BEHLER-YOUNG 348719-701 Muffler Kit Instruction Manual
- June 4, 2024
- BEHLER-YOUNG
Table of Contents
348719-701 Muffler Kit
Instruction Manual
348719-701 Muffler Kit
For Use on 24/26VS 5 Ton Heat Pump Units Only (models 25VNA460/284ANV060)
INSTALLATION INSTRUCTIONS
NOTE: Read the entire instruction manual before starting the installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use
can cause an explosion, fire, electrical shock, or other conditions which may
cause death, personal injury, or property damage. Consult a qualified
installer, service agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factory-authorized kits
or accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work
gloves. Use a quenching cloth for brazing operations. Have a fire extinguisher
available. Read these instructions thoroughly and follow all warnings or
cautions included in the literature and attached to the unit. Consult local
building codes and current editions of the National Electrical Code ( NEC )
NFPA 70. In Canada, refer to current editions of the Canadian electrical code
CSA 22.1. Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or manuals, be alert
to the potential for personal injury. Understand these signal words;
DANGER, WARNING, and CAUTION. These words are used with the safety
alert symbol.
DANGER identifies the most serious hazards which will result in severe
personal injury or death.
WARNING signifies hazards that could result in personal injury or death.
CAUTION is used to identify unsafe practices which would result in minor
personal injury or product and property damage.
NOTE is used to highlight suggestions that will result in enhanced
installation, reliability, or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing the system, the main electrical
disconnect switch must be in the OFF position. There may be more than 1
disconnect switch. Lock out and tag the switch with a suitable warning label.
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment
damage. Systems containing R-410A refrigerant operate at higher pressures than
systems containing R-22 refrigerant. Do not use R-22 refrigerant service
equipment or components on systems containing R-410A.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final
unit disposal. Use all service ports and open all flow-control devices,
including solenoid valves. Federal regulations require that you do not vent
refrigerant to the atmosphere. Recover during system repair or final unit
disposal.
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal
parts may have sharp edges or burrs. Use care and wear appropriate protective
clothing and gloves when handling parts.
INTRODUCTION
This instruction covers the installation of a Suction Muffler Kit designed to
mitigate a “whistle” sound caused by the excessive refrigerant gas pulsations
Refer to Table 1 for kit contents..
This kit is designed for use on 24/26VS 5 Ton Heat Pump units only (Model no.
25VNA460/284ANV060). A221130
Fig. 1 – Muffler Kit
Table 1 – Kit Contents
PART DESCRIPTION | QTY INCLUDED IN KIT |
---|---|
348562-401 Suction Tube | 1 |
348717-401 Adapter Tube | 1 |
LM10KK003 Suction Muffler | 1 |
345265-701 Pressure Transducer Assembly | 1 |
348719-701 Muffler Kit: INSTALLATION INSTRUCTIONS
INSTALLATION
Step 1 – KIT PRE-ASSEMBLY
The following pre-assembly steps must be taken prior to installing the kit in
the unit.
1. Braze the short leg of the Suction Tube to the Suction MufflerA221131
Fig. 2 – Braze Suction Tube to Suction Muffler
2. Remove the wire harness from the Pressure Transducer.
3. Braze the Pressure Transducer into the orifice in the top of the Suction
Tube.
NOTE: Facing the Control Panel corner, remove the front Top Cover screws
(at least 6) to allow it to tilt upward enough to clear the Control
Panel.
Fig. 3 – Top Cover Screw Locations
Fig. 4 –
Braze Pressure Transducer
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Components must be wrapped in a heat-sinking material such as a wet cloth
while brazing.
4. OPTIONAL: If a 3/4″ to 7/8″ swage tool is not available, Braze the
included Adapter Tube to the Suction Muffler. Ensure the large side of the
Adapter Tube (7/8″) is inserted into the muffler (see Fig. 4). A221159
Fig. 5 – Orientation of Adapter Tube in Muffler
Step 2 – KIT INSTALLATION
1. Remove power from the unit before following these instructions.
2. Pump system down and recover refrigerant
3. Completely remove the Control Panel and place it to one side. Leave the
wires attached.
4. Cut the wire tie on the Suction Tube.A221143
Fig. 6 – Cut wire Tie on suction Tube
5. Remove the Temperature Sensor form the Suction Tube
6. Remove the Wire Harness from the Pressure Transducer.
A221133a
Fig. 7 – Temperature Sensor and Wire Harness Location
7. Mark for cutting
a. If a 3/4″ to 7/8″ swage tool is available, measure from the Suction
Charging Port (small capillary tube) 11 1/4″ up the tube and make a mark for
cutting.
A221200
Fig. 8 – Swage Tool Available – Mark for Cutting
b. If a 3/4″ to 7/8″ swage tool is not available, measure from the Suction
Charging Port (small capillary tube) 9″ up the tube and make a mark for
cutting. A221201
Fig. 9 – Swage Tool Not Available – Mark for Cutting
8. Cut the Suction Tube at the marked line using a tube cutter. A221134
Fig. 10 – Cut Suction Tube at Marked Line
9. Unbraze the other side of the Suction Tube from the top of the
Accumulator, and remove the piece of tube.
A221135
Fig. 11 – Unbraze Suction Tube from Top of Accumulator
10. Bell the exposed Suction Tube out using a 3/4″ to 7/8″ swage tool.
OPTIONAL: If a swage tool is not available and the Adapter Tube is used, skip
this step.11. Braze in the new Muffler Kit assembly. One brazes joint
connects the Suction Muffler to the belled-out Suction Tube, and the other
connects the new tube to the top of the Accumulator.
A221137
Fig. 13 – Braze Joint Locations
12. Replace the Temperature Sensor on the Suction Tube below the muffler.
13. Reconnect the wire harness to the pressure transducer. Fig.
14 – Temperature Sensor and Wire Harness Location
14. Use a new wire tie to secure the wires to the Suction Tube below the
installed Muffler Kit.
Fig. 15 – Secure Wires to Suction Tube with Wire Tie
15. Reinstall the unit control panel.
16. Evacuate and charge unit per Installation Instructions provided with the
unit.
The manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations.
© 2022 Carrier. All rights reserved.
A Carrier Company
Edition Date: 07/22
Catalog No: IIK-348719-01
Replaces: New