DALI Sensor Coupler E
Luminaire Integrated DALI Coupler

GETTING STARTED

OVERVIEW
The DALI Sensor Coupler E allows integration of external third-party light and presence sensors into the Encelium X System. The DALI Sensor Coupler E enables each sensor to be independently configured to best meet the needs of the facility. For more information on product specifications and design tools visit encelium.com.

PRODUCT SAFETY

READ THESE INSTRUCTIONS BEFORE USING THE PRODUCT
When using electrical equipment, basic safety precautions should always be followed, including the following:

  • Do not mount near gas or electric heaters or let power supply cords touch hot surfaces.
  • Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
  • The use of accessory equipment is not recommended by Encelium as it may cause an unsafe condition.
  • All DALI channels are internally connected together to the control unit. Make sure to consider this when installing.
  • Do not use this equipment for other than the intended use.

SAVE THESE INSTRUCTIONS.

WIRED SYSTEM OVERVIEW

ENCELIUM-DALI-Sensor-Coupler-E-Luminaire-Integrated-
fig-1

Encelium X enables you to control DALI devices. With any Encelium wired design, you get a reliable, lighting control system that can be installed quickly and easily.

STEP 1ENCELIUM-DALI-Sensor-Coupler-E-Luminaire-Integrated-
fig-2

The DALI Sensor Coupler E is intended for luminaire integration and requires direct connection to third-party sensors. Secure the DALI Sensor Coupler E to the luminaire using screws (not included). The DALI Sensor Coupler E is to be installed in dry, indoor locations ONLY. Recommended input voltage is 220 to 240 V, 50/60 Hz. Maximum of 300 m (984 ft) total wire length for DALI and third-party sensor interface.
Note: Once the DALI Sensor Coupler E is connected to power, press the SELECT button to switch on the LED Indicator. Another short press to the SELECT button will switch off the LED Indicator, otherwise the LED Indicator will switch off after 30 seconds.

STEP 2
INDEPENDENT CEILING INTEGRATION (OPTIONAL)ENCELIUM-DALI-Sensor-Coupler-E
-Luminaire-Integrated-fig-3

Independent Ceiling Integration is possible with installation of the ECO CI KIT (ordered separately), a strain relief housing kit. The DALI Sensor Coupler E requires the installation of an ECO CI KIT to ensure protection from electrical contact. The DALI Sensor Coupler E is to be installed in dry, indoor locations ONLY. Recommended input voltage is 220 to 240 V, 50/60 Hz. Maximum of 300 m (984 ft) total wire length for DALI and third-party sensor interface.
Note : Once the DALI Sensor Coupler E is connected to power, press the SELECT button to switch on the LED Indicator. Another short press to the SELECT button will switch off the LED Indicator, otherwise the LED Indicator will switch off after 30 seconds.

STEP 3ENCELIUM-DALI-Sensor-Coupler-E-Luminaire-Integrated-
fig-4

Remove cable guards from the ECO CI KIT bases and place ECO CI KIT bases onto the DALI Sensor Coupler E. Push the center of the cable guard down and bend, enabling the cable guard to wrap around the cable.

STEP 4 |ENCELIUM-DALI-Sensor-Coupler-E-Luminaire-Integrated-
fig-5

Install the cable guards on the LINE IN, DALI, and THIRD-PARTY SENSOR cables then connect the wires into the DALI Sensor Coupler E ports. Place the ECO CI KIT covers onto the DALI Sensor Coupler E and tighten the screws.

STEP 5
FLOATING CONTACT ELECTRICAL CONNECTIONENCELIUM-DALI-Sensor-Coupler-E
-Luminaire-Integrated-fig-6
Integration of external third-party motion detector with floating contact.

STEP6
SWITCHED MAINS ELECTRICAL CONNECTIONENCELIUM-DALI-Sensor-Coupler-E
-Luminaire-Integrated-fig-7

Integration of external third-party motion detector with switched mains.

FEATURES

The DALI Sensor Coupler E features a SELECT Button and LED Indicator. The SELECT Button enables you to identify a device and reset to factory default settings. The different colors of the LED Indicator indicate motion has been detected and what operating mode has been selected (see the DALI Sensor Coupler E LED Indicator details below).

DALI Sensor Coupler E LED Indicator Lights

  • Green LED Indicator Flashes: Indicates motion detection.
  • Red LED Indicator: Indicates a user has entered OSRAM proprietary mode.

FACTORY DEFAULT SETTINGS

ENCELIUM-DALI-Sensor-Coupler-E-Luminaire-Integrated-
fig-9With the power connected, press and hold the SELECT button for about 10 seconds until the LED Indicator blinks red for 4 seconds. The DALI Sensor Coupler E is reset to the factory default settings.
Note: Resetting to factory default settings will delete the DALI short address and require the device to be re-commissioned.

VISIT OUR HELP CENTER

For instructions to install, configure, test, or use Encelium products or systems, or to contact an Encelium Technical Support Specialist, please scan the QR code or visit help.encelium.com.

Copyright © 2022 Digital Lumens, Incorporated. All rights reserved. Digital Lumens, the Digital Lumens logo, We Generate Facility Wellness, SiteWorx, LightRules, Lightelligence, Encelium, the Encelium logo, Polaris, GreenBus and any other trademark, service mark, or tradename (collectively “the Marks”) are either trademarks or registered trademarks of Digital Lumens, Inc. in the United States and/or other countries, or remain the property of their respective owners that have granted Digital Lumens, Inc. the right and license to use such Marks and/or are used herein as nominative fair use. Due to continuous improvements and innovations, specifications may change without notice.
DOC-000456-00 Rev A 11-22