RG2I EM300-SERIES Environment Monitoring Sensor Featuring LoRaWAN User Guide

June 9, 2024
RG2i

RG2I EM300-SERIES Environment Monitoring Sensor Featuring LoRaWAN

Applicability

This guide is applicable to EM300 series sensors shown as follows, except where otherwise indicated.

Model Description
EM300-TH Temperature and Humidity Sensor
EM300-MCS Magnet Switch Sensor
EM300-SLD Spot Leak Detection Sensor
EM300-ZLD Zone Leak Detection Sensor

Safety Precautions

Milesight will not shoulder responsibility for any loss or damage resulting from not following the instructions of this operating guide.

  • The device must not be disassembled or remodeled in any way.
  • In order to protect the security of the device, please change device password when first configuration. The default password is 123456.
  • The device is not intended to be used as a reference sensor, and Milesight will not should responsibility for any damage which may result from inaccurate readings.
  • Do not place the device close to objects with naked flames.
  • Do not place the device where the temperature is below/above the operating range.
  • Make sure electronic components do not drop out of the enclosure while opening.
  • When installing the battery, please install it accurately, and do not install the reverse or wrong model.
  • Make sure both batteries are newest when install, or battery life will be reduced.
  • The device must never be subjected to shocks or impacts.

Declaration of Conformity
EM300 series is in conformity with the essential requirements and other relevant provisions of the CE, FCC, and RoHS.RG2I-EM300-SERIES-Environment-
Monitoring-Sensor-Featuring-LoRaWAN-fig-1

All information in this guide is protected by copyright law. Whereby, no organization or individual shall copy or reproduce the whole or part of this user guide by any means without written authorization from Xiamen Milesight IoT Co., Ltd.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-
LoRaWAN-fig-2

For assistance, please contact Milesight technical support:
Email: iot.support@milesight.com
Tel: 86-592-5085280
Fax: 86-592-5023065
Address: Building C09, Software Park III, Xiamen 361024, China

Revision History

Date Doc Version Description
Oct. 14, 2020 V 1.0 Initial version
Oct. 21, 2020 V 1.1 Model name change and pictures replace
Nov. 19, 2020 V 2.0 Layout replace
Mar. 4, 2021 V 2.1 Layout update
July 5, 2021 V 2.2 Delete USB Type-C description
Dec. 7, 2021 V 2.3 Add alarm setting, change SN to 16 digits

Product Introduction

Overview

EM300 series is a sensor mainly used for outdoor environments through a wireless LoRa network. EM300 device is battery-powered and designed for multiple mounting ways. It is equipped with NFC (Near Field Communication) and can easily be configured by a smartphone.
Sensor data are transmitted in real-time using standard LoRaWAN® protocol. LoRaWAN® enables encrypted radio transmissions over long distance while consuming very little power. The user can obtain sensor data and view the trend of data change through Milesight IoT Cloud or through the user’s own Network Server.

Features

  • Up to 11 km communication range
  • Easy configuration via NFC
  •  Standard LoRaWAN® support
  • Milesight IoT Cloud compliant
  • Low power consumption with 4000mAh replaceable battery

Hardware Introduction

Packing ListRG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-
LoRaWAN-fig-3

Note: If any of the above items is missing or damaged, please contact your sales representative.

Hardware Overview

Front View:

  1. NFC Area Bottom View:
  2. Vent
  3. Waterproof Connectors
    (For water leakage and magnet switch sensor)

Dimensions(mm)RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-
LoRaWAN-fig-6

Power Button

Note: The LED indicator and power button are inside the device. Switch on/off and reset can also be configured via NFC.

Function Action LED Indication
Turn On Press and hold the button for more than 3 seconds. Off → On
Turn Off Press and hold the button for more than 3 seconds. On -> Off
Reset Press and hold the button for more than 10 seconds. Blink 3 times.

Check

On/Off Status

|

Quickly press the power button.

| Light On: Device is on.
---|---|---
Light Off: Device is off.

Operation Guide

NFC Configuration
EM300 series can be configured via NFC.

  1. Download and install the “Milesight ToolBox” App from Google Play or Apple Store.
  2. Enable NFC on the smartphone and open the “Milesight ToolBox” App.
  3. Attach the smartphone with NFC area to the device to read basic information.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-fig-7
  4. Basic information and settings of devices will be shown on ToolBox if it’s recognized successfully. You can turn on/off the device by tapping the button on the Device Status. In order to protect the security of devices, password validation is required when configuring via unused phone. The default password is 123456.
  5. Tap the “Read” button to check the current status and sensor data of the device.
  6. Tap the “Write” button to write all your settings to the device.

Note:

  1. Ensure the location of the smartphone NFC area and it’s recommended to take off the phone case.
  2. If the smartphone fails to read/write configurations via NFC, keep the phone away and back to try again.
  3. EM300 series can also be configured by a dedicated NFC reader provided by Milesight IoT or you can configure it via TTL interface inside the device.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-fig-9

LoRaWAN Settings
LoRaWAN settings is used for configuring the transmission parameters in LoRaWAN® network.

Basic LoRaWAN Settings:
Go to Device- >Setting->LoRaWAN Settings of ToolBox App to configure join type, App EUI, App Key and other information. You can also keep all settings by default.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-
LoRaWAN-fig-10

Parameters Description
Device EUI Unique ID of the device which can also be found on the label.
App EUI Default App EUI is 24E124C0002A0001.
Application Port The port used for sending and receiving data, default port

is 85.
Join Type| OTAA and ABP mode are available.
Application Key| Appkey for OTAA mode, default is 5572404C696E6B4C6F52613230313823.
Device Address| DevAddr for ABP mode, default is the 5th to 12th digits of SN.
Network Session

Key

|

Nwkskey for ABP mode, default is 5572404C696E6B4C6F52613230313823.

Application

Session Key

|

Appskey for ABP mode, default is 5572404C696E6B4C6F52613230313823.

Spread Factor| If ADR is disabled, the device will send data via this spread factor.

Confirmed Mode

| If the device does not receive ACK packet from network server, it will resend data 3 times at most.

Rejoin Mode

| Reporting interval ≤ 30 mins: device will send specific mounts of LoRaMAC packets to check connection status every 30 mins; If no reply after specific packets, the device will re-join.

Reporting interval > 30 mins: the device will send specific mounts of LoRaMAC packets every to check the connection status every reporting interval; If no reply

after specific packets, the device will re-join.

ADR Mode| Allow the network server to adjust data rate of the device.
Tx Power| Transmit power of device.

Note:

  1. Please contact sales for device EUI list if there are many units.
  2. Please contact sales if you need random App keys before purchase.
  3. Select OTAA mode if you use Milesight IoT cloud to manage devices.
  4. Only OTAA mode supports rejoin mode.

LoRaWAN Frequency Settings:
Go to Setting- >LoRaWAN Settings of ToolBox App to select supported frequency and select channels to send uplinks. Make sure the channels match the LoRaWAN® gateway.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-
Featuring-LoRaWAN-fig-11

If frequency is one of CN470/AU915/US915, you can enter the index of the channel that you want to enable in the input box, making them separated by commas.

Examples:

1, 40: Enabling Channel 1 and Channel 40
1-40: Enabling Channel 1 to Channel 40
1-40, 60: Enabling Channel 1 to Channel 40 and Channel 60
All: Enabling all channels
Null : Indicates that all channels are disabledRG2I-EM300-SERIES-
Environment-Monitoring-Sensor-Featuring-LoRaWAN-fig-12

Note:
For -868M model, default frequency is EU868;
For -915M model, default frequency is AU915.

Basic Settings
Go to “Device- >Setting->General Settings” of ToolBox App to change the reporting interval, etc.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-
Featuring-LoRaWAN-fig-13

Parameters Description
Reporting Interval Reporting interval of transmitting data to a network

server.Default: 600s

Temperature Unit

| Change the temperature unit displayed on the ToolBox. Note:

1)    The temperature unit in the reporting package is fixed as °C.

2)    Please modify the threshold settings if the unit is changed.

Change Password

| Change the password for ToolBox App or software to read/write this device.

Advanced Settings

Calibration Settings
The toolbox supports numerical calibration for all items. Go to **“Device-

Setting->Calibration Settings”** of the ToolBox App to type the calibration value and save, the device will add the calibration value to the raw value .RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-
fig-14

Threshold Settings
Go to Device- >Setting->Threshold Settings of ToolBox App to enable the threshold settings and input the threshold. EM300 series will upload the current data once instantly after the temperature threshold is triggered .RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-
fig-15

Alarm Settings
Go to “Device- >Setting->Alarm Settings” of ToolBox App to enable the alarm settings. When EM300 detects door status change or water leakage, it will report the alarm according to reporting interval and reporting times setting.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-
fig-16

Maintenance

Upgrade

  1. Download firmware from Milesight website to your smartphone.
  2. Open Toolbox App and click “Browse” to import firmware and upgrade the device.

Note:

  1. Operation on ToolBox is not supported during an upgrade.
  2. Only Android version ToolBox supports the upgrade feature.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-fig-17

Backup
EM300 devices support configuration backup for easy and quick device configuration in bulk. Backup is allowed only for devices with the same model and LoRa frequency band.

  1. Go to “Template” page on the App and save current settings as a template. You can also edit the template file.
  2. Select one template file which saved in the smartphone and click “Write” , then attach to another device to write configuration.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-fig-18

Note: Slide the template item left to edit or delete the template. Click the template to edit the configurations.RG2I-EM300-SERIES-Environment-
Monitoring-Sensor-Featuring-LoRaWAN-fig-19

Reset to Factory Default
Please select one of the following methods to reset the device:
Via Hardware : Hold on power button (internal) for more than 10s.
Via ToolBox App: Go to “Device- >Maintenance” to click “Reset”, then attach the smartphone with NFC area to device to complete reset.RG2I-EM300
-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-
fig-20

Installation

  1. Attach EM300 to the wall and mark the two holes on the wall. The connecting line of two holes must be a horizontal line.
  2. Drill the holes according to the marks and screw the wall plugs into the wall.
  3. Mount the EM300 to the wall via mounting screws.
  4. Cover the mounting screws with screw caps.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-fig-21
  5. For leak detection senor, install the probe/cable to the place where liquid may leak. For magn et switch sensor, install the magnet beside the door/window.
    Note: For SLD sensor, please ensure the metal pins of the probe are flat on the floor; for ZLD sensor, the cable can’t be twined or accumulated together. The probe or cable of water leakage sensor should be placed in an area of concern where water from a leak would likely accumulate.RG2I-EM300
-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-
fig-22

Milesight IoT Cloud Management

EM300 series can be managed by Milesight IoT Cloud platform. Milesight IoT cloud is a comprehensive platform that provides multiple services including device remote management and data visualization with the easiest operation procedures. Please register a Milesight IoT Cloud account before operating following steps.

  1. Ensure Milesight LoRaWAN® gateway is online in Milesight IoT Cloud. For more info about connecting gateway to cloud please refer to gateway’s user guide.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-fig-23
  2. Go to “My Devices” page and click “+New Devices”. Fill in the SN of device and select associated gateway.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-fig-24
  3. After the device is online in Milesight IoT Cloud, you can check the data via webpage or mobile App and create dashboard for it.RG2I-EM300-SERIES-Environment-Monitoring-Sensor-Featuring-LoRaWAN-fig-25

Device Payload

All data are based on the following format(HEX):

Channel1 Type1 Data1 Channel2 Type2 Data2 Channel 3
1 Byte 1 Byte N Bytes 1 Byte 1 Byte M Bytes 1 Byte

For decoder examples please find files on https://github.com/Milesight- IoT/SensorDecoders.

Basic Information

EM300 series sensors report basic information of sensor whenever joining the network.

Channel Type Description

ff

| 01(Protocol Version)| 01=>V1
09 (Hardware Version)| 01 40 => V1.4
0a(Software Version)| 01 14 => V1.14
0f(Device Type)| 00: Class A, 01: Class B, 02: Class C
16(Device SN)| 16 digits

Example:

ff 09 01 00 ff 0a 01 02 ff 0f 00

Channel| Type| Value| Channel| Type| Value

ff

| 09

(Hardware version)

|

0100 (V1.0)

|

ff

| 0a (Software version)| 0102 (V1.2)
Channel| Type| Value|  |  |

ff

| 0f

(Device Type)

| 00

(Class A)

|  |  |

Sensor Data
EM300 series sensors report sensor data according to reporting interval (10min by default). Battery level is reported every 6 hours.

Channel Type Description
01 75(Battery Level) UINT8, Unit: %
03 67 (Temperature) INT16, Unit: °C
04 68(Humidity) INT8, Unit: %

05

| 00(Water Leakage

Status)

| 00: Not water leakage 01: Water leakage

06

|

00(Magnet Status)

| 00: Magnet switch closed 01: Magnet switch open

Example:

01 75 64 03 67 10 01 04 68 71 05 00 01

Channel| Type| Value| Channel| Type| Value

01

|

75

(Battery)

|

64 => 100%

|

03

| 67

(Temperat ure)

|

10 01 => 01 10 = 272

Temp=272*0.1=27.2°C

---|---|---|---|---|---
Channel| Type| Value| Channel| Type| Value

04

|

68

(Humidity)

| 71=>113

Hum=113* 0.5=56.5%

|

05

|

00

|

01=>Water leakage

Downlink Commands
EM300 series sensors support downlink commands to configure the device. The application port is 85 by default.

Channel Type Description
ff 03 (Set Reporting Interval) 2 Bytes, unit: s

Example: Set reporting interval as 20 minutes.

ff03b004

Channel| Type| Value
ff| 03 (Set Reporting Interval)| b0 04 => 04 b0 = 1200s = 20 minutes

Tél: +33 (0) 477 92 03 56
Fax: +33 (0) 477 92 03 57

Rémv GUEDOT
Gsm:
+33 (0) 662 80 65 57
guedot@rg2i.fr

Olivier BENAS
Gsm: +33 (0) 666 84 26 26
olivier.benas@rg2i.fr

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals