VENTS TT PRO EC Series TT PRO 100 EC Inline Mixed-Flow Fans User Manual
- June 4, 2024
- VENTS
Table of Contents
INLINE MIXED-FLOW FANS
User’s manual
TT PRO EC
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff. The manual contains information about the
purpose, technical details, operating principle, design, and installation of
the TT PRO EC unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
All user’s manual requirements, as well as the provisions of all the
applicable local and national construction, electrical, and technical norms
and standards, must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000
V are allowed for installation. The present user’s manual should be carefully
read before beginning work.
Check the unit for any visible damage to the impeller, the casing, and the
grille before starting installation. The casing internals must be free of any
foreign objects that can damage the impeller blades. While mounting the unit,
avoid compression of the casing!
Deformation of the casing may result in motor jams and excessive noise.
Misuse of the unit and any unauthorized modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky
substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure efficient
airflow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to incorporate
the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
This appliance can be used by children aged 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction concerning the
use of the appliance in a safe way and understand the hazards involved
Cleaning and user maintenance shall not be made by children without
supervision
Children shall not play with the appliance.
Connection to the mains must be made through a disconnecting device, which is
integrated into the fixed wiring system in accordance with the wiring rules
for the design of electrical units and has a contact separation in all poles
that allows for full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent, or similarly qualified persons in order to avoid a safety
hazard.
If the cord set is damaged, it must be replaced by a special cord set
available from the manufacturer or its service agent.
CAUTION: In order to avoid a safety hazard due to inadvertent resetting
of the thermal cut-out, this unit must not be supplied through an external
switching device, such as a timer, or connected to a circuit that is regularly
switched on and off by the utility. Ensure that the unit is switched off from
the supply mains before removing the guard.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances.
THE PRODUCT MUST BE DISPOSED OF SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE OF THE UNIT AS UNSORTED DOMESTIC WASTE.
DELIVERY SET
Fan | — 1 pc. |
---|---|
Screws and dowels | — 4 pcs. |
User’s manual | — 1 pc. |
Packing box | — 1 pc. |
BRIEF DESCRIPTION
The product described herein is a mixed-flow inline fan for supply or exhaust
ventilation of premises heated during winter time.
The fan is designed for connection to ø 100, 125, 150, 160, 200, 250, and 315
mm air ducts.
The fan is equipped with an energy-efficient and high-performance
electronically commutated motor (EC motor) and with a built-in speed
controller.
An external control unit can be connected to the fan (purchased separately).
The fan design is constantly being improved, thus some models may be slightly
different from those described in this manual.
OPERATION GUIDELINES
The fan is rated for connection to single-phase AC 220-240 V/50 (60) Hz power
mains. The fan is rated for continuous operation.
Air motion direction in the system must match the pointer on the fan casing.
Hazardous parts access and water ingress protection rating is IPX4.
The fan is rated for operation at the ambient temperature ranging from +1 °C
up to +40 °C.
The transported air temperature must not exceed +40 °C. Temperature up to +60
° C is allowed for a short time (up to 15 minutes).
The ventilator is rated as a class II electric appliance.
DESIGNATION KEY
To comply with the ErP 2018 regulation, a local demand controller must be used.
INSTALLATION
The fan is suitable both for horizontal or vertical mounting on the floor, on
the wall or on the ceiling (Fig. 1).
While mounting the fan provide extra protection against water ingress, such
as:
- For the top mounting: install an outer protecting hood above (Fig. 2).
- For any mounting position: connect an air duct on both sides of the fan (Fig. 2).
The mounting sequence is shown in Fig. 3-8.
The sequence of connecting the fan to power mains is shown in Fig. 9-11, 13-14.
The fan wiring diagram is shown in Fig. 15.
TERMINAL DESIGNATIONS ON WIRING DIAGRAMS
QF | external circuit breaker |
---|---|
Х1 | terminal block for 230 V/50-60 Hz power mains |
Х2 | terminal block for connection of an external speed controller |
S1 | external speed controller 0-10 V |
R1 | internal speed controller |
SW | DIP switch |
OPERATION ALGORITHM
The motor is controlled by sending of an external control signal from 0 to 10
V to the X2 terminal block or by the R1 internal speed controller. Control
method selection is carried out by means of the SW DIP switch:
– DIP switch in IN position. The control signal is set by the R1 internal
speed controller, which allows turning the fan on and off, and smoothly adjust
the speed of the fan motor (airflow) in the range from minimum to maximum
speed.
Rotations are controlled from minimum (extreme right position) to maximum
(extreme left position). When rotating clockwise, the rotations decrease.
– DIP switch in EXT position. The control signal is set by the S1 external
control unit.
The TT PRO EC U (Un) fan is equipped with an electronic module TSC (speed
controller with an electronic thermostat) for automatic fan speed control
(airflow) depending on the air temperature.
The terminal compartment incorporates 2 control knobs:
• presetting speed
• setting an electric thermostat threshold value
The thermostat operation indicator is located on the fan cover.
To set the thermostat threshold, rotate the thermostat control knob clockwise
to increase or counter-clockwise to decrease the temperature set point.
To set the fan speed (airflow), rotate the speed control knob in the same way.
CAUTION! In case of short-term effects of electrostatic disturbance on the TT PRO EC U (Un) fan, the fan may stop. To restore it, turn the fan off and on with the speed controller, which is located on the fan casing.
MAINTENANCE
Clean the product surfaces regularly (once in 6 months) from dust and dirt
(Fig. 18-21). Disconnect the fan from power mains prior to any maintenance
operations. To clean the fan, use a soft cloth or a brush wetted in a mild
detergent solution. Avoid water ingress to electrical components.
Wipe the unit surfaces dry after cleaning.
TROUBLESHOOTING
Problem | Possible reasons | Troubleshooting |
---|
When the unit is connected to power
mains, the fan does not rotate and
does not respond to any controls.| No power supply.| Make sure the power
supply line is connected correctly, otherwise
troubleshoot the connection error.
Internal connection fault.| Contact the Seller.
Low airflow.| The ventilation system is clogged.| Clean the ventilation
system.
Increased noise, and vibration.| The impeller is clogged.| Clean the impeller.
The fan is not secured well or is not mounted properly.| Troubleshoot the
installation error.
The ventilation system is clogged.| Clean the ventilation system.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with a temperature range from +5 ˚С to +40 ˚С and relative humidity up to 70 %.
- The storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility. We hereby declare that the
product complies with the provisions of the Electromagnetic Compatibility
(EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low
Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the
Council and CE-marking Council Directive 93/68/EEC. This certificate is issued
following a test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to the elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated by means of replacement or repair of the unit components or a
specific part of the such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from a warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts, and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit were committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT, AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
|
---|---
|
|
Certificate of Acceptance
TT PRO EC
The fan is recognized as serviceable.