artsound MAT-8000 Venue Mixer Instruction Manual

June 9, 2024
ArtSound

Operating Manual
MAT-8000
VENUE MIxER

MAT-8000 Venue Mixer

Please follow the instructions in this manual to obtain the optimum results from this unit.
We also recommend that you keep this manual handy for future reference Check our website for any updates of this manual: www.artsound.be

House of Music NV
Ronse, Belgium
www.artsound.be
Tel. +32 9 380 81 80
Fax. +32 9 386 12 35
[email protected]

Safety precautions.

  • Be sure to read the instructions in this section carefully before use.
  • Make sure to observe the instructions in this manual as the conventions of safety symbols and messages regarded as very important precautions are included.
  • We also recommend you keep this instruction manual handy for future reference.

Warnings and safety.
Safety Symbol and Message Conventions.
Safety symbols and messages described below are used in this manual to prevent bodily injury and property damage, which could result from  mishandling. Before operating your product, read this manual first and understand the safety symbols and messages so you are thoroughly aware of  the potential safety risk.

WARNIN
Indicates a potentially hazardous situation which, if mishandled, could result in death or serious personal injury.
CAUTION
Indicates a potentially hazardous situation which, if mishandled, could result in moderate or minor personal injury, and/or property damage.

Warning.
When Installing the Unit.

  • Do not expose the unit to rain or an environment where it may be splashed by water or other liquids, as doing so may result in fire or electric  shock.
  • Use the unit only with the voltage specified on the unit. Using a voltage higher than that which is specified may result in fire or electric shock.
  • Do not cut, kink, otherwise damage nor modify the power supply cord. In addition, avoid using the power cord in close proximity to heaters,  and never place heavy objects — including the unit itself — on the power cord, as doing so may result in fire or electric shock.
  • Be sure to replace the unit’s terminal cover after connection completion. Because high voltage is applied to the speaker terminals, never touch  these terminals to avoid electric shock.
  • Be sure to ground to the safety ground (earth) terminal to avoid electric shock. Never ground to a gas pipe as a catastrophic disaster may result.
  • Avoid installing or mounting the unit in unstable locations, such as on a rickety table or a slanted surface. Doing so may result in the unit falling down, causing personal injury and/or property damage.

When the Unit is in Use.

  • Should the following irregularity be found during use, immediately switch off the power, disconnect the power supply plug from the AC outlet  and contact your nearest ArtSound dealer. Make no further attempt to operate the unit in this condition as this may cause fire or electric shock. • If you detect smoke or a strange smell coming from the unit.
    • If water or any metallic object gets int o the unit
    • If the unit falls, or the unit case breaks
    • If the power supply cord is damaged (exposure of the core, disconnection, etc. )
    • If it is malfunctioning (no tone sounds.)

  • To prevent a fire or electric shock, never open nor remove the unit case as there are high voltage components inside the unit. Refer all servicing to your nearest ArtSound dealer.

  • Do not place cups, bowls, or other containers of liquid or metallic objects on top of the unit. If they accidentally spill into the unit, this may  cause a fire or electric shock.

  • Do not insert nor drop metallic objects or flammable materials in the ventilation slots of the unit’s cover, as this may result in fire or electric  shock.

Caution.
When Installing the Unit.

  • Never plug in nor remove the power supply plug with wet hands, as doing so may cause electric shock.
  • When unplugging the power supply cord, be sure to grasp the power supply plug; never pull on the cord itself. Operating the unit with a   damaged power supply cord may cause a fire or electric shock.
  • When moving the unit, be sure to remove its power supply cord from the wall outlet. Moving the unit with the power cord connected to the  outlet may cause damage to the power cord, resulting in fire or electric shock. When removing the power cord, be sure to hold its plug to pull.
  • Do not block the ventilation slots in the unit’s cover. Doing so may cause heat to build up inside the unit and result in fire.
  • Avoid installing the unit in humid or dusty locations, in locations exposed to the direct sunlight, near the heaters, or in locations generating sooty smoke or steam as doing otherwise may result in fire or electric shock.

When the Unit is in Use.

  • Do not place heavy objects on the unit as this may cause it to fall or break which may result in personal injury and/or property damage. In  addition, the object itself may fall off and cause injury and/or damage.
  • Make sure that the volume control is set to minimum position before power is switched on.
  • Loud noise produced at high volume when power is switched on can impair hearing.
  • Do not operate the unit for an extended period of time with the sound distorting. This is an indication of a malfunction, which in turn can  cause heat to generate and result in a fire.
  • Contact your ArtSound dealer as to the cleaning. If dust is allowed to accumulate in the unit over a long period of time, a fire or damage to the  unit may result.
  • If dust accumulates on the power supply plug or in the wall AC outlet, a fire may result. Clean it periodically. In addition, insert the plug in the  wall outlet securely.
  • Switch off the power, and unplug the power supply plug from the AC outlet for safety purposes when cleaning or leaving the unit unused for  10 days or more. Doing otherwise may cause a fire or electric shock.

An all-pole mains switch with a contact separation of at least 3 mm in each pole shall be incorporated in the electrical installation of the building.

Introduction.

The MAT-8000 is an 8 channel model which is cater for multi-zone, paging and multi-sources selection system.
It is a complete solution for multi-zone, multi-functional venues like entertainment places, large hotels, sport or gym centers, shopping malls, etc.
MAT-8000 offers direct connection of up 8 music source inputs ,8 remote control panels, 4 remote paging consoles and one microphone input,all of these inputs can be freely allocated into different 8 zone outputs simultaneously.

Front panel layout.

1. Select Source
2. Zone LED Display
3. Monitor Zone Select
4. Page Busy
5. MIC Priority Indicator
6. MIC Priority Button
7. Music Volume
8. Master Volume| 9. MIC Volume
10. Monitor LED Display
11. Monitor Zone Output Level
12. Monitor Volume
13. ESC
14. ENTER
15. BGM ALL
16. Page ALL
---|---

1. SOURCE SELECT
The source select button (1) is used to select the source for the zone. Each zone has a separate source selection button. There are 9 selectable  sources: Line sources 1 through 8 and a local Microphone source. A different local source (remote in wall mixer or source select/volume control)  can be connected to each zone. A zone cannot select the local source connected to another zone. Pressing the source select button will cycle  through all zones in sequence:1, 2, 3, 4, 5, 6,7, 8, L and OFF. To select a required source, press the source select button (1). Once the display shows  the desired source, press in sequence:1, 2, 3, 4, 5, 6,7, 8, L,and OFF. To select a required source, press the source select button and the ENTER (14) button to confirm the change to the selected source.

Note:
The source will only change after the ENTER (14) button is pressed. If the ENTER(14) button is not pressed, the source selection will return to  previous setting after 10 seconds. When the system is used in conjunction with remote control panels, the zone source select button will be disabled when a remote control panel is connected to a zone. In this situation the source selection can only be controlled via the remote control panel. If the event power is lost, the last source selection settings are automatically saved and the unit will return to its previously configured source selections when powered back on.

2. ZONE LED DISPLAY
The Single Digit Zone LED Display will display the selected source number: lines 1-8 and local input shown as L.

3. PAGE BUSY
The Zone Page Busy indicator LED (3) will illuminate amber to indicate a paging microphone is paging to this zone.

4. MIC1 PRIORITY INDICATOR
The MIC1 Priority Indicator LED (4) will illuminate blue indicating the Zone MIC1 priority paging function is enabled.

5. MIC1 PRIORITY BUTTON
The MIC1 Priority button (5) will enable/disable the MIC1 priority paging function. When enabled MIC1 will override zones 1-8 and all local inputs, if a signal is present on the MIC1 input. When disabled, MIC1 will mix with lines 1-8 and local inputs if required. This Microphone input has been designed to give global priority over all other inputs if enabled via the front panel. The MIC1 priority setting is not saved when the MAT-8000  is switched off, and will return to its default state on powered back on. The default state of the MIC1 Priority is disabled.

6. MUSIC VOLUME
The Music Volume control knob (6) controls the selected source (zones 1-8 and local input) input level. If the system is used with Remote Control  Panels, the Music Volume knob will be disabled Source Music Volume level will be controlled at the remote control panel only. for zones where a remote control panel is connected.

7. MASTER VOLUME
The Master Volume control knob (7) will control the combined MIC1 and Source Output Volume Level, if the MIC1 input has been enabled for a zone. The Master Volume control knob will not control the Paging Console Public Address Volume Level,or the Line 8 Source Input Volume Level when the Line 8 Source Input Priority Function is enabled. This function has been designed as a global BGM input if required.

8. MIC1 VOLUME
The MIC1 Volume control knob (8) will control the MIC1 input level if this global mic has been configured to operate within the zone.

9. MONITOR ZONE SELECT
The ZONE SELECT button (9) is used to select one of the 8 zones to be monitored. Pressing the zone select button will cycle through all zones in sequence as follows: 1, 2, 3, 4, 5, 6, 7, 8, and OFF. A zone can be selected pressing the ZONE SELECT button. Once the display shows the desired zone, press the ENTER button to confirm and change to the selected zone.

Note:
The zone will only change after the ENTER button is pressed, otherwise the source selection will be returned to its previous setting after 10  seconds. The monitor zone function enables the audio output from a zone to be monitored through a small speaker on the front panel. This is  particularly useful when controlling the audio in a remote zone or testing the system.

10. MONITOR ZONE LED DISPLAY
The Single Digit Monitor Zone LED Display (10) will display the selected zone numbers,1-8.

11. MONITOR ZONE OUTPUT LEVEL
The 5 LED Monitor Zone Output Level Meter (11) will provide visual indication of the audio signal level for a selected zone.

12. MONITOR VOLUME
The Monitor Volume control knob (12) will control the in-built Monitor Speaker volume level.

13 ESC
The ESC button (13) is used to cancel the selection of source select,monitor zone select and BGM function buttons.

14. ENTER
The ENTER button (14) is used to confirm selection of source select,monitor zone select and BGM function buttons.

15. BGM ALL
The BGM ALL button (15) is used to select the same source for all 8 zones simultaneously. To confirm the BGM ALL selection,press ENTER.

Note:
The BGM ALL selection will only be confirmed after the ENTER button is pressed ,otherwise the source selection will be return to previous  setting after 10 seconds. In the event power is lost, the BGM ALL selection settings will be saved and the unit will return to the previous BGM ALL setting when powered back on.

Rear panel layout.

1 Dip Switches
2 EVAC / Fire System Interface
3 Tone Output
4 EMC Input
5 Extension Link
6 Remote Source
7 Remote Control Input
8 Page| 9 LF Bass
10 Output
11 Gain
12 HF
13 Enable/Disable Switch
14 Remote Source Gain
15 Fire Alarm
16 Line Gain| 17 Line Inputs
18 Paging Console Inputs
19 Paging MIC Gain
20 MIC 1 Input
21 MIC 1 Gain
22 MIC 1 Bass
23 MIC 1 HF
---|---|---

1. DIP SWITCHES
Dip switches set the Matrix system address. If the system is to be expanded, each MAT-8000 unit must be defined as Master, Slave1, 2 or 3. If you  are expanding the system, only line in puts 1-8, MIC 1 and 2 x Remote Paging Consoles of the Master Matrix are enabled. All Slave Matrix units  connected to the Master will use the Master Matrix inputs. For the avoidance of doubt, if a Matrix unit is configured as a slave, the slave Matrix Inputs1 – 8, MIC1 and remote paging consoles inputs will be disabled.
However, the optional wall plates (WP-8000B and WP8000C) can be used to operate these additional zones. Dip switch settings are as follows for configuring the MAT-8000 as a Master or Slave:

2. EVAC / FIRE SYSTEM INTERFACE (7 WAY PHEONIX CONNECTOR)
PIN 1- [+24V DC 24V]
Power supply input.(Battery Back Up or UPS)
PIN 2- [GROUND DC 24V]
Power Supply input .(Battery Back Up or UPS)
PIN3 – [COMMON].
Which is Common for ALERT & EVAC
PIN 4 – [ALERT DRY CONTACT]
The built-in alert voice message will be broadcast to all 8 zones after triggered by dry contact between ALERT and COMMON.
PIN 5 – [EVAC DRY CONTACT]
The built-in EVAC voice message will be broadcasted to all 8 zones after being triggered by dry contact between EVAC and COMMON.
PIN 6 – [EMC IN]
An optional external voice alarm message may be broadcasted to all 8 zones of the system, when an alarm signal is detected from an external voice message generator. Fire alarm, alert, EVAC and EMC in are of equivalent priority.

3. TONE OUTPUT
The Tone Output Volume Control will adjust the output level of the FIRE ALARM, ALERT, EVAC voice messaging.

4. EMC INPUT
The EMC INPUT Volume control will adjust the output level of the EMC voice messaging. Fire alarm, ALERT, EVAC and EMC in are of equivalent priority.
5. EXTENSION LINK (DB37 CONNECTOR)
The extension link connectors enable 8 zone Matrix units to be connected together to form a larger system.
Up to four 8 Zone Matrix units can be connected to make a 32 zone system.
The Matrix can be linked with a DB37 Cable. This will enable the Line 1-8 Sources, MIC1 input, Paging Consoles 1 & 2, and Communication Data of the master unit to be shared with any Slave Matrix Units connected to the system.

6. REMOTE SOURCE
Each zone can have a remote line level source connected.
The remote source input connector is shown here.
This has been designed to be used if you don’t wish to use a local in wall mixer. This could be for example,a Radio MIC.
On selecting this input via the front panel controls, select “L”. Please note that this input cannot be distributed to other zones.
Local zone source level has three adjustments, namely:
a. Gain control for the local source Input on the rear of the Matrix
b. A Music level control on the Matrix front panel or the remote wall control
c. A Master level control on the Matrix front panel.

Please Note: The input signal is set at 300 mV – 1.1 v/10 K Ohm

7. REMOTE CONTROL PANEL INPUT
Each of the eight zones can have a remote control panel connected. The Remote control Panel will enable the source and volume to be controlled from a remote location. Each zone has its own RJ45 input connector allowing for a Remote Control Panel to be connected for control over each zone.

Local Source Connections are as follows:

  1. A remote wall panel can be connected to the Matrix, with only one remote wall controller able to be connected per zone.
  2. The remote wall panel will be selectable on the system. Therefore, selectable sources will be L (local) as well as source line1 to 8.

The RJ45 pin assignment is as follows:

  1. RS485 B
  2. RS485 A
  3. GND
  4. 24V (OUT)
  5. GND
  6. + 24V (OUT)
  7. SPARE
  8. SPAR

8. PAGE
The Zone Page Output Volume Control will adjust the output paging level for the Zone. Every Zone has a Page Output Volume Control which  enables the paging level of each zone to be set independently of other zones.

9. LF BASS
The Zone LF Bass of the Zone Output can be controlled by adjusting the LF Bass Level Control.
This Level Control will provide adjustment of the 100 Hz Audio Frequency by ± 10 dB.
Every Zone has a LF Bass Level Control which enables the LF Bass Level of each zone to be set independently of other zones.

10. OUTPUT
Every Zone has an AUDIO OUTPUT connector; this should be connected to the Audio Amplifier for the designated Audio Zone.
Zone Audio Output Connections are as labeled.

11. GAIN
The Zone Gain control will set the maximum Source Output Volume Level for the Zone.
This will ensure the user cannot adjust the Audio Level too high using the Master, MIC1 and Music Level Control Knobs on the Front Panel. Gain will set the Maximum Output Volume of Line Source and MIC1. It will have no control over the Paging Level.

12. HF
The Zone HF Treble of the Zone Output can be controlled by adjusting the HF Treble Level Control.
This Level Control will provide adjustment of the 100Hz Audio Frequency by 10 dB.
Every Zone has a HF Treble Level Control which enables the HF Treble Level of each zone to be set independently of other zones.

13. ENABLE/DISABLE SWITCH
If a Zone Remote Wall Control Panel is to be used with the System, the RJ45 Remote Control Panel Input needs to be enabled. The RJ45 Remote Control Panel Input is enabled/disabled by pressing the Enable / Disable Switch. Every Zone has an RJ45 Remote Control Panel Input Enable / Disable Switch.
NOTE: Only Enable when a Zone Remote Wall Control Panel is connected.

14. REMOTE SOURCE GAIN
The Zone Local Source Input Signal Level can be adjusted from 190 mV to 200 mV using the Remote Source Gain control. This will enable the signal level of all sources to be equalized there by ensuring Output Volume Level remains constant when switching from one source to another source. Every Zone Remote Source Input has a Gain Control.

15. FIRE ALARM
There are Fire Alarm dry contacts for zones 1-8. When Dry Contact is detected the EMC Input will be open and take priority over all other inputs.
The EMC Input will only take priority and broadcast to zones where there is a Zone Fire Alarm Dry Contact Closure. Each zone has a separate Fire Alarm Dry Contact. Fire alarm, alert, EVAC and EMC in are of equivalent priority.

16. LINE GAIN
The System Line Source Input Signal Levels can be adjusted from 190mV to 200mV using the Line Source Input Gain control. This will enable the signal level of all sources to be equalized there by ensuring Output Volume Level remains constant when switching from one source to another source.
All system source inputs L(lines 1-8) have a separate Gain Control.

17. LINE INPUTS
The system has 4 Line Inputs, as well as 4 inputs selectable as mic or line with phantom power available.
Every Line Source Input has a dual RCA Phono Connector, which will enable a Stereo Source Signal to be connected. Note, however, this is a Mono system and a Stereo Input will be combined to give a Mono Output.

The Line Inputs have an impedance of 47 K Ohms

  1. Line 1-8 source inputs will be selectable using the Source Select control on the front of the Matrix.
  2. The selected source input number will be indicated on the Matrix zone display.
  3. Any extension Matrix unit connected to the system will use sources line 1-8 from the master Matrix.
  4. Only one set of input sources for lines 1-8 can be connected per system.

18. PAGING CONSOLE INPUTS
Up to two paging consoles can be connected to the system simultaneously via the two paging console RJ45 input ports.
The paging consoles will have equal priority and will operate on a first come first served basis. The RJ45 pin assignment order is as below:

19. PAGING MIC GAIN
The Paging MIC Gain control will adjust the Paging MIC Input Signal Level. Each Paging MIC will have its own gain control. There by each Paging MIC can be set independently of the other Paging MICs.

20. MIC1 INPUT
The balanced MIC1 input XLR type has an impedance of 600ohms. Each zone has a MIC1
Priority Button. When the MIC1 priority button is not enabled,MIC1 will be mixed with the line inputs on each zone (1-8 or L). When the MIC1 priority button is enabled,MIC1 will take priority over all line inputs (1 – 8 or L) as well the wall control panel for that zone.
MIC1 will have priority only on Zones where the MIC1 Priority Switch is enabled on the front panel.
Zones where the MIC1 priority switch is not enabled, MIC1 will mix with the Source Selected for the Zone.
The MIC1 level will be controlled by the MIC1 Level Adjustment Knob and the Master Level Adjustment Knob.
The MIC1 signal will be sent to any extension Matrix connected to the system.

21. MIC1 GAIN
The MIC1 Gain controls the MIC1 range from 5 mV to 300 mV.

22. MIC1 BASS
The MIC1 Bass controls the MIC1 gain at 100hz (+/-10dB).

RS 485 communication protocol.

RS 485 Communication protocol
Baud Rate: 57600 bps / S Parity
Check: Odd parity check
Data: 16 bytes
Accumulation = 2 nd data byte +3rd data byte + 4th data byte

MAT-8000 Inquiry Data
The MAT-8000 sends inquiry data to 2 remote paging consoles, 8 remote wall panels and extension Matrix. The new data will feedback to the Matrix when any new data has been checked. Any extension MAT-8000 will only enquire to its own 8 remote wall panels only.

Inquiry Data To paging Console
The MAT-8000 sends the inquiry data to remote paging consoles in the following format: AA 10 00 00 AM (accumulation)
AA: data head
10: inquiry to the paging console
00: meaningless
AM: (accumulation = 2nd data byte + 3rd data byte + 4th data byte)

Feedback Data From paging Console
The feedback data from the remote paging console to the Matrix after got inquiry and ready for paging format as:
AA 11 Matrix address code zone data AM
AA: data head
11 : zone paging command

Matrix address code:
01 : master matrix,
02 : extension matrix 1
03 : extension matrix 2
04 : extension matrix
3 zone data: the zone data is in 8 bytes
0 : no paging
1 : paging, ie: binary system
00000011 B : zone 1 and zone 2 paging
00000100B : zone 3 paging
11111111 B : all 8 zone paging
AM: (accumulation = 2nd data byte + 3rd data byte + 4th data byte)

Status Data To paging Console
After getting paging data from the remote paging console, the Matrix sends zone status data to the paging console in the following format:
hA 1 E Matrix address code zone data AM
AA: data head
1 E: Zone status feedback to paging console

Matrix address code=
01 : master matrix
02: extension matrix 1
03: extension matrix 2
04: extension matrix
3 zone data: the zone data is in 8 bytes,
0: no paging
1 :paging, ie: binary system
00000011 B:zone 1 and zone 2 busy
0000100B: zone 3 busy,
11111111 B: all 8 zone busy
AM: (accumulation = 2nd data byte
3rd data byte + 4th data byte)

Inquiry Data To Remote Wall plate
If the zone is not controlled by a remote wall plate , the inquiry data will not be sent to this zone.
The inquiry command which is from the Matrix to the remote wall plate is both inquiry and status data to update the wall plate status, ie:source input, zone volume. The inquiry data format is:
hA 20 line input volume AM
hA: data head
20: inquiry to wall plate line input: source input
01 : line 1
02 : line 2
08 : line 8
09 : remote sources input volume: volume level
00 : 0 level
01:1 level
AM: (accumulation = 2nd data byte + 3rd data byte + 4th data byte)

Feedback Data From The Wall plate
The feedback data from the wall plate to the Matrix delivered in the following format:
AA 21 line input volume AM
AA: data head
21 : feedback data from wall plate to Matrix line input: source input
01 : line 1
02 : line 2
08 : line 8
09 : remote sources input
volume: volume level
00 : 0 level
01:1 level
AM: (accumulation= 2nd data byte 3rd data byte + 4th data byte)

Inquiry Data To Extension Matrix
The Matrix inquiry data to the extension Matrix format as: AA 30 00 00 AM

Specifications.

| Conditions| Parameters| Deviation
---|---|---|---
AC Power Supply| Voltage selector between 115 V & 240 V| AC 115- 240 V; 50 / 60 Hz Specific voltage and frequency values to the machine to prevail In kind.| 10%
DC Power Supply| | + 24 V| ± 4 V
Line Input Sensitivity| Clockwise rotation gain to Increase| 195 mV-2.0 V|
Line Input Impedance| | 47 K Ω|
Local Input Sensitivity| Balanced input| 500 mV|
Local Gain| | 1 8 dB|
MIC1 Sensitivity| Clockwise rotation gain to Increase| |
MIC1 Impedance| | 600 Ω|
MIC Level Control| Input 100 Hz sine wave signal| 1 8 dB|
Paging Console Sensitivity| Input 1 KHz sine wave signal & output 0.775 V| 500mV|
Paging Console Gain Control| | 1 8 dB|
Zone Output| Balanced output| 0.775 V|
Zone Gain Control| | ± 8 dB|
Zone Output Level Control| Input 100Hz sine wave signal| 10 dB|
S/N Ratio| Non-weighting| < 60 dB|
Isolation Degree| | > 40 dB|
Channel Crosstalk| | > 50 dB|
Gain Deviation| 20 Hz-20 KHz| < 2 dB|
T.H.D| 20 Hz-20 KHz| < 0.07%|
Channel Phase Position| 20 Hz-20 KHz| Same phase|
Frequency Response| Line 1-8 Inputs and remote source Input, 20 Hz-20 KHz| +L / -3 dB|
Frequency Response| MIC1 Input, 80 Hz-18 KHz| +L / -3 dB|

Connection diagram.

Connection and setting.

Power Supply
The remote paging console is powered by the Matrix through the RJ45 communication port when the communication distance is < 50 meters. An extra DC 24V power input is equipped on the back part of the paging console to supply power when the communication distance is longer than 50 meters.

Connection Between Remote paging Console & Extension keypad
The IDE communication cable is used to provide connection between the remote paging console and the extension keypad as well as between two extension keypads.

Extension keypad Dip Switch Setting

There are 4 address codes on both remote the paging console and the extension keypad which are used to identify these.

Please Note:
Only one address code switch of each dip switch can be placed in the downward position. If any of the dip switches are set at different addresses to those shown above, the console will not operate.
Extension keypad Remote paging Console Connection is made through the supplied 10P IDE cable. Once either two or three extension panels are connected, the operation of paging announcements is the same as described previously for individual zone paging or all call actions.

smart solutions in audio

Discover the complete ArtSound
range at www.artsound.be

House Of Music SA/NV Ronse, Belgium
www.artsound.be
Tel. +32 9 380 81 80
Fax. +32 9 386 12 35
[email protected]

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ArtSound User Manuals

Related Manuals