LENNOX 603364-29 Enthalpy Sensor Kit
INSTALLATION INSTRUCTIONS
FOR ENTHALPY SENSOR KIT (603364-29; 11G21) USED WITH HIGH PERFORMANCE ECONOMIZERS ON ZG/ZC/ZH 036, 048, 060, 072 & QG/QC/QZ, 036, 042, 048, 060 AND TAA/ELA/EL_XA UNITS
Shipping and Packing List
Package 1 of 1 contains:
- 1 – Temperature and humidity sensor
- 1- Wiring harness (used for differential sensing only)
- 1- Bag assembly containing:
- 2-#10-16 X 5/8” SDST screws
Check packaging for shipping damage. Contact the last carrier immediately if any shipping damage is found.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier
Application
Sensors provide input to determine free cooling suitabil-ity. The enthalpy
sensor provided in this kit senses both sensible temperature and humidity. See
table 1 for usage.
Refer to economizer installation instructions.
Note – Differential sensor applications must use the same two sensors.
TABLE 1
Sensors| Dampers modulate to maintain 55°F mixed air (R1) when:
Single OA Enthalpy Not approved for CA Title 24| OA temperature and humidity
(A7) is lower than free cooling setpoint.
Differential Enthalpy
– 1 in OA & 1 in RA Not approved for CA Title 24
| OA temperature and humidity (A7) is lower than RA temperature and humidity (A62).
CAUTION As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
ZG/ZC/ZH – Single Enthalpy
Note – Install the return air sensor before installing option-al power exhaust dampers and gravity exhaust dampers. If gravity exhaust, power exhaust, or hoods are already installed, remove from unit.
- Disconnect all power to unit.
- Remove filter access panel and return air access panel. If hood is already installed, remove hood. See figure 1.
- Set the DIP switch on kit sensor to appropriate “OA“ setting as indicated on sensor.
- Replace existing RT26 OA sensor with new A7 sensor from this kit. See figure 2 for sensor location.
- On A6 economizer control, remove orange wires going to terminals marked “OAT” and reconnect them to free terminals marked “SBUS”. Discard harness provided in kit. See figure 4.
- Follow economizer installation instruction for setup.
ZG/ZC/ZH – Differential Enthalpy
Note – Install the return air sensor before installing option-al power exhaust dampers and gravity exhaust dampers. If gravity exhaust, power exhaust, or hoods are already installed, remove from unit.
- Disconnect all power to unit.
- Remove filter access and return air access panel. If hood is already installed, remove hood.
- Set the DIP switch on one kit sensor to “OA” setting and the second kit sensor to “RA” setting as indicated on the sensor.
- Replace existing RT26 OA sensor with new A7 kit sensor set to “OA”. See figure 2 for sensor location.
- On A6 economizer control, remove orange wires going to terminals marked “OAT” and reconnect them to free terminals marked “SBUS”. See figure 4.
- Install new sensor from second kit as A62 RA sensorin the return air with screws provided. Be sure not to obstruct the damper movement and not to damage wires.
- Connect harness from EITHER kit between the A62 RA sensor and free “S-BUS” terminals on the A6 economizer control. Be sure to route wires away form moving parts. Discard second harness.
- Follow economizer installation instruction for setup
QG/QC/QH – Single Enthalpy
Note – Differential Enthalpy not available on Q-series units.
Note – Install the return air sensor before installing option-al power
exhaust damper and gravity exhaust damper. If Gravity exhaust, power exhaust
or hoods are already in-stalled, remove from unit.
- Disconnect all power to unit.
- Remove blower access panel. If hood is already installed, remove hood.
- Set the DIP switch on kit sensor to appropriate “OA” setting as indicated on the sensor.
- Replace the outdoor air sensor with the sensor provided in this kit. See figure 3 for sensor install location.
- On the economizer controller, remove wires going to terminals marked “OAT” and reconnect them to free terminals marked “SBUS”. Discard harness provided in kit. See figure 4.
- Follow economizer installation instructions for setup.
TAA/ELA/EL_XA – Single Enthalpy
- Disconnect all power to unit.
- Set the DIP switch on kit sensor to appropriate “OA“ setting as indicated on sensor.
- Replace existing RT26 OA sensor, if applicable, and replace with new A7 sensor from this kit. See figure 5 for sensor location.
- Remove economizer control access panel. See figure 5.
- On A6 economizer control, remove orange wires going to terminals marked “OAT” and reconnect them to free terminals marked “SBUS”. Discard harness provided in kit. See figure 4.
- Follow economizer installation instruction for setup
TAA/ELA/EL_XA – Differential Enthalpy
- Disconnect all power to unit.
- Set the DIP switch on one kit sensor to “OA” setting and the second kit sensor to “RA” setting as indicated on the sensor.
- Replace existing RT26 OA sensor with new A7 kit sensor set to “OA”. See figure 5 for sensor location.
- Remove economizer control access panel. See figure 5.
- On A6 economizer control, remove orange wires going to terminals marked “OAT” and reconnect them to free terminals marked “SBUS”. See figure 4.
- Install new sensor from second kit as A62 RA sensor in the return air with screws provided. Be sure not to obstruct the damper movement and not to damage wires.
- Connect harness from EITHER kit between the A62 RA sensor and free “S-BUS” terminals on the A6 economizer control. Be sure to route wires away form moving parts. Discard second harness.
- Follow economizer installation instruction for setup.