OVERVIEW

The DALI LS PD CI is light and presence sensor that is designed for quick and easy installation into a suspended (drop) ceiling. The DALI LS PD CI communicates to the Encelium Wired Manager — DALI via directly connect DALI bus. For more information on product specifications and design tools visit encelium.com.

PRODUCT SAFETY

READ THESE INSTRUCTIONS BEFORE USING THE PRODUCT
When using electrical equipment, basic safety precautions should always be followed, including the following:

  • Do not mount near gas or electric heaters or let power supply cords touch hot surfaces.
  • Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
  • The use of accessory equipment is not recommended by Encelium as it may cause an unsafe condition.
  • All DALI channels are internally connected together to the control unit. Make sure to consider this when installing.
  • Do not use this equipment for other than the intended use.

WIRED SYSTEM OVERVIEW

ENCELIUM-DALI-LS-PD-CI-Suspended-Ceiling-Integration-
FIG-1

Encelium X enables you to control DALI devices. With any Encelium wired design, you get a reliable, lighting control system that can be installed quickly and easily.

STEP 1
SUSPENDED CEILING INTEGRATIONENCELIUM-DALI-LS-PD-CI-Suspended-Ceiling-
Integration-FIG-2 Cut a Ø 68 mm (2.7 inches) hole in the ceiling. Connect the sensor cable to the DALI Line. The DALI LS PD CI is supplied from DALI Voltage as per DALI standard EN 62386. Power consumption approximately 6 mA. Position the mounting brackets up and push the DALI LS PD CI through the hole. The mounting brackets will snap down onto the ceiling tile, securing the DALI LS PD CI into place.

WIRING MULTIPLE DALI LS PD CIs

If multiple DALI LS PD CIs are used see how to connect them to the Wired Manager — DALI above.

FEATURES

DALI LS PD CI features an Occupancy and Light Sensors, SELECT Button , and LED Indicator. The SELECT Button enables you to identify a device and reset to factory default settings. The LED Indicator displays green or red lights (see the DALI LS PD CI LED Indicator details below).

DALI LS PD CI LED Indicator Lights

  • Green LED Indicator Flashes: Motion is detected.
  • Green LED Indicator Illuminates Continuously: Motion detection is temporarily deactivated.
  • Red LED Indicator Flashes 3 Times: IR Signal of remote control has been received.
  • Red LED Indicator Flashes 1 Time: Vibration has been detected.
  • Red LED Indicator Illuminates Continuously: 100h burn-in is active.

FACTORY DEFAULT SETTINGS

With the power connected to the DALI LS PD CI, press and hold the SELECT Button for about 10 seconds until the LED Indicator blinks red for 4 seconds. The DALI LS PD CI is then reset to the factory default settings.
Note: Resetting to factory default settings will delete the DALI short address and require the device to be re-commissioned.

ADJUSTING THE SENSOR SHUTTER

Using a small screwdriver pull up on the shutter sides. Remove, insert, or rotate one or both shutters where necessary.

SENSOR DETECTION RANGE

ENCELIUM-DALI-LS-PD-CI-Suspended-Ceiling-Integration-
FIG-7

The detection range of the DALI LS PD CI sensor is determined by the shutter position.ENCELIUM-DALI-LS-PD-CI-Suspended-Ceiling-Integration-
FIG-8By changing the shutter position, you can influence the detection range of the sensor directionally and avoid undesired presence detection.

VISIT OUR HELP CENTER For instructions to install, configure, test, or use Encelium products or systems, or to contact an Encelium Technical Support Specialist, please scan the QR code or visit help.encelium.com.

Copyright © 2022 Digital Lumens, Incorporated. All rights reserved. Digital Lumens, the Digital Lumens logo, We Generate Facility Wellness, SiteWorx, LightRules, Lightelligence, Encelium, the Encelium logo, Polaris, GreenBus and any other trademark, service mark, or tradename (collectively “the Marks”) are either trademarks or registered trademarks of Digital Lumens, Inc. in the United States and/or other countries, or remain the property of their respective owners that have granted Digital Lumens, Inc. the right and license to use such Marks and/or are used herein as nominative fair use. Due to continuous improvements and innovations, specifications may change without notice.
DOC-000457-00 Rev A 11-22

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ENCELIUM User Manuals

Related Manuals