Building Integration Platform
The OnGuard® Data Connector add-on communicates with OnGuard® Server via the
Building Integration Platform.
The OnGuard® Data Connector communicates to the Building Integration Platform
using REST and Server Sent Event technologies. The REST APIs are secured using
TLS 1.2 and authenticated using a username/password that is configured in the
Building Integration Platform. Credentials for the service account are stored
to a file by this add-on and secured using AES-128 encryption. The Server Sent
Events are only accessible through the REST APIs, so they are secured in a
similar way.
Configuring the Server
- On the Server Configuration tab, enter the OnGuard Connector settings. See table below.
- To allow a Self Signed Certificate, check the checkbox.
Note: Choosing this option will result in a less secure configuration, therefore should only be chosen when you are unable to use a certificate signed by a certificate authority.
NOTE
Status indicates Connected if configured properly. If errors occurred, view
the Activity Log (to the right) to help diagnose what may be preventing the
connection from being established.
NOTE
You must configure your Lenel® OnGuard system with the System Name
“OnGuard”. You can edit this field in the Building Integration Platform’s
System Configuration tab.
Setting up the Data Connector add-on
To track occupancy through the security system, you must define one or more
zones.
NOTE For the purpose of this integration, a zone is a geographical area
for which occupancy can be detected through the activity of its associated
badge readers.
Adding a zone
- On the Occupancy tab, enter a unique name for the new zone in the Add New Zone field.
- Press Enter to add the new zone – it appears in the list of zones below.
NOTE
To remove a zone from the list, click the Delete button to the right of the
zone name.
Setting zone properties
-
On the Occupancy tab, click the zone you wish to configure in the Zone list.
-
Click Config in the Occupancy panel.
-
Select a value for the Full Occupancy Count lertethe zone.
The zone is considered fully occupied when the occupancy count reaches this number. -
Enter a time for the Reset Time.
The occupancy count is automatically cleared at this time each day to ensure that each day’s occupancy tracking does not accumulate errors from the day before.
NOTE If the add-on is shut down at any time, the last known occupancy count is retained.
Exporting and clearing the prediction history
Prediction history can be exported to a .csv file which is named after a
selected zone. Exporting the prediction history purges all but the most recent
30 entries from the Prediction History panel.
On the Scheduling tab, select the desired zone, then click the Export
Predictions button in the Prediction History panel.
Associating macroblocks with a zone
A control program can be designed to operate on zone occupancy data from the integration. Do this by associating macroblocks in the control program as targets to receive the zone occupancy data. The macroblocks are updated 1 minute after startup and every 5 minutes following that. There are four different macroblocks that can be configured.
Microblock | Maps too… | And represents… |
---|---|---|
Occupancy Count | an AV microblock | how many people are currently badged into a |
zone.
Full Occupancy Count| an AV microblock| the number of people that would be
considered 100% occupied.
Occupancy Percent| an AV microblock| the percentage of people in a zone based
on the Occupancy Count/Full Occupancy Count.
Comm stat| an MSV microblock| the communication status with the Building
Integration Platform.
MSV values must be configured in the macroblock:
1=Comm Failed
2=Comm OK
3=Subscriptions Pending
This value is updated both periodically and on change of value.
Auto-mapping with predetermined reference names
Use these predefined reference names in the equipment file:
Set this reference name… | to start with… | for this microblock type |
---|---|---|
Occupancy Count | onguard_occ | AV |
Full Occupancy Count | onguard_full_occ | AV |
Occupancy Percent | onguard_pct_occ | AV |
Communication Status | onguard_comm_stat | MSV |
- On the Occupancy tab, click the zone you wish to configure in the Zone list.
- Click Macroblocks in the Occupancy panel.
- When the Equipment panel appears, navigate the Equipment tree and select the equipment with the predefined reference names (see table above).
- Drag the selected equipment from the tree to any slot in the Macroblocks section.
NOTES
- All the predefined reference names will be assigned to the associated points. Depending on the system size, this operation may take a few seconds.
- To remove a macroblock association, click the Delete button to the right of the micro block name.
Manual mapping of reference names
- On the Occupancy tab, click the zone you wish to configure in the Zone list.
- Click Microblocks in the Occupancy panel.
- When the Equipment panel appears, navigate the Equipment tree and select a micro block to associate.
- Drag the selected micro block from the tree to the corresponding slot in the Micro blocks section.
NOTE To remove a micro block association, click the Delete button to the right of the micro block name.
Associating badge readers with a zone
Each zone can be assigned entrance badge readers to detect how many people have badged into a zone. Each unique badge entry event increments the occupancy count for that zone. When the badge is detected in another zone the occupancy count is decremented in the original zone and incremented in the new zone.
NOTES
- If no readers are configured under an OnGuard® device panel, the OnGuard® device panel will not show up under Peripheral Devices.
- A badge reader can only be mapped to a single zone. Readers that are already mapped will be grayed out (disabled) in the Peripheral Devices panel.
- Use the electrical drawing to determine which Access Control Devices belong to which zone.
To associate a badge reader
-
On the Occupancy tab, click on the zone you wish to configure in the zone list.
-
Click Associated Devices in the Occupancy panel.
-
When the Peripheral Devices panel appears, select a reader to associate.
NOTE The items in the list are retrieved from the configuration of the connected OnGuard® system. -
Drag the selected reader to the Associated Devices section.
NOTE To remove a reader association, click the Delete button to the right of the reader name.
Setting up the Advanced Occupancy Scheduling add-on
Advanced Occupancy Scheduling is an add-on that predicts and schedules
occupancy based on past occupancy data. The schedule that is generated
contains no undefined regions and the whole day is scheduled with off and on
times. For example, a 9-5 schedule would be written with midnight to 9am as
off, 9am-5pm as on and 5pm to midnight as off.
The Occupancy Schedule Optimizer algorithm provided with the algorithm
schedules optimal building area operational schedules based on actual building
usage patterns. This add-on compares security card logs to occupancy count
information in user-defined areas and then schedules equipment based on the
average time the area reaches a user-defined occupancy threshold.
The add-on functions by associating data by day of the week and maintaining
rolling data sets of the last five occurrences. For example, the add-on
schedules equipment on Monday based upon the usage patterns of the five most
recent Mondays. This allows the algorithm to accommodate variations of
occupancy among the different days of the week and adapt over time as usage
patterns change.
The Occupancy Percentage parameter allows the user to define when the building
is considered occupied for the purposes of scheduling using a percentage
value. For example, for an area with full occupancy of 100 people, setting the
parameter to 5% results equipment being scheduled ON when the algorithm
predicts five or more occupants will be present. Increasing the parameter
conserves energy by allowing a larger occupancy count to be considered
unoccupied, with the converse true for reducing it.
Finally, the Occupancy Schedule Optimizer algorithm conducts continuous data
quality checks to ensure that irregular occupancy events, such as holidays, do
not impact the scheduling function. Any data that deviates significantly from
the rolling data set is discarded when predicting schedules.
Setting scheduling properties of a zone
TIP For the scheduling properties described below, you must have either the Start Time or Stop Time set to Predicted before you can configure Algorithm or Occupancy Percent.
-
On the Scheduling tab, click on the zone you wish to configure in the Zone list.
-
Click on Config in the Schedules panel.
-
Set both the Start Time and Stop Time to either Predicted or Fixed; if Fixed, select a time.
NOTE If Predicted, select an algorithm and a percent for occupancy. -
Select an Algorithm from the drop list to use for the occupancy prediction.
-
Adjust the Occupancy Percent setting to modify how the selected algorithm predicts the start and stop time.
NOTE
Use the Reset All Occupancy Data button () on the Zone panel to remove all
data used by the occupancy schedule algorithm. The add-on must re-accumulate
this data before the algorithm can make schedule predictions. Use this option
after an extended period of unusual occupancy activity. For example, when a
building has just come out of commissioning and is ready to start recording
real occupancy data.
Associating schedulable items to a zone
- On the Scheduling tab, click on zone you wish to configure in the Zone list.
- Click on Destinations in the Schedules panel.
- From the Destination panel, you can either add Areas and Equipment or Scheduling Groups:
- In the Areas and Equipment section of the Destination panel, drag the desired Area or Equipment to the Destinations section of the Schedules panel.
- In the Scheduling Groups section of the Destination Panel, drag and drop the scheduling group to the Destinations section of the Schedules panel.
NOTES:
- To remove a schedulable association, click the Delete button to the right of the schedulable name.
- Toggle on and off the Write Schedules button ( ) on the Zone panel to enable and disable the writing of predictions to system schedules.
- Use the Export Predictions button ( ) in the Prediction History panel to export the prediction history to a .csv file named after the selected zone. Exporting the prediction history purges all but the most recent 30 entries from the Prediction History panel.
Setting up the Integrated Alarm Management add-on
Integrated Alarm Management is an add-on that enables the exchange of alarms between the i-Vu® Pro system and the OnGuard® system.
Setting up alarms from OnGuard to the i-Vu® Pro system
In order to send alarms from an OnGuard® system to the i-Vu® Pro system, you must define a mapping. The mapping describes the OnGuard® event source and the destination macroblock which re-generates the alarm for the i-Vu® Pro system.
Adding an alarm mapping
- On the Alarms tab, click OnGuard to i-Vu Pro.
- Click the Edit Events button.
- Click the Add New Mapping button.
- In the Mapping Configuration panel, set the OnGuard Source:
- Click the Event Type slot, then select a type from the available choices.
- With the Event Sub Type slot now selected, select a sub-type.
- In the Mapping Configuration panel, specify if this mapping should Use Schedule:
- No will always transfer alarms regardless of the schedule.
- Yes will only transfer alarms during the scheduled time range. See Setting up the alarm transfer schedule (page 14) for more information.
NOTES
- To remove a mapping, click the Delete button to the right of the mapping.
- You can use an exported configuration to generate an equipment file containing your mapped alarm points. See Exporting Zone Mapping below. Alarm points will be given renames as indicated in the Rename Template below.
- To add alarm points to an existing equipment file, locate the i-Vu® Pro Destination section on the Mapping Configuration panel to see the macroblock rename template generated by the add-on. Use this template to construct a rename to be used in the equipment file to map this point to a BV macroblock. See the rename template and example below.
RefnameTemplate: almbv_p
All of the fields in <> above are numbers provided by the OnGuard system.
EXAMPLE: almbv_p1_d4_type4_subtype8
In this example, the alarm is from Panel 1, device 4, event type 4 (system),
sub-event 8 (door forced open)
Adding Zone Mapping
Map the equipment files to the zones to receive OnGuard® events. Once the Zone
Mapping is set up, any mapped OnGuard® events will be written to the mapped BV
micro blocks in the mapped Equipment file.
- On the Alarms tab, click OnGuard to i-Vu Pro.
- Click the Edit Zones button to open the Zone Map and Equipment panels.
- Drag the equipment from the Equipment panel to the desired zone in the Zone Map panel.
NOTE
To delete a zone’s association with a piece of equipment, click the Delete
button to the right of the zone.
Exporting Zone Mapping
You can export a JSON configuration file that contains the current OnGuard to
i-Vu Pro Events and Zones to be used with Snap to build equipment for the
selected Alarm Mappings.
- On the Alarms tab, click OnGuard to i-Vu Pro.
- Click on the Export ( ) button to download the current configuration file; this downloads an on guard mapping .json file.
Adding Alarm Manager Points to an equipment file
The JSON configuration file can be used in the Snap application to add the
mapped points to an equipment file.
To add Snap Script to the Snap application:
- In the Snap application add the “Scripts plug-in” (refer to Snap Help for this step).
- In Snap select Tools>Scripts>Configure, then click Add.
- Select the alarm-manager. logic-script from the onguard-integration.zip file.
- Click Ok.
To add Snap Symbols:
- Create a folder called “onguard_integration_helper” inside of
\extras\tools. - Select the on guardalarms .logic-symbol file from the onguard-integration.zip file; then move the file into the onguard_integration_helper folder created above.
To add OnGuard® Alarm Points to an equipment file:
Once the alarm-manager.logic-script and alarm-manager.logic symbol has been
properly installed, OnGuard® Alarm points can be appended to existing
equipment files with appropriate reference names.
- Export the current Zone Mapping JSON configuration file (see Exporting Zone Mapping section above) and note where you download the onguardmapping.json file.
- In Snap, open the equipment file that corresponds to the zone that you want to append the OnGuard® alarm points to.
- Select Tools>Scripts>alarm-manager to open a script editor.
- Press the Execute button in the script editor to run the script which will bring up a file dialog. Navigate to the onguardmapping.json file created in step 1.
- Select the onguardmapping.json file and click Open.
- From the drop-down list of available zones, select the zone that corresponds to your equipment file and click Ok. The Alarm Manager points are appended to the open equipment file.
- Close the script editor.
NOTE
If constructing an equipment file serving multiple zones, repeat steps 4
through 6 for different zone selections on the same equipment file.
Setting up alarms from the i-Vu® Pro system to OnGuard
In order to send alarms from the i-Vu® Pro system to the OnGuard® system, a source must be defined in the OnGuard® system to act as the originator of the alarms. There can be many sources defined for the i-Vu® Pro system to use, and each source can be configured to transfer i-Vu® Pro alarms by category.
The i-Vu® Pro alarms notifications that are sent to OnGuard® are:
- Alarm is generated
- Alarm is acknowledged
- Alarm point returned to normal
Setting up the alarm source
- On the Alarms tab, click System Select > i-Vu Pro to OnGuard.
- Select the OnGuard Source to configure.
- Under the Category column to the right, select each alarm category to enable for that source.
- Next to each alarm category, specify when it should transfer alarms:
- Select No to always transfer alarms regardless of the schedule.
- Select Yes to only transfer alarms during the scheduled time range. See Setting up the alarm transfer schedule (page 14) for more information.
Setting up the alarm transfer schedule
For items that you have selected YES for Use Schedule, you must specify the alarm transfer schedule. The transfer schedule time range applies to both OnGuard to i-Vu Pro and i-Vu Pro to OnGuard alarms.
On the Alarms tab, set the following from the System Select column in the Schedule section:
- Start Time – to start sending alarms
- Stop Time – to stop sending alarms
Troubleshooting
If the connection is not successful and you receive an error message in the Activity Log panel, see the table below.
Error message / Solution
- Error reading system id, No active system named OnGuard
- Make sure your Lenel® OnGuard system is configured with the System Name “OnGuard”. You can edit this field in the Building Integration Platform’s System Configuration tab.
- Error authenticating with DIP
- Check Allow Self Signed Certificate. If using a signed certificate, uncheck after the connection is established. If using a self-signed certificate, leave it checked.
Document revision history
Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not listed.
Date | Topic | Change description | Code* |
---|---|---|---|
7/28/22 | Requirements | Updated version requirements | AC-PM-LO-O- LO |
- For internal use only
OnGuard v1.1 Integration for v8.0 or later systems
Carrier Proprietary and Confidential
©2022 Carrier.
All rights reserved.