Qlima PES 7125 Mobile Air Conditioning User Manual

June 9, 2024
Qlima

Qlima PES 7125 Mobile Air Conditioning

IMPORTANT COMPONENTS

  1. Outlet blade
  2. Control panel
  3. Cover
  4. Handle
  5. Side plate
  6. Front plate
  7. Roller
  8. Back air inlet grille
  9. Water inlet and knob
  10. Water outlet and knob
  11. Back plate

ACCESSORIES

  1. One inlet pipe and one outlet pine
  2. Versatile water pipe joint

READ THE DIRECTIONS FOR USE FIRST. IN CASE OF ANY DOUBT, CONTACT YOUR DEALER.

Dear Sir, or Madam,
Congratulations on the purchase of your air conditioner. This air conditioner has three functions in addition to cooling the air, namely, air dehumidification, circulation, and filtration. The mobile air conditioner is extremely easy to operate and move. You have acquired a high-quality product that will provide you with many years of pleasure, on condition that you use it responsibly. Reading these instructions for use before operating your air conditioner will optimize its life span. We wish you coolness and comfort with your air conditioner. Yours sincerely, PVG Holding B.V. Customer service department

SAFETY INSTRUCTIONS

Read this user manual carefully before using the appliance and keep it for future reference. Install this device only when it complies with local/national legislation, ordinances, and standards. This product is intended to be used as an air conditioner in residential houses and is only suitable for use in dry locations, in normal household conditions, and indoors in the living room, kitchen, and garage.

Minimum clearance from the

appliance to combustible surface

| 0.3M
---|---
Details of type and rating of fuse| F6.3AL250V
Maximum water operating

temperature

| -6°C
Minimum water operating

temperature

| -40°C
The maximum inlet water pressure,

in pascals

| ≥1.0MPa
Minimum inlet water pressure,

in pascals

| 0.6MPa

Always use the hose set supplied with the appliance. Do not use hold hose sets.

IMPORTANT

  •  Never use the device with a damaged power cord, plug, cabinet or control panel. Never trap the power cord or allow it to come into contact with sharp edges.
  •  The installation must be completely in accordance with local regulations, ordinances, and standards.
  •  The device is suitable exclusively for use in dry places, and indoors.
  •  Check the mains voltage. This device is suitable exclusively for earthed sockets –connection voltage 220-240 Volt/ 50 Hz.
  •  The device MUST always have an earthed connection. You may absolutely not connect the device if the power supply is not earthed.
  •  The plug must always be easily accessible when the device is connected.
  •  Read these instructions carefully and follow the directions.

Before connecting the device, check that

  •  The connection voltage corresponds to that on the type plate.
  •  The socket and power supply are suitable for the device.
  •  The plug on the cable fits the socket.
  •  The device is on a stable and flat surface.
  • Has the electrical installation been checked by a recognised expert if you are not sure that everything is in order?
  • The air conditioner is a safe device, manufactured in accordance with CE safety standards. Nevertheless, as with every electrical device, exercise caution when using it.
  •  Never cover the air inlets and outlets.
  •  Empty the water reservoir through the water drain before moving it.
  •  Never allow the device to come into contact with chemicals.
  •  Do not insert objects into the openings of the device.
  •  Never allow the device to come into contact with water. Do not spray the device with water or submerge it as this may cause a short circuit.
  •  Always take the plug out of the socket before cleaning or replacing the device or a part of the device.
  •  NEVER connect the device with the aid of an extension cable. If a suitable, earthed socket is not available, have one fitted by a recognised electrician.
  •  Always consider the safety of children in the vicinity of this device, as with every electrical device.
  •  Always have any repairs – beyond regular maintenance – carried out by a recognized service engineer. Failure to do so may lead to the  Qinvalidation of the guarantee.
  •  Always take the plug out of the socket when the device is not in use.
  • If the power cable is damaged it must be replaced by the manufacturer, its customer service department or persons with comparable qualifications in order to prevent danger.
  • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  •  Children should be supervised to ensure that they do not play with the appliance.
  •  This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowl-edge if they have been given supervision or instruction concerning use of the appliance in a safe way and understanding the hazards involved.
  •  Children shall not play with the appliance.
  •  Cleaning and user maintenance shall not be made by children without supervision.

ATTENTION!

  •  Never seal the room – where this device will be used – completely airtight. This will prevent pressure in this room. Under pressure can disrupt the safe operation of geysers, ventilation systems, ovens, etc.
  •  Failing to follow the instructions may lead to the nullification of the guarantee on this device.
  • Specific information regarding appliances with R290 / R32 refrigerant ga.
  •  Thoroughly read all of the warnings.
  •  When defrosting and cleaning the appli-ance, do not use any tools other than those recommended by the manufacturing company.
  •  The appliance must be placed in an area without any continuous sources of ignition (for example open flames, gas or elec-trical appliances in operation).
  •  Do not puncture and do not burn.
  •  This appliance contains Y g (see rating label back of unit) of R290 / R32 refrigerant gas.
  •  R290 / R32 is a refrigerant gas that complies with European directives on the environment. Do not puncture any part of the refrigerant circuit. Be aware the refrigerants may not contain an odor.
  •  If the appliance is installed, operated or stored in a nonventilated area, the room must be designed to prevent to the accumulation of refrigerant leaks resulting in a risk of fire or explosion due to ignition of the refrigerant caused by electric heaters, stoves, or other sources of ignition.
  •  The appliance must be stored in such a way as to prevent mechanical failure.
  •  Individuals who operate or work on the refrigerant circuit must have the appropriate certification issued by an accredited organization that ensures competence in handling refrigerants according to a specific evaluation recognized by associations in the industry.
  •  Repairs must be performed based on the recommendation from the manufacturing company.
  •  Keep ventilation openings clear of obstruc-tion Maintenance and repairs that require the assistance of other qualified personnel must be performed under the supervision of an individual specified in the use of flammable refrigerants.
  • Appliances shall be installed, operated, and stored in a room with a floor area larger than 4 m2.
  • The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
  • INSTRUCTIONS FOR REPAIRING APPLIANCES CONTAINING R290 / R32

GENERAL INSTRUCTIONS

This instruction manual is intended for use by individuals possessing adequate backgrounds of electrical, electronic, refrigerant, and mechanical experience.

Checks to the area

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.

Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of flammable gas or vapor being present while the work is being performed.

General work area
All maintenance staff and others working in the local area shall be instructed on the nature of the work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.

Checking for the presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.

Presence of fire extinguisher
lf any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

No ignition sources
No person carrying out work in relation to a refrigeration system that involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.

Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it extremely into the atmosphere.

Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. lf in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: – the charge size is in accordance with the room size within which the refrigerant-containing parts are installed;

  •  the ventilation machinery and outlets are operating adequately and are not obstructed;
  •  if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
  •  marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
  •  refrigeration pipes or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant-containing components unless the components are constructed of materials that are inherently resistant to being corroded or are suitably protected against being so corroded.

Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. lf a fault exists that could compromise the safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. lf the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. initial safety checks shall include:

  • that capacitors are discharged: this shall be done in a safe manner to avoid the possibility of sparking;
  •  that there no live electrical components and wiring are exposed while charging, recovering, or purging the system;
  •  that there is continuity of earth bonding.

REPAIRS TO SEALED COMPONENTS

During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. lf it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.

Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, an excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that the apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. intrinsically safe components do not have to be isolated prior to working on them.

REPAIR TO INTRINSICALLY SAFE COMPONENTS

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and currently permitted to the equipment in use. intrinsically safe components are the only types that can be worked on while living in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

CABLING
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continua! vibration from sources such as compressors or fans.

DETECTION OF FLAMMABLE REFRIGERANTS
Under no circumstances shall potential sources of ignition be used in the search for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame} shall not be used.

LEAK DETECTION METHODS
The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate or may need recalibration. (Detection equipment shall be calibrated in a refrigerant- free area.)
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum} is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipework. lf a leak is suspected, all open flames shall be removed/extinguished.

lf a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut- off valves} in a part of the system remote from the leak. Oxygen-free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.

REMOVAL AND EVACUATION
When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: remove refrigerant; purge the circuit with inert gas; evacuate; purge again with inert gas; open the circuit by cutting or brazing.

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to the atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipework are to take place. Ensure that the outlet tor the vacuum pump is not close to any ignition sources and ! there is ventilation available.

CHARGING PROCEDURES
In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them. Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete (if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow-up leak test shall be carried out prior to leaving the site.

DECOMMISSIONING
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. lt is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to the re-use of reclaimed refrigerant. lt is essential that 4 GB of electrical power is available before the task is commenced.

  • Become familiar with the equipment and its operation.
  • isolate the system electrically.
  • Before attempting the procedure ensure that: mechanical handling equipment is available, if required, for handling refrigerant cylinders;
  • All personal protective equipment is available and being used correctly; the recovery process is supervised at all times by a competent person;
  • recovery equipment and cylinders conform to the appropriate standards.
  • Pump down the refrigerant system, if possible. g) lf a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. h) Make sure that cylinder is situated on the scales before recovery takes place.i) Start the recovery machine and operate in accordance with the manufacturer’s instructions.
  • Do not overfill cylinders. (No more than 80 % volume liquid charge).
  • Do not exceed the maximum working pressure of the cylinder, even temporarily.
  • When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. m) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

LABELLING
Equipment shall be labeled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

RECOVERY

When removing refrigerant from a system, either for servicing or decommissioning, il is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valves and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that il is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult the manufacturer if in doubt.

The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.

lf compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric healing to the compressor body shall be employed to accelerate this process. When oil is drained from a system, il shall be carried out safely.

CONNECT POWER SUPPLY

  1. For the first use, please connect the power supply, then refer to step 2 “water inflow”
  2. When it is not used for the first time or there is water in the water tank, insert the power plug into the power socket and press the [power] key on the control panel.

WATER INFLOW
In case of a water shortage alarm (no water in the water tank during the first use or water shortage during use), please follow the steps below to feed water into the water tank inside the machine.

  1. Use an inlet/outlet pipeline to connect this machine to the faucet. Press the water inlet key, and the faucet should be turned on at the same time.
  2. When the water level reaches the specified height, the water inlet valve will automatically close to complete the water inlet.
  3. Remove the water inlet /outlet pipe and screw the water inlet knob cover.

REPLACE THE WATER IN THE WATER TANK REGULARLY
It is recommended to replace the water in the water tank through drainage/water inlet at least every quarter.

OPERATION

Qlima-PES 7125-Mobile-Air-Conditioning-User-Manual-
FIG-2

  1.  Power
    Press this button to switch on/off the air conditioner

  2.  Drainage
    Press this button to start the water drainage function.

  3.  Inflow
    Press this button to start the water inflow function.

  4.  (+) and (-)
    In cool, strong cold, dehumidify, cool storage, heat storage, or heat mode, press this button to increase or decrease the setting temperature (Each press adjusts 1 degree). In the timing and preset mode, press this button to increase or decrease the setting time (Each press adjusts 1 hour.)

Screen display

Mode
Press this button to select the modes: Heat, Strong cold, Dehumidify, Cold storage, Heat storage, Heat, and Ventilation.

Wind speed
Press this button to select the wind speed: Mid, High, Auto, and Low

Swing
Press this button to select the up-down swing or to stop the swing.

Timing
In every mode (Cool, Strong cold, Dehumidify, Cold storage, Heat storage, Ventilation), press [timing] to set the end time of such running mode. After powering on, press [timing] to set the mode, as well as the start and end time of such running mode.

Preset
Press this button to preset hours before the air conditioner will be used, and this unit will store the energy (heat storage/cold storage) automatically during this period.

Cooling

  1.  Press the [Mode] key to select the cooling function
  2.  Press the [+] or [-] key to set the cooling temperature, and set the temperature range between 16ºC and 32ºC.
  3.  Press the [wind speed] key to select low wind, mid wind, high wind, and automatic wind speed in 4 levels.
  4.  Press the [swing wind] key to select the upper and lower swing blades to swing or stop. When the cooling capacity of the water in the water tank is used up (the water temperature reaches 40ºC), the cooling shall be stopped, and the water can only be used after the cold storage or the high-temperature water in the water tank is replaced.

Strong Cooling
This mode can be used when fast cooling is required.

  1.  Press the [Mode] key to select the forced cooling function
  2. Press the [+]or[-] key to set the strong cooling temperature, and set the temperature range between 16ºC and 32ºC.
  3.  Press the [swing wind] key to select the upper and lower swing blades to swing or stop. It displays the actual air inlet temperature during cooling when the cooling capacity of the water in the water tank is used up (the water temperature reaches 40ºC), the cooling shall be stopped, and the water can only be used after the cold storage or the high-temperature water in the water tank is replaced

Dehumidification

  1.  Press the [Mode] key to select the dehumidification function
  2.  Press the [swing wind] key to select the upper and lower swing blades to swing or stop. It displays the actual air inlet temperature during the dehumidification

Cold Storage

  1.  Press the [Mode]key to select the cold storage function
  2.  Press the [+] or [-] key to set the cold storage temperature. The lower the set temperature is, the greater the storage capacity is. Set the temperature range between – 6ºC and 5ºC
  3.  After the completion of cold storage, it will automatically enter the standby insulation state.

Heat Storage

  1.  Press the [Mode]key to select the heat storage function
  2. Press the [+]or[-]key to set the heat storage temperature, between 20ºC and 30ºC. After heat storage completes, the unit enters in standby and temperature-holding status.

Heating

  1.  Press the [mode] key to select the heating function
  2.  Press the [+] or [-] key to set the heating temperature, and select the temperature range between 16ºC and 32ºC.
  3.  Press the [wind speed] key to select low wind, mid wind, high wind and automatic wind speed in 4 levels.
  4.  Press the [swing wind] key to select the upper and lower swing blades to swing or stop.

Ventilation

  1.  Press the [mode] key to select the ventilation function
  2.  Press the [wind speed]key to select low wind, mid wind, high wind and automatic wind speed in 3 levels.
  3.  Press the [swing wind] key to select the upper and lower swing blades to swing or stop.

Preset

  1.  Press the [preset] key to enter the preset mode, and then select the cold storage preset and heat storage preset.
  2. Press the [preset] key to confirm cold storage preset or heat storage preset.
  3.  Press [+] or [-] to select how many hours to use after the preset, and select the time interval between 4 hours and 24 hours. After selecting the time, press the [preset] key again to confirm, and the voice prompts that the preset is completed.

Preset cancellation method

  1.  Press the [preset] key again, the previous preset will be canceled, and a new preset can be made at this time
  2.  After the power is off, the preset will be canceled automatically.
  3.  Press and hold the[preset] key for more than 3 seconds to cancel the preset.

Timing

  1. When it is not in cooling, strong cooling, ventilation, heating or dehumidification mode.
    • Press the  [Mode] key to select the function, then press [Timing] to confirm
    •  Press [+] and [-] to select the start time, and then press [Timing] to confirm. c Press [+] and [-] again to select the end time, and then press[Timing] to confirm.
    • t the end of the timing setting, there shall be a voice prompt.
  2. When it is in cooling, strong cooling, ventilation, heating or dehumidification mode:
    •  Press [+] and [-] to select the end time, and then press [Timing] to confirm. b Press [Timing] to confirm.
    • At the end of the timing setting, there shall be a voice prompt.

Condensation Removal
After the completion of cold storage or heat storage, if there is no other operation, the condensation removal function will start automatically without any other operation.

Drainage
In case of full water alarm and need to drain to the working water level or drain the water in the water tank, please follow the steps below to drain the water in the internal water tank of the machine.

  1. Unscrew the drain knob on the rear plate, tighten one end of the water inlet/drain pipe to the drain, and connect the other end to the drain such as the water collecting container or floor drain.
  2. Insert the power plug into the power socket and press the on key on the control panel.
  3.  Press the [drainage] key, and press the drainage key for more than 3 seconds according to the voice prompt, and the system will automatically start the water pump for drainage.
  4.  When the water level is above the working water level, the drainage will stop only when it reaches the working water level. If it is necessary to drain the water in the water tank, repeat step (3) to continue the drainage until it is drained.
  5.  After the completion of drainage, the drainage pump will automatically shut down.
  6.  Remove the water inlet/drain pipe and screw the drain knob cover.

APP USE

Download APP
Please download Tuya APP from the Internet.

Register

  • Click “create new account” to enter the registration page
  • The system will automatically determine the current country/region. You can also select the country/region manually, enter the mobile phone number or email, and click next.
  •  If you fill in the mobile number, fill in the verification code received by the mobile phone, enter the password, and click “OK” to register successfully
  •  If you fill in the email address, enter the password on the page and click “OK” to register successfully

Log in / Retrieve Password Account + Password Login

  • If you have already registered your APP account, click “log in with existing account” to enter the login page
  •  The system will automatically judge the current country/region, or you can select a country/region manually.
  •  Enter your registered mobile number or email, enter your password and log in to the system
  •  Click “Short message verification code login” to enter the new page
  •  The system will automatically judge the current country/region, or you can select a country/region manually.
  •  Enter the mobile number and click the “get” button to get the short message verification code. Enter the verification code in the short message and click the “verify and log in” button to log in to the system
  • If you forget the account login password of APP, you can reset the account password through the process of retrieving the password
  •  Click “forget password”
  •  The system automatically judges the current country/region. You can also select the country/region manually, enter your registered mobile phone number or email, and click next,
  •  Fill in the verification code received by mobile phone or email, enter the new password, and click “Confirm”

Family / Member management

  • After login, click “Start your smart life” to enter the “add family” page
  • Family name” can be manually entered from the definition, and “family location” can be clicked to enter the map page. You can move the family coordinate point to change the address manually, and then click “confirm” after confirming the address
  • Click “add other rooms” to add. Click “finish” in the upper right corner to finish the room setting. After that, you can also modify the room settings at any time, and click the button on the “my home” page

WIFI connection

  •  Place the product within WIFI range.
  • Plug in power supply cable, press Power button into standby mode, then press Power button as long as over 5 seconds, and WIFI indicator will be flashing.
  •  3.Enter “Tuya” APP, click Add equipment➙ Big appliance➙ Air conditioner➙ select WIFI 2.4GHZ➙ select WIFI➙ Input WIFI password, then press Power button into standby mode, then press Power button as long as over 5 seconds, then repeat operation on the mobile phone.

Control device- separate control

After the device is configured successfully, the name of the intelligent device will appear on the home page. Click to enter the control panel of the intelligent device. At this time, you can control the on and off of the air conditioner, select the working mode(Cool, Strong cold, Dehumidify, Cold storage, Heat storage, Ventilation, Standby) of the air conditioner, and select functions of the air conditioner temperature, wind speed, auxiliary heating, screen display, child lock, wind swing, etc.).

[Timing] function: Press “Timing”, click “Add” and select time period, then select timing on/off(Note: when timing off is selected, you need to select the time period and running mode, and need not to select a temperature, wind swing or wind speed). Set temperature range (Note: The temperature ranges for all modes are: Strong cold 16-32ºC; Cool 16-32ºC; Heat 16-32ºC; Cold storage -6-5ºC; Heat storage 20-30ºC; Dehumidify 25ºC).Set wind swing and wind speed (Note: The wind speed might be different in different running modes). Then click “Save”, the preset values are saved. (In APP, the Health button is only valid for the unit with an ultra-violet health lamp.)

Note

  •  When the device is online, it supports shortcut key operation. Click “common functions” to operate.
  •  When the device is offline, the device displays “offline” and cannot be operated.
  • Click “add sharing”, then fill in the account needed to share, and click finish. For those added shared accounts, you can long press it to delete it and no longer share the device.

AIR FILTER

Unscrew the two knobs of water inlet and water outlet from the rear side, then remove the rear air inlet grille, and remove the filter screen from the rear air inlet grille for cleaning. Put the filter screen into clean water or warm water (about 40ºC) which has been added with neutral detergent, and then place it in dry air to dry naturally, and then reinstall the filter screen.

  •  Do not use water with too high a temperature (suitable temperature is about 40 ºC) or irritant detergent (such as alcohol, gasoline, benzene, etc.) to clean the filter screen;
  •  In order to avoid the deformation of the filter screen, the cleaned filter screen should be kept away from the heat source and put in the dry air to dry naturally;
  •  It is recommended to clean the filter screen once every two weeks.

SEASONAL MAINTENANCE

WARNING!
Switch off the unit and remove the electrical plug from the mains before cleaning the appliance or filter, or before replacing the filters.If you do not use the machine for a long time, please follow the steps below to maintain it:

  1. Drain the water from the tank.
  2.  Clean and reinstall the filter screen.
  3.  Cover the machine with plastic bags and place it in a cool and dry place.If it is not used for a long time, please pay attention to the following points when using it again.

TROUBLESHOOTING

Intelligent Fault Detection

Fault Code Code Meaning Solution

E1

| ****

Water shortage of water tank

| Please connect the water inlet pipe and press the [water

inlet] key to feed water


E2

| ****

Water tank is full

| Please connect the drain pipe and press the [drain] key to

drain

Fault Maintenance
The following table lists the common faults and maintenance methods of this energy-storage mobile air conditioner. When the machine is abnormal, simple diagnosis and maintenance can be carried out through the following table. If it still cannot be solved, please contact professional maintenance personnel

Problem Possible Reason Solution

Air conditioner does not work

| Power is not on| Turn on the power

Cooling, dehumidification and heating do not start

| Check whether the set

temperature has been reached

No waiting for three minutes

after cooling heating switching or shutdown

|

Wait for over three minutes.

Poor cooling (heating) effect of air conditioner

| The doors and windows are open, and there is a cold or heat leak in the room. There are other heat sources (cold

sources)

|

Close the door or window and remove the heat source (cold source)

Filter screen is dirty

| Clean or replace the filter

screen

Air inlet or outlet blocked,

poor air circulation

|

Remove blockage

Air conditioner is noisy

|

Air conditioner is not put flat

| Put it on flat surface to avoid

waggling

– The sound comes from the flowing of the refrigerant

inside the air conditioner

|

It is normal.

Compressor does not work

|

Compressor delay protection enabled

| Wait for more than 3 minutes and turn on the air conditioner after the

temperature drops

In the cooling mode, when the water temperature does not reach the starting

condition of the compressor, the water cycle is used for cooling, and the compressor

does not start at this time.

|

When the water cycle cooling is completed, the compressor will be automatically started for cooling

During cold storage, there is condensate on the front

and rear plates

|

When the air humidity is high and the water vapor in the air is cold, the dew will condense on the air conditioning plate

|

It is not a fault, you can continue to use it, please check whether you have turn off dew removal function.

Never try to repair or dismantle the air conditioner yourself. Incompetent repairs result in loss of warranty and can endanger the user.

GUARANTEE CONDITIONS

The air conditioner is supplied with a 24-month guarantee, commencing on the date of purchase. All material and manufacturing defects will be repaired or replaced free of charge within this period. The following rules apply:

  1.  We expressly refuse all further damage claims, including claims for collateral damage.
  2.  Repairs to or replacement of components within the guarantee period will not result in an extension of the guarantee.
  3.  The guarantee is invalidated if any modifications have been made, nongenuine parts are fitted or repairs are carried out by third parties.
  4.  Components subject to normal wear, such as the filter, are not covered by the guarantee.
  5.  The guarantee is valid only when you present the original, dated purchase invoice and if no modifications have been made to the product nor to the purchase invoice.
  6.  The guarantee is invalid for damage caused by neglect or by actions that deviate from those in this instruction booklet.
  7.  Transportation costs and the risks involved during the transportation of the air conditioner or air conditioner components shall always be for the account of the purchaser.
  8. Damage caused by not using suitable filters is not covered by the guarantee.

To prevent unnecessary expense, we recommend that you always first carefully consult the instructions for use. Take the air conditioner to your dealer for repairs if these instructions do not provide a solution.

Do not dispose of electrical appliances as unsorted municipal waste, use separate collection facilities. Contact your local government for information regarding the collection systems available. If electrical appliances are disposed of in landfills or dumps, hazardous substances can leak into the groundwater and get into the food chain, damaging your health and well-being. When replacing old appliances with new ones, the retailer is legally obligated to take back your old appliance for disposal at least for free of charge. Do not throw batteries into the fire, where they can explode or release dangerous liquids. If you replace or destroy the remote control, remove the batteries and throw them away in accordance with the applicable regulations because they are harmful to the environment.

Environmental information: This equipment contains fluorinated greenhouse gases covered by the Kyoto Protocol. It should only be serviced or dismantled by professionally trained personnel. This equipment contains R290 / R32 refrigerant in the amount as stated in the table above. Do not vent R290 / R32 into the atmosphere: R290 / R32 is a fluorinated greenhouse gas with a Global Warming Potential (GWP) = 3.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals