STAHL 210759 miniCLIX Plug Connector Device Owner’s Manual

June 3, 2024
STAHL

Installation Equipment
miniCLIX plug connector Device plug < 2 dm³
8591/291-10-3000 Art. No. 210759

210759 miniCLIX Plug Connector Device

  • Simple installation and maintenance in Zone 1, safe and fast disconnection under load
  • 6+1- pole, rated voltage up to 400 V AC, rated current up to 16 A
  • Suitable for harsh industry environments, IP66/ IP68, for Zones 1 and 2

WebCode 8591B
R. STAHL Series 8591/ 2 7- pole, explosion- protected miniCLIX plug connectors disconnect non- instrinsically safe circuits up to 400 V/ 16 A and are used as a hot swap plug connection for signal and data cables. They are available in various versions and materials: Device plugs, flange sockets, plugs/ couplers made of polyamide, nickel-
plated brass or stainless steel. The cable can be connected using a crimp or spring clamp terminal. Preinstalled cables for device plugs and flange sockets enable fast and safe installation in the end devices.

Technical Data

Explosion Protection

Application range (zones)| 1

2

IECEx gas certificate| IECEx BKI 07.0001X
IECEx gas explosion protection| Ex db eb IIC T6 Gb
ATEX gas certificate| PTB 07 ATEX 1028 X
ATEX gas explosion protection| E II 2 G Ex db eb IIC T6 Gb
Certificates| ATEX (PTB), IECEx (BKI)
Electrical Data
Rated operational voltage AC| 380 – 415 V
Switching capacity| IEC/EN 60947
AC-1: 400 V / 16 A
DC-1: 400 V / 1 ADC-3: 60 V / 0.5 A
Frequency Hz (for AC)| 50

60

Ambient Conditions
Ambient temperature| -55 °C … +40 °C
Note| –  20 … + 40 °C plastic version
–  20 … + 75 °C plastic version Ith max. 1 A
–  55 … + 40 °C metal version
–  55 … + 75 °C metal version Ith max. 1 A
Mechanical Data
Degree of protection (IP)| IP66
Degree of protection note| IP68 (2 m water column, 1 hour) according to IEC/EN 60529 (with protective caps closed and secured as well as properly fitted and secured compo- nents)

Installation Equipment

miniCLIX plug connector Device plug < 2 dm³ 8591/291-10-3000 Art. No. 210759

Mechanical Data

Enclosure material| Nickel-plated brass
Cable entry| M25
Recommended colour ring coding| Blue
Coding (clock hour position)| 10
Detailed number of poles| 6 P + PE
Weight| 0.1 kg
Weight| 0.22 lb
Mounting / Installation
Connection type| 1.5 mm² conductor 30 cm
Components
Locking device present| No
Protective cap available| No

Dimensional Drawings (All Dimensions in mm [inches]) – Subject to Alterations Device plug for Ex d enclosure with volume < 2 dm3   (metal)

Accessories

| | Art. No.
---|---|---


| | 165671


| for plug, device plug: brass, nickel-plated| 154580

Anti- twist protection

**** for flange socket, device plug 154587

Crimping tool

**** for all crimp connection versions up to 4 mm² 109116
for all crimp connection versions up to 4 mm² 109116

We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.

2022-11-16 V 0.59 EN
R. STAHL Schaltgeräte GmbH
Am Bahnhof 30
74638 WALDENBURG
Tel. +49 7942 943 1700
+49 7942 943 1777
Email: [email protected] 
r-stahl.com