Novus N1030T Temperature Controller Instruction Manual
- June 3, 2024
- Novus
Table of Contents
N1030T Temperature Controller
N1030T Controller
TEMPERATURE CONTROLLER AND TIME INSTRUCTION MANUAL V2.0x (*)
(*) The V2.0x version also covers V1.05 version controllers, except for the
points indicated in the text.
SAFETY ALERTS
The symbols below are used on the equipment and throughout this document to
draw the user’s attention to important operational and safety information
CAUTION:
Read the manual thoroughly before installing and operating
the equipment.
CAUTION OR DANGER: Electrical shock hazard.
All safety related instructions that appear in the manual must be observed to ensure personal safety and to prevent damage to either the instrument or the system. If the instrument is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
INSTALLATION / CONNECTIONS
The controller should be fixed to a panel, following the sequence of steps
below: · Make a cutout in the panel according to the Specifications. · Remove
the controller fixing clip. · Insert the controller into the cutout from the
front of the panel. · Replace the clip on the controller, pressing until it is
well fixed.
INSTALLATION RECOMMENDATIONS
· Input signal conductors should run through the plant separately from output
and supply conductors. If possible, in grounded conduits.
· The power supply for electronic instruments must come from a network
dedicated to the instrumentation.
· The use of RC FILTERS (noise suppressors) in contactor coils, solenoids,
etc. is recommended.
· In control applications, it is essential to consider what can happen when
any part of the system fails. The controller internal devices do not provide
full protection.
ELECTRICAL CONNECTIONS
The figure below shows the connections on the back panel of the controller:
Figure 1 Connections of the back panel
NOVUS AUTOMATION
FEATURES
INPUT TYPE DEFINITION The temperature sensor or input type to be used by the
controller is defined during equipment configuration. Table 01 shows the
available options:
TYPE
CODE
MEASUREMENT RANGE
Thermocouple J Tc j Range: -110.0 to 950.0 °C (-166.0 to 1742 °F)
Thermocouple K Thermocouple T
Tc k Tc t
Range: -150.0 to 1370 °C (-238.0 to 2498 °F) Range: -160.0 to 400.0 °C (-256.0 to 752.0 °F)
Pt100
Pt
Range: -200.0 to 850.0 °C (-328.0 to 1562 °F)
Table 1 Input types
The input type should be the first parameter to be configured. Any modifications on the input type will automatically change other related parameters. When changing the sensor type, you should check the overall condition of the configuration.
OUTPUTS The controller has two outputs, OUT1 and OUT2, which have the
following characteristics:
OUTPUT OUT1 – Logical pulse, 5 Vdc / 25 mA or Output Relay SPST-NA / 1.5 A /
240 Vac
OUTPUT OUT2 – Output Relay SPST-NA / 1.5 A / 240 Vac
These outputs can be configured to operate as Control Output, Alarm Output, or
Output Timers T1 or T2.
CONTROL OUTPUT ((TRL)
The process control output can operate in ON/OFF mode or in PID mode.
To operate in ON/OFF mode, the value set in parameter PB must be 0.0.
With values other than zero in parameter PB, the controller operates in PID
mode. The values for the PID parameters can be set automatically with the help
of Auto Tune (ATvN).
ALARM OUTPUT (A1)
The controller has an alarm that can be directed to any of the outputs. When
enabled, you can configure the alarm to operate with one of the functions
described in Table 02:
off Alarm off.
Alarm of absolute minimum value. It triggers when the lo value of measured PV is below the value defined for alarm Setpoint (SPA1).
PV SPA1
Alarm of absolute maximum
value. It triggers when the PV
ki value of measured PV is
above the value defined for
SPA1
alarm Setpoint (SPA1).
1/7
dif difl
Differential alarm. In this function, SPA1 represents an error (difference) between CONTROL PV and SP.
PV
PV
SP SPA1 SP SP + SPA1
SP + SPA1 SP SP SPA1
Positive SPA1
Negative SPA1
Alarm of minimum differential value. It triggers when the PV value is below the defined point by SP-SPA1.
PV
PV
SP SPA1
SP
SP
SP SPA1
Positive SPA1
Negative SPA1
Alarm of maximum differential. It triggers when the PV value is above the defined point by SP+SPA1.
difk
SP SP + SPA1
PV
PV
SP + SPA1 SP
Positive SPA1
Negative SPA1
ierr
Open sensor alarm. It triggers when the input presents problems such as a broken sensor, poorly connected sensor etc.
Table 2 Alarm functions
Important note: Alarms configured with the ki, dif, and difk functions also trigger their associated output when a sensor fault is identified and signaled by the controller. A relay output, for example, configured to function as a Higher Alarm (ki), will operate when the SPA1 value is exceeded and when the sensor connected to the controller input is broken.
ALARM INITIAL BLOCKING
The Initial Blocking option inhibits the alarm from being triggered if an
alarm condition exists when the controller is turned on. The alarm is
triggered only after the process goes through a non-alarm condition.
The initial blocking is useful, for example, when one of the alarms is
configured as a minimum value alarm, which can cause the alarm to be triggered
as soon as the process is started (a behavior that is often undesired).
The initial block is not valid for the ierr function.
RUN FUNCTION
The RUN function is executed by parameter RvN and works as a general switch
that allows you to enable or disable the operation of the controller.
When enabled (RvN = YES), the controller is free to perform all its functions.
When disabled (RvN = NO), its outputs are turned off, and only the functions
related to temperature measurement and display will continue to operate.
When lit on the controller front panel, the RUN indicator signals that the
control is enabled (RvN = YES).
You can perform this function by using the key, which switches the control
condition between enabled and disabled.
The key must be pressed longer, i.e., > 2 seconds, to disregard accidental
touches.
OFFSET
Function that allows you to make a small adjustment to the PV indication.
Allows you to correct measurement errors that appear, for example, when
replacing the temperature sensor.
N1030T Controller
TIMERS
The controller has two timers, T1 and T2, which have different modes of
operation. Timing starts with T1 and, at the end of T1, starts with T2.
Only the time count of T1 will be shown in the controller display.
When you set ZERO for any of the timers, the timing and sequence will remain
unchanged.
The timers can be associated with any output of the controller: OUT1 or OUT2.
The output associated with T1 turns on during T1 timing, and the output
associated with T2 turns on during T2 timing.
A1 and A2 indicators turn on during T1 and T2 timings, respectively.
At the end of T2, A2 indicator flashes. If T2 = 0, then A1 flashes at the end
of T1. It is possible to configure the controller to disable control (RvN =
OFF) at the end of the timer. In this situation the indicators are also turned
off.
TIMING START MODES There are two starting options:
SP Starts counting when the measured temperature value (PV) reaches the SP value set for the process.
F
Starts the timer by pressing the key (short touch
< 1 s).
After the timer starts, pressing the key briefly allows you to interrupt the timer only (stop and reset).
When RvN = F, pressing the key for a long time (> 2 s) allows you to start the control and the timer.
Pressing the key for a long time allows you to disable control.
Table 3 Timing start modes
The timing start mode is defined in parameter t.str of the controller Timer
Cycle.
BEHAVIOR OF THE TEMPERATURE CONTROL AT THE END OF THE TIMER (T1+T2)
During T1 and T2 interval timing, the temperature control has normal,
independent operation. However, at the end of the T1 + T2 interval, it is
possible to configure the controller to disable temperature control.
In the controller Timer Cycle, the parameter t.e.(.o allows you to set the
desired condition:
on Temperature control continues to operate as usual. off Temperature control
is disabled by turning off the
control output
Table 4 t.e.(.o parameter
UP/DOWN TIMER COUNTING
The time counting for both timers can occur in UP or DOWN mode. In UP mode,
counting starts at zero and runs up to the programmed time interval (T1, T2).
In DOWN mode, it starts at the programmed time value and counts down to zero.
TIMERS TIME BASE
At the end of the Timing Cycle, the parameter TBAS defines the time base to be
used. The options are:
Sec MM:SS. T1 and T2 time intervals are shown in minutes and seconds.
Min HH:MM. T1 and T2 time intervals are shown in hours and minutes.
Table 5 Timers time base
NOVUS AUTOMATION
2/7
OPERATION
The front panel of the controller can be seen in the figure below:
Figure 2 Front panel
Display: Displays the measured variable, configuration parameter symbols and
their respective values/conditions. TUNE Indicator: Stays on while the
controller is in tuning process. RUN Indicator: Indicates that the controller
is enabled to operate. OUT Indicator: Signals the control output status. A1
Indicator: Signals the T1 output status. A2 Indicator: Signals the T2 output
status. A4 Indicator: Signals the alarm status.
Key: Key used to advance the successive parameters and parameter cycles.
Increment key and parameter values.
Decrement key: Keys used to change
Key: Key used to move back parameters during configuration and perform special functions.
OPERATION
When turned on, the controller shows the software version for the first 3
seconds, then it shows the value of the measured process variable (PV) in the
upper display. In the lower display, it shows the SP value. This is the
Indication Screen.
To be used in a process, the controller must be previously configured. To
configure it, each of the various parameters presented must be defined. You
must understand the importance of each parameter and determine a valid
condition or value.
The configuration parameters are gathered in affinity groups, called parameter
cycles. The parameter cycles are:
1 Operation / 2 – Tuning / 3 – Timer / 4 – Input / 5 – Calibration
The key gives access to the cycles and their parameters.
By keeping the key pressed, every 2 seconds the controller jumps from one
cycle to another, presenting the first parameter of each cycle:
PV >> atvn >> t1 >> type >> PASS >> PV …
To enter the desired cycle, simply release the key when the first parameter is displayed. To move forward through the parameters of
that cycle, use the
key. To go backwards through the
parameters, use the key.
The symbol of each parameter is shown in the upper display. Its respective
value/condition is shown in the lower display.
Depending on the configuration protection that you have adopted, the PASS
parameter is shown as the first parameter of the cycle where the protection
starts. See Configuration Protection chapter.
N1030T Controller
PARAMETERS DESCRIPTION
OPERATION CYCLE
PV PV Indication Screen. The upper (red) display shows SP the measured
temperature value (PV).
The lower display (green) shows the control Setpoint
value (SP), which is the desired value for the process
temperature.
PV Display PV and current timer count. The upper
TM
display (red) shows the measured temperature value (PV).
The lower display (green) shows the current T1 timer count. You cannot set this display.
T1
Timer 1
T1 time interval. From 00:00 to 99:59 (HH:MM or MM:SS).
Parameter shown in this cycle when set in parameter T.en.
Rvn Enables or disables the controller to act on the Run process. Acts as a
switch, turning the controller on or
off.
YES Enabled control.
NO Disabled control.
F Enable/disable command via key (*).
Parameter shown in this cycle when set in parameter r.en.
Spa1 Alarm SP. Value that defines the alarm actuation point. For Differential type functions, this parameter specifies error (**) (***).
() When set to RVN = F, the control will be disabled (NO) when you turn on
the controller or when it returns from a power failure.
() This parameter is not displayed when the alarm function is set to off or
ierr.
() This parameter is not available for version 1.0x of the controller.
TUNING CYCLE
Atvn
AUTO-TUNE. Enables the automatic tuning of the PID parameters (pb,ir, dt). See
PID Parameters Definition chapter.
off Auto-tune off.
Fast Perform tuning in fast mode.
Full Perform tuning in precise mode.
PB Proportional Band. Value of the term P of the control mode PID, in
percentage of the maximum span of the input type.
Adjustable between 0 and 500.0 %.
When set to zero (0), control action is ON/OFF.
ir Integral Rate. Value of the term I of the PID algorithm, in repetitions per minute (Reset). Adjustable between 0 and 24.00. Displayed only if proportional band 0.
dt Derivative Time. Value of the term D of the control mode PID, in seconds.
Adjustable between 0 and 250 seconds.
Displayed only if proportional band 0.
(t Cycle time. Pulse Width Modulation (PWM) period in seconds. Adjustable
between 0.5 and 100.0 seconds.
Displayed only if proportional band 0.
NOVUS AUTOMATION
3/7
kyst A(t
0vt.1 0vt.2
Control hysteresis. Hysteresis value in degrees for ON/OFF control.
Adjustable between 0 and the measurement range width of the selected input
type.
Action control:
re Control with Reverse Action. Appropriate for heating. Turns control output
on when PV is below SP.
dir Control with Direct Action. Appropriate for cooling. Turns control output
on when PV is above SP.
Operation mode of OUT1 and OUT2 outputs:
Off Not used.
(trL Acts as a temperature controller.
A1
Acts as alarm output.
t1
Acts as T1 timer output.
t2
Acts as T2 timer output.
TIMER CYCLE
T1 Allows setting T1 time interval. From 00:00 to 99:59 Timer 1 (MM:SS or
HH:MM).
T1.en Allows displaying the T1 parameter in the main Timer Enable (operating)
cycle.
Yes Shows T1 in the Operating cycle. No Hides T1 from the Operating cycle.
T.dir Counting direction of T1 timer: Timer Direction vp Up counting, starting
from zero.
Dn Down counting.
T.str Defines starting mode for T1 timer. Timer Start sP Starts when PV
reaches SP.
f
key starts the timing.
T2
Timer 2
Allows setting the time interval T2. From 00:00 to 99:59 (MM:SS or HH:MM).
Time interval that output T2 will remain on after the end of timing T1.
T.e.(.o Control output behavior after T1 + T2 interval.
Timer End Control Off ?
on Control output remains active.
off Turns off the control at the end of the timer.
tbas
time base
Time base for T1 and T2 timers. Sec Minutes and seconds (MM:SS). Min Hours and minutes (HH:MM).
INPUT CYCLE
Type
Input Type: Sets the input type used by the controller:
J:
Tc J -110 to 950 °C / -166 to 1742 °F
K:
Tc k -150 to 1370 °C / -238 to 2498 °F
T:
Tc t -160 to 400 °C / -256 to 752 °F
Pt100: Pt -200 to 850 °C / -328 to 1562 °F
Dp.po Decimal point. Sets the presentation mode of the decimal point.
vni t Sets the temperature unit to be used: ( Indication in Celsius.
f Indication in Fahrenheit.
NOVUS AUTOMATION
N1030T Controller
offs Offset. Parameter that allows you to make corrections to the indicated PV value.
Spll Spxl
Fva1
SP Low/High Limit. Sets the lower/upper limits for adjustments to the control
SP value. Does not limit the setting of the Alarm SP value.
Alarm functions. Sets the alarm functions from the options in Table 02.
Sp.a1 Alarm SP. Sets the alarm actuation point. For Differential type functions, this parameter defines the error (**).
Bla1
Blocking Alarm. This function blocks the alarms (**). YES Enables initial blocking. NO Inhibits initial blocking.
Xya1 Sp1.e
Alarm hysteresis. Sets the difference between the PV value at which the alarm
is turned on and the value at which it is turned off ().
Allows to display Sp.a1 parameter in the controller Operation Cycle ()
(***).
YES Displays Sp.a1 parameter in the Operation Cycle.
No Does not display Sp.a1 parameter in the Operation Cycle.
(**) This parameter is not displayed when the alarm function is set to off or
ierr.
(***) This parameter is not available for version 1.0x of the controller.
CALIBRATION CYCLE
All types of input are calibrated in the factory. In case a recalibration is
required; it shall be conducted by a specialized professional. In case this
cycle is accidentally accessed, do not perform alteration in its parameters.
pass
Password. This parameter is shown before the protected cycles. See Configuration Protection chapter.
(alib
Calibration. Allows you to enable the function to calibrate the controller. When the function is not enabled, the calibration of the related parameters will remain hidden.
inL(
Input Low Calibration. Allows you to enter the value corresponding to the low scale signal applied to the analog input.
ink(
Input High Calibration. Allows you to enter the value corresponding to the full-scale signal applied to the analog input.
rstr Restore. Allows you to reset the input factory calibrations, disregarding all changes made.
Pas.( Password Change. Allows you to set a new access password, always different from zero.
Prot Protection. Allows you to define the protection cycle. See Table 06.
r.en Displays RUN (rvn) parameter also in the Operation RUN Enable Cycle.
Yes Releases RUN for the Operation cycle.
no Does not release RUN for the Operation cycle.
Rvn Enables or disables the controller to act on the Run process. Acts as a
switch, turning the controller on or
off.
YES Enabled control.
4/7
NO Disabled control.
F Enable/disable command via key (). Parameter shown in this cycle when
set in parameter r.en.
() When set to RVN = F, the control will be disabled (NO) when you turn on
the controller or when it returns from a power failure.
CONFIGURATION PROTECTION
The controller allows you to protect its configuration, preventing undue
changes. In the Calibration cycle, the Protection parameter (PROt) determines
the protection cycle to be adopted, limiting access to the cycles, as shown in
the table below:
PROTECTION CYCLE 1 2 3
4
5
PROTECTION CYCLES
Only the Calibration cycle is protected. Calibration and Input cycles are
protected. Calibration, Input, and Timers cycles are protected. Calibration,
Input, Timers and Tuning cycles are protected. All cycles are protected,
including SP. Table 6 Protection cycles
ACESS PASSWORD
To access the Calibration cycle, a password is required. If entered correctly,
it allows changing the configuration of the parameters of these cycles,
including the Protection parameter (PROt).
You can set the password in the Password Change parameter (PAS.(), which is
also present in the Calibration cycle. The controllers leave the factory with
the password set to 1111.
PROTECTION ACCESS PASSWORD
The controller has a security system that helps prevent the entry of numerous
passwords to guess the correct password. Once 5 consecutive invalid passwords
are identified, the controller stops accepting passwords for 10 minutes.
MASTER PASSWORD
If you forget the password, you can use the Master Password feature. When
entered, this password gives access and allows changing the Password Change
parameter (PAS(). This makes it possible to set a new password for the
controller.
The master password is formed by the last three digits of the controller
serial number plus the number 9000.
Example: For a device with serial number 07154321, the master password is
9321.
You can get the serial number of the controller by pressing key for 5 seconds.
PID PARAMETERS DEFINITION
During auto-tuning, the process is controlled in ON/OFF mode at the programmed
setpoint (SP). In some processes the auto-tuning can take many minutes to
complete. The recommended procedure for its execution is:
· Set the desired SP value for the process.
· On the Atvn screen, enable automatic tuning by selecting FAST or FULL.
The FAST option performs the tuning in the minimum possible time. The FULL
option prioritizes a more precise tuning.
NOVUS AUTOMATION
N1030T Controller
During automatic tuning, the TUNE indicator remains lit on the front of the
controller. You must wait until the tuning is finished before you can use the
controller.
During the execution of the automatic tuning, it is possible to induce PV
oscillations in the process around the setpoint.
If the tuning does not result in satisfactory control, Table 04 presents
guidelines on how to correct the process behavior:
PARAMETER
VERIFIED PROBLEM SOLUTION
Band Proportional
Slow answer Great oscillation
Decrease Increase
Rate Integration
Slow answer Great oscillation
Increase Decrease
Derivative Time
Slow answer or instability Great oscillation
Decrease Increase
Table 7 Guidance for manual adjustment of the PID parameters
FACTORY CONFIGURATION
OPERATION CYCLE
PARAMETER
DESCRIPTION
PARAMETER FACTORY
PV
PV Indication screen.
0
SP
PV
PV and current timer count screen.
–
TM
T1
Set the T1 time interval.
0.00
Screen that enables or disables Rvn the controller action on the no
process.
Table 8 Factory configuration: Operation
TUNING CYCLE
PARAMETER
DESCRIPTION
PARAMETER FACTORY
Atvn
Enables the auto-tuning function for PID parameters (pb,ir, dt).
off
PB
Proportional band.
0.0
ir
Integral rate.
0.00
dt
Derivative time
0
(t
Cycle time PWM.
5.0
kyst Control hysteresis.
1
A(t Action control.
RE
0vt.1
Operation mode of OUT1 and OUT2 outputs.
off
Table 9 Factory configuration: Tuning
TIMER CYCLE
PARAMETER
DESCRIPTION
PARAMETER FACTORY
T1
T1 time interval setting.
0.00
T1.en
Allows displaying T1 parameter in the main (operating) cycle.
yes
T.dir Counting direction of T1 timer.
UP
T.str
Defines starting mode for T1 timer.
SP
5/7
PARAMETER
DESCRIPTION
PARAMETER FACTORY
T2
T2 time interval setting.
0:20
T.e.(.o
Control output behavior after T1 + T2 interval.
on
tbas Time base for T1 and T2 timers.
sec
Table 10 Factory configuration: Timer
INPUT CYCLE
PARAMETER
DESCRIPTION
Type Input type.
PARAMETER FACTORY
J
Dp.po Selects the decimal point position.
0
vni t
Selects display indication: Celsius or Fahrenheit.
c
offs
Parameter that allows to adjust the PV value indicated.
0
Spll Spxl
Defines the lower/upper limit for SP adjustment.
-110 / 950 (limits do sensor J)
FvaL Alarm functions.
off
Sp.aL Alarm SP.
0
BlaL Alarm initial blocking.
no
XyaL Alarm hysteresis.
0
Table 11 Factory configuration: Input
CALIBRATION CYCLE
PARAMETER
DESCRIPTION
PARAMETER FACTORY
pass Access password Input.
0000
(alib Enables calibrating the indicator.
no
inL(
Enter the value corresponding to the low scale signal applied to the analog input.
0000
inK(
Enter the value corresponding to the full-scale signal applied to the analog input.
0000
rstr Restores input factory calibration.
no
Pas.( Restores input factory calibration. 0000
Prot Sets up the protection cycles.
1
r.en
Shows the parameter RUN (rvn) yes also in the Operation Cycle.
Rvn
Display for enable or disable the controller action on the process.
no
Table 12 Factory configuration: Calibration
N1030T Controller
MAINTENANCE
PROBLEMS WITH THE CONTROLLER
Wiring errors and improper programming represent most of the problems that can
occur when using the controller. A final review can avoid wasted time and
losses.
The controller presents some messages that are intended to help you identify
problems.
MESSAGE
PROBLEM DESCRIPTION
—- Open input. No sensor or signal.
Err1 Err6
Connection and/or configuration problems. Check the wiring and the configuration.
Table 13 Error messages
Other error messages displayed by the controller represent internal damages that necessarily imply sending the equipment for maintenance.
INPUT CALLIBRATION All controller input types leave the factory already
calibrated. Recalibration is not recommended for inexperienced operators. If
it is necessary to recalibrate an input, proceed as follows: a) In the type
parameter, set the input type to be calibrated. b) Program the lower and upper
SP limits for the extremes of the input type. c) Access the Calibration cycle.
d) Enter the access password. e) In parameter (alib, enable the calibration by
setting YES. f) With an electrical signal simulator, apply to the input
terminals a signal near the lower limit of the configured input measurement
range.
g) In the nL( parameter, use the and keys to make the display indicate the
expected value for the applied signal. Then press
the key. h) Apply a signal near the upper limit of the configured input
measurement range to the input terminals.
i) In the ink( parameter, use the and keys to make the display indicate the
expected value for the applied signal. Then,
press the key until returning to the PV Indication Screen. j) Validate the
calibration. Note: When checking the controller calibration with a Pt100
simulator, pay attention to the simulator minimum excitation current
requirement, which may not be compatible with the 0.170 mA excitation current
provided by the controller.
NOVUS AUTOMATION
6/7
SPECIFICATIONS
DIMENSION: ……………………………………………………..48 x 48 x 35 mm Approximate weight:
……………………………………………………… 60 g
POWER SUPPLY: Standard Model ……………………100 to 240 Vac (±10 %), 50/60 Hz
…………………………………….. 48 to 240 Vdc (±10 %) 24 V Model:………………….. 12 to 24 Vdc / 24
Vac (-10 % / +20 %) Maximum Consumption:……………………………………………….. 5 VA
ENVIRONMENTAL CONDITIONS: Operation Temperature: ……………………………………….. 0 to 50 °C
Relative Humidity:…………………………………………… 80 % @ 30 °C For temperatures above 30 °C,
reduce 3 % for each °C Internal use; Category of installation II, Pollution
Degree 2; altitude < 2000 meters
INPUT: ….. Thermocouples J; K; T and Pt100 (according of Table 01) Internal
Resolution:……………………………….. 32767 levels (15 bits) Display Resolution:……………..
12000 levels (from -1999 up 9999) Rate of input reading: …………………………………….up 5
per second Accuracy: ..Thermocouples J, K, T: 0.25 % of the span ±1 °C (*)
……………………………………………………….Pt100: 0.2 % of the span Input impedance: ………………Pt100
and thermocouples: > 10 M Pt100 Measurement: ……………………….. 3-wire type, (=
0.00385) With compensation for cable length. Excitation current of 0.170 mA.
OUTPUTS: OUT1: …………………………..Voltage pulse, 5 Vdc / 25 mA ……………….Relay SPST; 1.5
A / 240 Vac / 30 Vdc
OUT2: ………………Relay SPST; 1.5 A / 240 Vac / 30 Vdc FRONT PANEL: ……………………. IP65,
Polycarbonate (PC) UL94 V-2 HOUSING: ……………………………………………. IP30, ABS+PC UL94 V-0
ELECTROMAGNETIC COMPATIBILITY: …………… EN 61326-1:1997 and EN 61326-1/A1:1998
EMISSION: …………………………………………………… CISPR11/EN55011 IMMUNITY:………………….EN61000-4-2,
EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-8 and
EN61000-4-11 SAFETY: …………………….. EN61010-1:1993 and EN61010-1/A2:1995 SPECIFIC
CONNECTIONS FOR PIN TERMINALS. PWM PROGRAMABLE CYCLE: From 0.5 up 100 seconds.
START-UP: After 3 seconds connected to the power supply. CERTIFICATIONS: CE,
UKCA, UL.
IDENTIFICATION
N1030T –
A –
B
A: Outputs Features PR: OUT1 = Pulse / OUT2 = Relay RR: OUT1 = Relay / OUT2 =
Relay
B: Power Supply (Blank): ………………………………………………………..Model standard ……………………….
100~240 Vac / 48~240 Vdc; 50~60 Hz 24V: …………………………………………………………………. Model 24 V
……………………………………………………….12~24 Vdc / 24 Vac
WARRANTY
The warranty conditions are on our website www.novusautomation.com/warranty.
NOVUS AUTOMATION
N1030T Controller
7/7
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>