BEHLER-YOUNG FX4D Fan Coils Instruction Manual
- June 9, 2024
- BEHLER-YOUNG
Table of Contents
FX4D Fan Coils
Instruction Manual
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use
can cause explosion, fire, electrical shock, or other conditions which may
cause death, personal injury or property damage. Consult a qualified
installer, service agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factory-authorized kits
or accessories when modifying this product.
Refer to the individual instructions packaged with kits or accessories when
installing.
Follow all safety codes. Wear safety glasses, protective clothing and work
gloves. Have a fire extinguisher available. Read these instructions thoroughly
and follow all warnings or cautions included in literature and attached to
the unit. Consult local building codes and the current editions of the
National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA
C22.1.
Recognize safety information. This is the safety-alert symbol . When you see
this symbol on the unit and in instruction manuals, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER identifies the most
serious hazards which will result in severe personal injury or death. WARNING
signifies hazards which could result in personal injury or death. CAUTION is
used to identify unsafe practices which may result in minor personal injury or
product and property damage.
NOTE is used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
WARNING
ELECTRICAL OPERATION HAZARD
Failure to maintain proper clearances could result in personal injury or
death.
Before installing or servicing unit, always turn off all power to unit.
There may be more than 1 disconnect switch. Turn off accessory heater power if
applicable. Lock out and tag switch with a suitable warning label.
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate
protective clothing, safety glasses and gloves when handling parts.
INTRODUCTION
Model FX4D is designed for flexibility and can be used for upflow, horizontal,
or downflow (kit required) and manufactured and mobile home applications.
These units are designed to meet the low air leak requirements currently in
effect. Because of this, the units need special attention in the condensate
pan and drain connection area and when brazing tubing. These units are
designed specifically for Puronr refrigerant and must be used only with Puronr
refrigerant air conditioners and heat pumps as shipped. These units are
available for systems of 18,000 through 60,000 Btuh nominal cooling capacity.
Factory-authorized, field-installed electric heater packages are available in
sizes 5 through 30kW. See Product Data literature for available accessory
kits.
HEATER PACKAGES
This unit may or may not be equipped with an electric heater package.
For units not equipped with factory-installed heat, a factory-approved, field-
installed, UL listed heater package is available from your equipment supplier.
See unit rating plate for a list of factory-approved heaters. Heaters that are
not factory approved could cause damage which would not be covered under the
equipment warranty. If fan coil contains a factory-installed heater package,
minimum circuit ampacity (MCA) and maximum fuse/breaker may be different than
units with a same size field-installed accessory heater. The difference is not
an error and is due to calculation differences per UL guidelines.
INSTALLATION
CHECK EQUIPMENT
Unpack unit and move to final location. Remove carton taking care not to
damage unit. Inspect equipment for damage prior to installation. File claim
with shipping company if shipment is damaged or incomplete. Locate unit rating
plate which contains proper installation information. Check rating plate to be
sure unit matches job specifications.
MOUNT UNIT
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for
wiring, piping, and servicing unit.
IMPORTANT: When unit is installed over a finished ceiling and/or living
area, building codes may require a field-supplied secondary condensate pan to
be installed under the entire unit. Some localities may allow as an
alternative, the running of a separate, secondary condensate line. Consult
local codes for additional restrictions or precautions.
NOTE: Nuisance sweating may occur if the unit is installed in a high
humidity environment with low airflow.
UPFLOW INSTALLATION
If return air is to be ducted through a floor, set unit on floor over opening
and use 1/8 to 1/4-in (3 to 6 mm) thick fireproof resilient gasket between
duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening per
dimensions. (See Fig. 1.) A field-supplied bottom closure is required.
DOWNFLOW INSTALLATION
In this application, field conversion of the evaporator is required using
accessory downflow kit along with an accessory base kit. Use fireproof
resilient gasket, 1/8 to 1/4-in (3 to 6 mm) thick, between duct, unit, and
floor.
FX4D: Installation Instructions Fig. 1 – Slope Coil Unit in Upflow Application
CAUTION
PRODUCT OR PROPERTY DAMAGE HAZARD
Failure to follow this warning caution may result in product or property
damage.
The conversion of the fan coil to downflow requires special procedures for the
condensate drains on both A-coil and Slope-coil units. The vertical drains
have an overflow hole between the primary and secondary drain holes. This hole
is plugged for all applications except downflow, and must be used for
downflow. During conversion process, remove plastic cap covering vertical
drains only and discard. Remove plug from overflow hole and discard. At
completion of downflow installation, caulk around vertical pan fitting to door
joint to retain low air leak performance of the unit.
NOTE: To convert units for downflow applications, refer to Installation
Instructions supplied with kit for proper installation. For slope fan coils,
use kit Part No. KFADC0201SLP. For A-coils, use kit Part No.
KFADC0401ACL. Use fireproof resilient gasket, 1/8 to 1/4-in (3 to 6 mm) thick,
between duct, unit, and floor.
NOTE: Gasket kit number KFAHD0101SLP is also required for all downflow
applications to maintain low air leak/low sweat performance.
NOTE: Modular units can be disassembled and components moved separately
to installation area for reassembly. This process accommodates small scuttle
holes and limiting entrances to installation sites. (See Fig. 2.)
HORIZONTAL INSTALLATION
Units must not be installed with access panels facing up or down. All other
units are factory built for horizontal left installation. (See Fig. 3 and 4.)
When suspending unit from ceiling, dimples in casing indicate suitable
location of screws for mounting metal support straps. (See Fig. 3.)
For horizontal applications having high return static and humid return air,
the Water Management Kit, KFAHC0125AAA, may need to be used to assist in water
management.
Horizontal Right Conversion of Units with Slope Coils
NOTE: Gasket kit number KFAHD0101SLP is required for horizontal slope
coil conversion to maintain low air leak/low sweat performance. Fig. 2 –
Modular Unit Assembly
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
For optimum condensate drainage performance in horizontal installations, unit
should be leveled along its length and width.
- Remove blower and coil access panels and fitting panel. (See Fig. 5.)
- Remove coil mounting screw securing coil assembly to right side casing flange.
- Remove coil assembly.
- Lay fan coil on its right side and reinstall coil assembly with condensate pan down (See Fig. 5.)
- Attach coil to casing flange using previously removed coil mounting screw.
- Make sure pan cap in fitting door is properly seated on fitting door to retain low air leak rating of the unit.
- Add gaskets from kit – KFAHD.
- Align holes with tubing connections and condensate pan connections. Reinstall access panels and fitting panel.
Fig. 3 – Slope Coil in Horizontal Left Application (Factory Configuration)| Fig. 4 – A-Coil in Horizontal Left Application (Factory Configuration)
---|--- - Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. Install grommets after brazing.
Horizontal Right Conversion of Units with A-Coils
-
Remove blower and coil access panels. (See Fig. 6.)
-
Remove metal clip securing fitting panel to condensate pan.
Remove fitting panel. -
Remove 2 snap-in clips securing A-coil in unit.
-
Slide coil and pan assembly out of unit.
-
Remove horizontal drain pan support bracket from coil support rail on left side of unit and reinstall on coil support rail on right side of unit. (See Fig. 7.)
-
Convert air seal assembly for horizontal right.
a. Remove air seal assembly from coil by removing 4 screws. (See Fig. 6)
b. Remove air splitter (B) from coil seal assembly by removing 3 screws. (See Fig. 6 inset)
c. Remove filler plate (A) and install air splitter (B) in place of filler plate.
d. Install filler plate (A) as shown in horizontal right application.
e. Remove condensate troughs (C) and install on opposite tube sheets.
f. Install hose onto plastic spout. -
Install horizontal pan on right side of coil assembly.
-
Slide coil assembly into casing. Be sure coil bracket on each corner of vertical pan engages coil support rails.
-
Reinstall 2 snap-in clips to correctly position and secure coil assembly in unit. Be sure clip with large offset is used on right side of unit to secure horizontal pan.
-
Remove two oval fitting caps from left side of the coil, access panel, and fitting panel.
-
Remove insulation knockouts on right side of coil access panel.
-
Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel.
-
Install condensate pan fitting caps (from Step 10) in right side of coil door making sure that cap snaps and seats cleanly on back side of the coil door. Make sure no insulation interferes with seating of cap.
-
Reinstall access and fitting panels, aligning holes with tubing connections and condensate pan connections. Be sure to reinstall metal clip between fitting panel and vertical condensate pan.
-
Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.
Fig. 6 – Conversion for Horizontal Right Applications – A-Coil Fig. 7 – Drain Pan Support Bracket
MANUFACTURED HOUSING AND MOBILE HOME APPLICATIONS
- Fan coil unit must be secured to the structure using field-supplied hardware.
- Allow a minimum of 24 inches (610mm) clearance from access panels.
- Recommended method of securing for typical applications:
a. If fan coil is away from wall, attach pipe strap to top of fan coil using No. 10 self tapping screws. Angle strap down and away from back of fan coil, remove all slack, and fasten to wall stud of structure using 5/16” lag screws. Typically both sides of the fan coil.
b. If fan coil is against wall, secure fan coil to wall stud using 1/8” (3mm) wide right-angle brackets. Attach brackets to fan coil using No. 10 self tapping screws and to wall stud using 5/16” lag screws (refer to Fig. 8).
AIR DUCTS
Connect supply-air duct over the outside of 3/4-in (19 mm) flanges provided on
supply-air opening. Secure duct to flange, using proper fasteners for type of
duct used, and seal duct-to-unit joint. If return-air flanges are required,
install factory-authorized accessory kit.
Use flexible connectors between ductwork and unit to prevent transmission of
vibration. When electric heater is installed, use heat-resistant material for
flexible connector between ductwork and unit at discharge connection. Ductwork
passing through unconditioned space must be insulated and covered with vapor
barrier.
Units equipped with 20-30kW electric heaters require a 1-in (25 mm) clearance
to combustible materials for the first 36-in (914 mm) of supply duct.
DUCT WORK ACOUSTICAL TREATMENT
Metal duct systems that do not have a 90 degree elbow and 10 feet of main duct
before first branch takeoff may require internal acoustical insulation lining.
As an alternative, fibrous duct work may be used if constructed and installed
in accordance with the latest edition of SMACNA construction standard on
fibrous glass ducts. Both acoustical lining and fibrous duct work shall comply
with National Fire Protection Association as tested by UL Standard 181 for
Class 1 air ducts.
ELECTRICAL CONNECTIONS
All products from the factory protect the low voltage circuit with a 5 amp
automotive type fuse inline on the wire harness. Speed selections are made at
the fan motor by selecting taps 1, 2 or 3 with the blue wire (see section E).
The motor is pre-programmed with the time delay circuit on some of the speed
taps ( see section E for clarification).
When a factory-approved accessory control package has been installed, check
all factory wiring per unit wiring diagram and inspect factory wiring
connections to be sure none were loosened in transit or installation. If a
different control package is required, see unit rating plate.
Before proceeding with electrical connections, make certain that supply
voltage, frequency, phase, and ampacity are as specified on the unit rating
plate. See unit wiring label for proper field high- and low-voltage wiring.
Make all electrical connections in accordance with the NEC and any local codes
or ordinances that may apply. Use copper wire only.
WARNING
ELECTRICAL SHOCK OR UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death, and/or
unit damage.
If a disconnect switch is to be mounted on unit, select a location where drill
and fasteners will not contact electrical or refrigeration components.
The unit must have a separate branch electric circuit with a field-supplied
disconnect switch located within sight from, and readily accessible from, the
unit.
On units with a factory-installed disconnect with pull-out removed, service
and maintenance can be safely performed on only the load side of the control
package.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Field wires on the line side of the disconnect found in the fan coil unit
remain live, even when the pull-out is removed. Service and maintenance to
incoming wiring cannot be performed until the main disconnect switch (remote
to the unit) is turned off. Lock out and tag switch with a suitable warning
label.
LINE VOLTAGE CONNECTIONS
If unit contains an accessory electric heater, remove and discard power plug
from fan coil and connect male plug from heater to female plug from unit
wiring harness. (See Electric Heater Installation Instructions.)
For units without electric heat:
- Connect 208/230V power leads from field disconnect to yellow and black stripped leads.
- Connect ground wire to unit ground lug.
NOTE: Units installed without electric heat should have a field-supplied
sheet metal block-off plate covering the heater opening. This will reduce air
leakage and formation of exterior condensation.
MANUFACTURED HOUSING
In manufactured housing applications, the Code of Federal Regulations, Title
24, Chapter XX, Part 3280.714 requires that supplemental electric heat be
locked out at outdoor temperatures above 40_F (4_C), except for a heat pump
defrost cycle. Refer to Fig. 14 for typical low voltage wiring with outdoor
thermostat.
TRANSFORMER INFORMATION
Transformer is factory wired for 230V operation. For 208V applications,
disconnect the black wire from the 230V terminal on transformer and connect it
to the 208V terminal (refer to Fig. 15).
|
---|---
|
HEATER STAGING
The controls are factory circuited for single-stage operation. For 2-stage
operation, use outdoor thermostat kit Part No. KHAOT0301FST, and for 3-stage
use both kits Part No. KHAOT0201SEC and KHAOT0301FST.
When 2 stages are desired, cut W3 at the W2 wire nut, strip and reconnect per
the thermostat kit instruction. (See Fig. 13.) When 3 stages are desired, cut
the W2 wire nut off and discard. Strip W2, W3, and E and reconnect per
thermostat kit instructions. (See Fig. 13.)
NOTE: When 3 stages are used or anytime the E terminal is not tied to W2,
the emergency heat relay, part of outdoor kit Part No.
KHAOT0201SEC must be used.
|
---|---
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
If W2, W3, and E on any 3 stage heater (18, 20, 24, or 30kW) are individually
connected – as with outdoor thermostats or any other situation – emergency
heat relay must be used. This relay is in kit Part No. KHOT0201SEC and is used
normally with kit Part No.
KHAOT0301FST.
GROUND CONNECTIONS
NOTE: Use UL listed conduit and conduit connectors for connecting supply
wire(s) to unit to obtain proper grounding. Grounding may also be accomplished
by using grounding lugs provided in control box.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to establish uninterrupted or unbroken ground could result in personal
injury and/or death.
According to NEC, NFPA 70, and local codes, the cabinet must have an
uninterrupted or unbroken ground to minimize personal injury if an electrical
fault should occur. The ground may consist of electrical wire or metal conduit
when installed in accordance with existing electrical codes. If conduit
connection uses reducing washers, a separate ground wire must be used.
MINIMUM CFM AND MOTOR SPEED SELECTION
The fan speed selection is done at the motor connector. Units with or without
electric heaters require a minimum CFM. Refer to the unit wiring label to
ensure that the fan speed selected is not lower than the minimum fan speed
indicated.
Table 1 – Motor Speed Selection
Tap 1 | Low | 90 sec off delay |
---|---|---|
Tap 2 | Medium | 90 sec off delay |
Tap 3 | High | 90 sec off delay |
Tap 4 | Electric heat † | 0 sec off delay |
Tap 5 | Max ‡ | 0 sec off delay |
† electric heat airflow is same CFM as Tap 3, except 0 sec off delay
‡ high static applications, see airflow tables for max airflow
To change motor speeds disconnect the BLUE fan lead from motor connector
terminal #2 (factory default position) and move to desired speed-tap; 1, 2, 3,
or 5.
Speed-taps 1, 2, and 3 have a 90 second blower off time delay pre-programmed
into the motor. Speed-tap 4 is used for electric heat only (with 0 second
blower time delay) and the WHITE wire should remain on tap 4. Speed-tap 5 is
used for high static applications, but has a 0 second blower time delay pre-
programmed into the motor. See Airflow Performance tables for actual CFM.
Also, see Fig. 16 for motor speed selection location.
NOTE: In low static applications, lower motor speed tap should be used to
reduce possibility of water being blown off coil.
CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
A brazing shield MUST be used when tubing sets are being brazed to the unit
connections to prevent damage to the unit surface and condensate pan fitting
caps.
REFRIGERANT TUBING CONNECTION AND EVACUATION
Use accessory tubing package or field-supplied tubing of refrigerant grade.
Suction tube must be insulated. Do not use damaged, dirty, or contaminated
tubing because it may plug refrigerant flow-control device. ALWAYS evacuate
the coil and field-supplied tubing to 500 microns before opening outdoor unit
service valves.
Units have sweat suction and liquid tube connections. Make suction tube
connection first.
-
Cut tubing to correct length.
-
Insert tube into sweat connection on unit until it bottoms.
-
Braze connection using silver bearing or non-silver bearing brazing materials. Do not use solder (materials which melt below 800_F / 427_C). Consult local code equirements.
-
Evacuate coil and tubing system to 500 microns using deep vacuum method.
CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Wrap a wet cloth around rear of fitting to prevent damage to TXV and factory-
made joints.
REFRIGERANT FLOW-CONTROL DEVICE
The FX4D is equipped with PuronR refrigerant TXV. Use outdoor units designed
for PuronR refrigerant only.
CAUTION
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation.
If using a TXV in conjunction with a single-phase reciprocating compressor, a
compressor start capacitor and relay are required. Consult outdoor unit pre-
sale literature for start assist kit part number.
CONDENSATE DRAINS
To connect drains, the cap openings must be removed. Use a knife to start the
opening near the tab and using pliers, pull the tab to remove the disk. Clean
the edge of the opening if necessary and install the condensate line. Finally
caulk around the lines where they exit the fitting to retain the low leak
rating of the unit.
Units are equipped with primary and secondary 3/4-in. FPT drain connections.
For proper condensate line installations see Fig. 1, 3, 4, 5 and 6. To prevent
property damage and achieve optimum drainage performance, BOTH primary and
secondary drain lines should be installed and include properly-sized
condensate traps. (See Fig. 17 and 19.) Factory-approved condensate traps are
available. It is recommended that PVC fittings be used on the plastic
condensate pan. Finger-tighten plus 1-1/2 turns. Do not over- tighten. Use
pipe dope.
NOTE: When connecting condensate drain lines, avoid blocking filter
access panel, thus preventing filter removal. After connection, prime both
primary and secondary condensate traps.
WARNING
PRODUCT OR PROPERTY DAMAGE HAZARD
Failure to follow this warning caution may result in product or property
damage.
The conversion of the fan coil to downflow requires special procedures for the
condensate drains on both A-coil and Slope-coil units. The vertical drains
have an overflow hole between the primary and secondary drain holes. This hole
is plugged for all applications except downflow, and must be used for
downflow. During conversion process, remove plastic cap covering vertical
drains only and discard. Remove plug from overflow hole and discard. At
completion of downflow installation, caulk around vertical pan fitting to door
joint to retain low air leak performance of the unit.
|
---|---
NOTE: If unit is located in or above a living space where damage may
result from condensate overflow, a field-supplied, external condensate pan
should be installed underneath the entire unit, and a secondary condensate
line (with appropriate trap) should be run from the unit into the pan. Any
condensate in this external condensate pan should be drained to a noticeable
place. As an alternative to using an external condensate pan, some localities
may allow the use of a separate 3/4-in (19 mm) condensate line (with
appropriate trap) to a place where the condensate will be noticeable. The
owner of the structure must be informed that when condensate flows from the
secondary drain or external condensate pan, the unit requires servicing or
water damage will occur.
Install traps in the condensate lines as close to the coil as possible. (See
Fig. 19.) Make sure that the outlet of each trap is below its connection to
the condensate pan to prevent condensate from overflowing the drain pan. Prime
all traps, test for leaks, and insulate traps if located above a living area.
Condensate drain lines should be pitched downward at a minimum slope of 1-in
(25 mm) for every 10-ft (3 m) of length. Consult local codes for additional
restrictions or precautions.
CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Use only full size P-traps in the condensate line (refer to Fig. 17).
Shallow running traps are inadequate and DO NOT allow proper condensate
drainage (refer to Fig. 18).
ACCESSORIES
HUMIDIFIER
Connect humidifier and humidistat to fan coil unit as shown in Fig. 20 and
Fig. 21. The cooling lockout relay is optional.
SEQUENCE OF OPERATION
CONTINOUS FAN
Thermostat closes R to G. G energizes fan relay on PCB which completes circuit
to indoor blower motor. When G is de-energized, there is a 90 second delay
before relay opens.
NOTE: Speed taps 1, 2 and 3 have a 90 second blower off delay. Speed taps
4 and 5 have 0 second blower off delay.
COOLING MODE
Thermostat energizes R to G, R to Y, and R to O (heat pump only). Genergizes
fan relay on PCB which completes circuit to indoor blower motor. When G is de-
energized, there is a 90 second delay before fan relay opens.
NOTE: Speed taps 1, 2 and 3 have a 90 second blower off delay. Speed taps
4 and 5 have 0 second blower off delay.
HEAT PUMP HEATING WITH AUXILIARY ELECTRIC HEAT
Thermostat energizes R to G, R to Y, and R to W. G energizes fan relay on PCB
which completes circuit to indoor blower motor. W energizes electric heat
relay(s) which completes circuit to heater element(s). When W is de-energized,
electric heat relay(s) open, turning off heater elements. When G is de-
energized there is a 90 second delay before fan relay opens.
NOTE: Speed taps 1, 2 and 3 have a 90 second blower off delay. Speed taps
4 and 5 have 0 second blower off delay.
ELECTRIC HEAT OR EMERGENCY HEAT MODE
Thermostat closes R to W. W energizes electric heat relay(s) which completes
circuit to heater element(s). Blower motor is energized through normally
closed contacts on fan relay. When W is de-energized, electric heat relay(s)
opens.
START-UP PROCEDURES
Refer to outdoor unit Installation Instructions for system start-up
instructions and refrigerant charging method details.
CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor unit performance and/or
product damage.
Never operate unit without a filter. Factory authorized filter kits may be
used when locating the filter inside the unit. For those applications where
access to an internal filter is impractical, a field-supplied filter must be
installed in the return air duct system.
CARE AND MAINTENANCE
To continue high performance and minimize possible equipment failure, it is
essential that periodic maintenance be performed on this equipment. Consult
your local dealer as to the proper frequency of maintenance contract.
The ability to properly perform maintenance on this equipment requires certain
mechanical skills and tools. If you do not possess these, contact your dealer
for maintenance. The only consumer service recommended or required is filter
replacement or cleaning on a monthly basis.
Table 2 – Air Delivery Performance Correction Component Pressure Drop (in.
wc) at Indicated Airflow (Dry to Wet Coil)
F X Size
| CFM
---|---
5 0 0| 6 0 0| 7 0 0| 8 0
0| 9 0 0| 1 0 0 0| 1 1 0 0|
12 0 0| 1 30 0| 1 4 0 0| 1
5 0 0| 1 6 0 0| 1 7 0 0| 1
8 0 0| 1 9 0 0|
2 0 0 0
0 1 9| 0.034| 0.049| 0.063| —| —| —| —| —| —| —| —| —| —| —| —|
—
0 2 5| 0.016| 0.027| 0.038| 0.049| 0.059| —| —| —| —| —| —| —|
—| —| —| —
0 3 1| —| —| —| 0.049| 0.059| 0.070| 0.080| —| —| —| —| —| —| —|
—| —
0 3 7| —| —| —| —| —| 0.055| 0.064| 0.073| 0.081| —| —| —| —| —|
—| —
0 4 3| —| —| —| —| —| —| —| 0.049| 0.056| 0.063| 0.070| —| —| —|
—| —
0 4 9| —| —| —| —| —| —| —| —| —| 0.038| 0.043| 0.049| 0.054|
0.059| —| —
0 6 1| —| —| —| —| —| —| —| —| —| —| —| 0.027| 0.031| 0.035|
0.039| 0.043
Table 3 – Factory-Installed Filter Static Pressure Drop (in. wc)
F X SIZE
| CFM
---|---
4 0 0| 6 0 0| 8 0 0| 1 0 0
0| 1 2 0 0| 1 4 0 0| 1 6 0
0| 1 8 0 0|
2 0 0 0
0 1 9| 0.020| 0.044| 0.075| –| –| –| –| –| –
0 2 5 – 031| –| 0.022| 0.048| 0.072| 0.100| –| –| –| –
0 3 7 -049| –| –| –| 0.051| 0.070| 0.092| 0.120| 0.152| –
0 6 1| –| –| –| –| –| –| 0.086| 0.105| 0.130
Table 4 – Electric Heater Static Pressure Drop (in. wc)
F X
0 1 9 – 037
|
F X
0 4 3 – 061
---|---
HEATER ELEMENTS
| k W| EX T E RNAL STATIC PRESSURE CORRECTION|
HEATER ELEMENTS| k W| E X T E RNAL STATIC
PRESSURE CORRECTION
0| 0| +.02| 0| 0|
+.04
1
| 3, 5| +.01| 2| 8, 10| +.02
2| 8, 10| 0| 3| 9, 15|
0
3
| 9, 15| –.02| 4| 20| –.02
4| 20| –.04| 6| 18, 24, 30|
–.10
Table 5 – Airflow Performance (CFM) in Cooling Mode
M o d e l & Size
| Blower Speed| EX T E RNAL STATIC (in. wc)
---|---|---
0 . 1 0| 0 . 2 0| 0 . 3 0|
0 . 4 0| 0 . 5 0|
0 . 6 0
F X 4 D 019| Tap 5| 776| 745| 696| 660| 609| 572
Tap 4| 683| 644| 589| 548| 494| 461
Tap 3| 683| 644| 589| 548| 494| 461
Tap 2| 631| 563| 500| 443| 409| 361
Tap 1| 625| 524| 457| 417| 367| 319
F X 4 D 025| Tap 5| 956| 920| 891| 851| 816| 780
Tap 4| 825| 795| 757| 722| 674| 634
Tap 3| 825| 795| 757| 722| 674| 634
Tap 2| 726| 695| 635| 598| 543| 509
Tap 1| 631| 563| 500| 443| 409| 361
F X 4 D 031| Tap 5| 1189| 1151| 1104| 1050| 1003| 959
Tap 4| 1041| 998| 944| 886| 837| 772
Tap 3| 1041| 998| 944| 886| 837| 772
Tap 2| 924| 876| 817| 752| 704| 660
Tap 1| 779| 693| 628| 571| 526| 476
F X 4 D 037| Tap 5| 1363| 1332| 1294| 1253| 1207| 1157
Tap 4| 1237| 1206| 1160| 1121| 1070| 1013
Tap 3| 1237| 1206| 1160| 1121| 1070| 1013
Tap 2| 1095| 1058| 1007| 951| 888| 824
Tap 1| 1014| 885| 773| 673| 609| 549
F X 4 D 043| Tap 5| 1519| 1490| 1454| 1419| 1379| 1332
Tap 4| 1437| 1403| 1366| 1333| 1294| 1245
Tap 3| 1437| 1403| 1366| 1333| 1294| 1245
Tap 2| 1257| 1226| 1191| 1141| 1090| 1033
Tap 1| 1237| 1206| 1160| 1121| 1070| 1013
F X 4 D 049| Tap 5| 1757| 1725| 1693| 1653| 1614| 1576
Tap 4| 1664| 1626| 1593| 1552| 1517| 1477
Tap 3| 1664| 1626| 1593| 1552| 1517| 1477
Tap 2| 1459| 1420| 1379| 1336| 1298| 1259
Tap 1| 1301| 1241| 1195| 1150| 1102| 1039
F X 4 D 061| Tap 5| 2030| 1995| 1961| 1927| 1888| 1842
Tap 4| 1811| 1775| 1740| 1703| 1664| 1613
Tap 3| 1811| 1775| 1740| 1703| 1664| 1613
Tap 2| 1665| 1632| 1593| 1556| 1507| 1453
Tap 1| 1462| 1418| 1371| 1327| 1278| 1228
– Shading – Airflow outside 450 cfm/ton.
NOTES:
-
Airflow based upon dry coil at 230v with factory approved filter and electric heater (2 element heater sizes 019 through 037, 3 element heater sizes 043 through 061).
-
Airflow at 208 volts is approximately the same as 230 volts because the multi-tap ECM motor is a constant torque motor. The torque doesn’t drop off at the speeds the motor operates.
-
To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 043 – 061 sizes must have supply static greater than 0.20 in. wc. -
Airflow above 400 cfm/ton on 049 – 061 size could result in condensate blowing off coil or splashing out of drain pan.
© 2022 Carrier. All rights reserved.
A Carrier Company
Edition Date: 10/22
Catalog No: IM-FX4D-04
Replaces: IM-FX4D-03
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations.
Documents / Resources
|
BEHLER-YOUNG FX4D Fan
Coils
[pdf] Instruction Manual
FX4D Fan Coils, FX4D, Fan Coils, Coils
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>