EMERSON Copeland Water Cooled Scroll Condensing Units User Manual
- June 3, 2024
- Emerson
Table of Contents
- Introduction
- Safety Information
- Nomenclature
- Dimensional Drawings & Data
- Envelopes
- Electrical Data – 50Hz
- Fluid data – 50Hz
- Features & Benefits
- Physical Layout of Condensing Unit
- Scope of Supply
- Electrical Connections
- Installation, System Processing and Commissioning
- Initial pressure test (by vacuum and nitrogen)
- Charging and commissioning
- System Start-Up and Operational Check Sheet
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Copeland Water Cooled Scroll Condensing Units
User Manual
Introduction
Emerson Water-Cooled Scroll Condensing Units are fitted with high efficient
Copeland Scroll Compressors.
This document is designed to help the contractor and customer for the
installation, commissioning & operation of Emerson’s Water-Cooled Scroll
Condensing Unit.
Scope of supply – Check page number 10 of this manual for detailed scope of
supply.
Disclaimer
Thank you for purchasing the Emerson™ Water-Cooled Scroll Condensing Unit. We
hope that this product meets your intended refrigeration requirement. Please
read through this operation manual to familiarize yourself with the
installation, commissioning, and operation of this product. Please do read the
following information in this page before proceeding with the rest of the
manual.
The Emerson™ Water-Cooled Scroll refrigeration condensing units should only be
installed by suitably qualified and experienced refrigeration technicians. No
responsibility can be accepted for damage caused by inexperienced or
inadequately trained site technicians or improper system design. All
instructions and procedures described in this manual are based on good
refrigeration trade practices as applicable to this particular product.
The installation contractor may prefer to use variations to these
recommendations. However, the methods described in this manual represent the
minimum requirements to avoid any subsequent warranty claims for this
equipment and its components. These instructions do not cover the fundamentals
of good electrical or refrigeration practice and are therefore intended for
use only by qualified and/or experienced personnel or technicians.
For any additional query, please consult your local sales office, quoting unit
model and serial number as shown on the nameplate. In case of ambiguity, the
wiring diagram supplied with each unit takes precedence over the diagram in
this manual.
Safety Information
1.1 Installation and commissioning work on CDU shall be carried out only by
qualified, refrigeration personnel who have been trained and instructed.
1.2 Water Cooled Scroll Condensing Unit is manufactured according to the
latest safety standards. Emphasis has been placed on the user’s safety. For
relevant standards please refer to the manufacturer’s declaration, available
on request. You are strongly advised to follow these safety instructions.
1.3 Icon explanation
1.4 Safety Statements
a. Only qualified and authorized refrigeration personnel are permitted to
install, commission and maintain this equipment.
b. Electrical connections must be made by qualified electrical personnel.
c. All valid standards for connecting electrical and refrigeration equip- ment
must be observed.
d. The national legislation and regulations regarding personnel protection
must be observed.
Use personal safety equipment. Safety goggles, gloves, protective clothing,
safety boots and hard hats should be worn where necessary.
1.5 General Instructions
WARNING
System breakdown! Personal injuries! Never install a system in the field and
leave it unattended when it has no charge, a holding charge, or with the
service valves closed without electrically locking out the system.
System breakdown! Personal injuries! Only approved refrigerants and
refrigeration oils must be used.
WARNING
High shell temperature! Burning! Do not touch the compressor until it has
cooled down. Ensure that other materials in the area of the compressor do not
get in touch with it. Lock and mark accessible sections.
CAUTION
Overheating! Bearing damage! Do not operate compressors without refrigerant
charge or without being connected to the system.
CAUTION
Compressors contain oil & refrigerant under pressure. Release pressure from
both high & low side of compressor before servicing.
CAUTION
Tube brazing & compressor operation can produce hot surfaces. To avoid burns,
allow surfaces to cool.
1.6 Safety Refrigerants/Lubricant
a. Please use correct refrigerant as designed to work in safe operating
envelope.
b. Compressor is supplied with an initial oil charge. The standard oil charge
for use with HFC refrigerant is polyol ester (POE) lubricant Emkarate RL 32
3MAF.
Nomenclature
Dimensional Drawings & Data
Mechanical Data – 50Hz
Condensing Unit Model| Compressor Model| Receiver
Capacity
(I)| Depth/Width
(D/W) (mm)| Height [H)
(mm)| Suction 0
(SL) (“)| Liquid 0
[LL] n| Water
Inlet FPT
C)| Water
Outlet ODF
(“)| Net
Weight
(Kg)| Gross
Weight
(Kg)
---|---|---|---|---|---|---|---|---|---|---
FDCKA-ZS09-TFM| ZSO9KAE-TFD-600| 4.| 460/618| 495| 5/8| 1/2| 3/8| 5/8| 39| 49
FDCKA-ZS11-TFM| ZS11KAE-TFD-600| 4.| 460/618| 495| 5/8| 1/2| 3/8| 5/8| 39| 49
FDCKA-ZS13-TFM| ZS13KAE-TFD-600| 4.| 460/618| 495| 5/8| 1/2| 3/8| 5/8| 39| 49
FMCKA-ZB15-TFM| ZB15KQE-TFD-559| 4.| 460/610| 471| 3/4| 1/2| 3/8| 5/8| 42| 52
FMCKA-Z1319-TFM| ZB19KQE-TFD-559| 4.| 460/610| 471| 3/4| 1/2| 3/8| 5/8| 44| 54
FMCKA-ZB21-TFM| ZB21 KQE-TFD-559| 4.| 460/610| 494| 3/4| 1/2| 3/8| 5/8| 44| 54
FMCNA-ZB26-TFM| ZB26KQE-TFD-559| 8.| 570/680| 510| 7/8| 1/2| 3/4| 7/8| 62| 77
FMCNA-ZB29-TFM| ZB29KQE-TFD-559| 8.| 570/680| 527| 7/8| 1/2| 3/4| 7/8| 66| 81
FMCNA-Z838-TFM| ZB38KQE-TFD-559| 8.| 570/680| 545| 11/8| 1/2| 3/4| 7/8| 70| 85
FMCNA-ZB45-TFM| ZB45KQE-TFD-559| 8.| 570/680| 545| 11/8| 1/2| 3/4| 7/8| 72| 87
FMCPA-Z848-TFM| ZB48KQE-TFD-559| 8.| 610/725| 559| 1 1/8| 1/2| 3/4| 1 1/8| 76|
91
FLCKA-ZFO6-TFM| ZFO6KQE-TFD-551| 4.| 460/610| 477| 3/4| 1/2| 3/8| 5/8| 42| 52
FLCKA-ZFO9-TFM| ZFO9KQE-TFD-551| 4.| 460/610| 499| 3/4| 1/2| 3/8| 5/8| 44| 54
FLCNA-ZF11-TFM| ZF11KQE-TFD-551| 8.| 570/680| 515| 7/8| 1/2| 3/4| 7/8| 61| 76
FLCNA-ZF13-TFM| ZF13KQE-TFD-551| 8.| 570/680| 545| 7/8| 1/2| 3/4| 7/8| 71| 86
FLCNA-ZF15-TFM| ZF15KQE-TFD-551| 8.| 570/680| 545| 11/8| 1/2| 3/4| 7/8| 72| 87
FLCNA-ZF18-TFM| ZF18KQE-TFD-551| 8.| 570/680| 545| 1 1/8| 1/2| 3/4| 7/8| 74|
89
Mechanical Data – 60Hz
Condensing unit model| Compressor model| Receiver capacity
(l)| Depth/ width
[D/W] (mm)| Height [H] (mm)| Suction Ø[SL] (″)| Liquid Ø[LL] (″)| Water
inlet FPT
(″)| Water outletODF (″)| Net
weight
(kg)| Gross
weight
(kg)
---|---|---|---|---|---|---|---|---|---|---
FMCKA-ZS 11-TF7| ZS11KAE-TF7-600| 3.9| 460/610| 495| 8-May| 2-Jan| 8-Mar|
8-May| 39| 49
FMCKA-ZB 15-TF7| ZB15KQE-TF7-559| 3.9| 460/610| 471| 4-Mar| 2-Jan| 8-Mar|
8-May| 42| 52
FMCKA-ZB 19-TF7| ZB19KQE-TF7-559| 3.9| 460/610| 471| 8-Jul| 2-Jan| 8-Mar|
8-May| 44| 54
FMCNA-ZB 21-TF7| ZB21KQE-TF7-559| 7.9| 570/680| 496| 8-Jul| 2-Jan| 4-Mar|
8-Jul| 60| 75
FMCNA-ZB 26-TF7| ZB26KQE-TF7-559| 7.9| 570/680| 510| 8-Jul| 2-Jan| 4-Mar|
8-Jul| 62| 77
FMCNA-ZB 29-TF7| ZB29KQE-TF7-559| 7.9| 570/680| 527| 1 1/8| 2-Jan| 4-Mar|
8-Jul| 66| 81
FMCNA-ZB 38-TF7| ZB38KQE-TF7-559| 7.9| 570/680| 545| 1 1/8| 2-Jan| 4-Mar|
8-Jul| 71| 86
FMCPA-ZB 45-TF7| ZB45KQE-TF7-559| 7.9| 610/725| 555| 1 1/8| 2-Jan| 4-Mar|
1/1/2008| 76| 91
FLCKA-ZF 06-CFV| ZF06KQE-PFV-551| 3.9| 460/610| 477| 4-Mar| 2-Jan| 8-Mar|
8-May| 45| 55
FLCNA-ZF 09-CFV| ZF09KQE-PFV-551| 7.9| 570/680| 501| 4-Mar| 2-Jan| 4-Mar|
8-Jul| 62| 77
FLCNA-ZF 11-CFV| ZF11KQE-PFV-551| 7.9| 570/680| 515| 8-Jul| 2-Jan| 4-Mar|
8-Jul| 62| 77
FLCNA-ZF 13-TF7| ZF13KQE-TF7-551| 7.9| 570/680| 546| 8-Jul| 2-Jan| 4-Mar|
8-Jul| 73| 88
FLCNA-ZF 15-TF7| ZF15KQE-TF7-551| 7.9| 570/680| 546| 1 1/8| 2-Jan| 4-Mar|
8-Jul| 73| 88
FLCPA-ZF 18-TF7| ZF18KQE-TF7-551| 7.9| 610/725| 546| 1 1/8| 2-Jan| 4-Mar|
1/1/2008| 76| 91
Envelopes
Electrical Data – 50Hz
Condensing Unit Model| Compressor Model| Compressor Maximum
Operating Current (A)| Compressor Locked
Rotor Current (A)
---|---|---|---
FDCKA-ZS09-TFM| ZSO9KAE-TFD-600 3.0 27.0
FDCKA-ZS11-TFM| ZS11KAE-TFD-600| 3.| 27.0
FDCKA-ZS13-TFM
FMCKA-ZB15-TFM
FMCKA-ZB19-TFM| ZS13KAE-TFD-600 4.0 29.0
ZB15KQE-TFD-559| 5.| 26.0
ZB19KQE-TFD-559 6.5 32.0
FMCKA-ZB21-TFM| ZB21 KQE-TFD-559| 7.| 40.0
FM CNA-ZB26-TFM FM CNA-ZB29-TFM FM CNA-ZB38-TFM FM CNA-ZB45-TFM FM CPA-Z
B48-TFM| ZB26KQE-TFD-559 8.9 46.0
ZB29KQE-TFD-559| 10.0| 50.0
ZB38KQE-TFD-559 12.8 65.5
ZB45KQE-TFD-559| 13.| 74.0
ZB48KQE-TFD-559 14.0 101.0
FLCKA-Z F06-TFM| ZFO6KQE-TFD-551| 5.0| 26.0
FLCKA-Z F09-TFM ZFO9KQE-TFD-551 6.0 40.0
FLCNA-Z F11-TFM| ZF11KQE-TFD-551| 7.| 46.0
FLCNA-ZF13-TFM ZF13KQE-TFD-551 8.0 51.5
FLCNA-ZF15-TFM| ZF15KQE-TFD-551| 10.0| 64.0
FLCNA-ZF18-TFM ZF18KQE-TFD-551 12.5 74.0
Electrical Data – 60Hz
Condensing unit model| Compressor model| Compressor maximum
operating current (A)| Compressor locked
rotor current (A)
---|---|---|---
FM CKA-ZS 11-TF7| ZS11KAE-TF7-600| 3.9| 29
FM CKA-ZB 15-TF7| ZB15KQE-TF7-559| 5.1| 27
FM CKA-ZB 19-TF7| ZB19KQE-TF7-559| 6| 30
FM CNA-ZB 21-TF7| ZB21KQE-TF7-559| 7.2| 39
FM CNA-ZB 26-TF7| ZB26KQE-TF7-559| 8.8| 41
FM CNA-ZB 29-TF7| ZB29KQE-TF7-559| 10| 54
FM CNA-ZB 38-TF7| ZB38KQE-TF7-559| 13| 64
FM CPA-ZB 45-TF7| ZB45KQE-TF7-559| 13.1| 70
FLCKA-ZF 06-CFV| ZF06KQE-PFV-551| 17.1| 61
FLCNA-ZF 09-CFV| ZF09KQE-PFV-551| 20.2| 88
FLCNA-ZF 11-CFV| ZF11KQE-PFV-551| 24.7| 109
FLCNA-ZF 13-TF7| ZF13KQE-TF7-551| 10| 57
FLCNA-ZF 15-TF7| ZF15KQE-TF7-551| 12| 64
FLCPA-ZF 18-TF7| ZF18KQE-TF7-551| 14| 70
Fluid data – 50Hz
Medium temperature
Low temperature
Fluid data – 60Hz
Low temperature
Note: Operating conditions : 20°C suction gas return temperature and 3K subcooling
Features & Benefits
Efficiency
– High efficiency Copeland™ ZB/ZF/ZS compressors for multiple application.
Reliability
– Compressors are supplied with internal thermal protectors that safeguards
against motor overheating and high current.
– Dual compliance for better reliability.
Smooth Operation
– Scroll compressor has an inbuilt check valve that isolates high pressure
gas, allowing the compressor to start unloaded with low inrush currents.
– Less vibration.
Maintenance
– Optimal layout of components for easy serviceability.
Physical Layout of Condensing Unit
Scope of Supply
- High efficiency scroll compressor
- Co-axial condenser
- Compressor with Oil Sight Glass and Crank Case Heater
- HP/LP switch
- Condenser pressure regulator to be provided by the customer as required.
The Condenser Pressure Regulator could be selected from below table. This could be provided as additional accessory.
New Models | Condenser Pressure Regulator PCN |
---|---|
FDCKA-ZS09-TFM-0 | 510-0049-00 |
FDCKA-ZS11-TFM-0 | 510-0049-00 |
FDCKA-ZS13-TFM-0 | 510-0049-00 |
FMCKA-ZB15-TFM-0 | 510-0049-00 |
FMCKA-ZB19-TFM-0 | 510-0049-00 |
FMCKA-ZB21-TFM-0 | 510-0049-00 |
FMCNA-ZB26-TFM-0 | 510-0049-02 |
FMCNA-ZB29-TFM-0 | 510-0049-02 |
FMCNA-ZB38-TFM-0 | 510-0049-02 |
FMCNA-ZB45-TFM-0 | 510-0049-02 |
FMCPA-ZB48-TFM-0 | 510-0049-02 |
FLCKA-ZF06-TFM-0 | 510-0049-00 |
FLCKA-ZF09-TFM-0 | 510-0049-00 |
FLCNA-ZF11-TFM-0 | 510-0049-02 |
FLCNA-ZF13-TFM-0 | 510-0049-02 |
FLCNA-ZF15-TFM-0 | 510-0049-02 |
FLCNA-ZF18-TFM-0 | 510-0049-02 |
Electrical Connections
Installation, System Processing and Commissioning
Utmost care must be taken while handling the Water-Cooled Scroll condensing
unit. Please go through the contents below to ensure proper handling.
a. Inspection
Inspect the condensing unit and any accessories shipped with them for damages
or shortages before and during unloading. All items on bill of lading should
be accounted for prior to signing the shipping receipt. Note any shortages or
damage on delivery receipt (specify the extent and type of damage found). Unit
should be inspected carefully for concealed damage.
Notify Emerson sales/application personnel of the damage immediately. Do not
repair the unit until instructed by Emerson’s representative.
The system is shipped with a holding charge of dry nitrogen. Check to see that
pressure is still in the unit upon receipt. Report lack of pressure
immediately to the Emerson’s application/sales representative.
b. Location and Fixing
Generally installed on the top of the cold room to reduce the connection
length between the condensing unit and the evaporator. Enough space to be
provided around the unit for easy service. Also ensure easy access to the
unit.
c. Refrigeration Piping Installation
All interconnecting pipes should be of refrigeration grade, clean, dehydrated
and must remain capped at both ends until installation. Even during
installation, if the system is left for any reasonable period (say two
hours), pipes should be re- capped to prevent moisture and contaminants from
entering the system.
Do not assume that the service connection sizes on the unit (at the service
valves) are the correct size to run your interconnecting refrigeration pipes.
The service valve sizes have been selected for convenience of installation and
in some cases (larger units) these may be considered too small. However, for
the very short pipe run within our units, these service connection sizes are
adequate.
The pipe should be sized to ensure optimum performance and proper oil return.
The sizing must also consider the full capacity range through which this
particular unit will need to operate.
Pipe runs should be kept as short as possible, using the minimum number of directional changes. Use large radius bends and avoid trapping of oil and refrigerant. This is particularly important for the suction line. The suction line should ideally slope gently towards the unit. Recommendation slope is 1/200~1/250. P traps, double risers and reduced pipe diameters may be required for suction lines where long vertical risers cannot be avoided. All pipes should be adequately supported to prevent sagging which can create oil traps.
The recommended pipe clamp support distance is shown in the table.
1/2 inch | Max distance between 2 clamp supports |
---|---|
Tube Dia | 1.2 M |
5/8 inch | 1.5 M |
7/8 inch | 1.8M |
1 1/8 inch | 2.1M |
1 3/8 inch | 2.3M |
d. Refrigerant line insulation
– Insulate suction lines from the evaporators to the condensing unit with
minimum of 1” thickness closed-cell type insulation.
– Long liquid lines run in areas exposed to high temperatures should be fully
insulated with minimum 1/2” insulation.
– Suction and liquid lines should never be taped or soldered together.
e. Electrical
– All electrical work must be done in accordance with the National Electrical
Code and existing local codes.
– Power supply must be the same as specified on the unit’s name plate.
– Voltage fluctuations in excess of 10 percent must be corrected.
– Before starting the unit, ensure that all protective devices are in place
and that all wiring is secure.
f. Brazing Recommendation
Maintain a flow of oxygen-free nitrogen through the system at a very low
pressure during brazing. Nitrogen displaces the air and prevents the formation
of copper oxides in the system. If copper oxidization is allowed to form, the
copper oxide material can later be swept through the system and block screens
such as those protecting capillary tubes, thermal expansion valves, and
accumulator oil return holes. This minimizes any entry of contaminants and
moisture.
- Remove the liquid line connection cap.
- Then remove the suction connection cap.
- Open both valves midway.
- Care should be taken to avoid the holding charge from releasing too quickly.
- Be sure tube fitting inner diameter and tube outer diameter are clean prior to assembly.
- Recommended brazing materials: a copper / phosphorous or copper /phosphorous / silver alloy rod should be used for joining copper to copper whereas to join dissimilar or ferric metals, use a silver alloy rod, either flux coated or with a separate.
- Use a double tip torch.
g. Start-up & Operation
Initial pressure test (by vacuum and nitrogen)
Step-by-step
- Use a 4-port gauge manifold with 3/8” hose and connections to the vacuum pump. The vacuum gauge does not have to be connected for this part of the process.
- Connect the gauges to service ports provided on receiver valve and suction tube. In order to remove any non-condensable that may have entered the system during installation, follow these steps:
- Start the vacuum pump. The evaporator fan should be running and the compressor crankcase heater is energized at this point. This will involve powering up the unit so it is important to disconnect the live feed wire to the compressor contactor (so the compressor cannot run and the crank case heater can be energized).
- Open both valves on the manifold and then open the main vacuum valve on the pump. Run the system until the vacuum level of -0.85 bar (as read on manifold gauge) is achieved.
- Shut off the main vacuum pump valve. Check for vacuum rise using the manifold compound gauge. A rise would indicate a large leak.
- If vacuum holds for 10 minutes, break vacuum with Nitrogen. Check the name plate of the unit / compressor for allowable leak test pressure. Ensure that pressure regulators are installed on the Nitrogen cylinders.
Check for leaks and repair leakage.
Leak Check
The success of all the subsequent commissioning depends on a leak free system,
free of contaminants, free of oxides, free of non-condensable’ s, that has
been evacuated to a low vacuum and charged with the prescribed refrigerant.
Leak test is particularly important for field-connected systems. Typically,
field systems lose as much as 20%–30% of their refrigeration charge annually.
This is not only an unnecessary expense but also damages the environment.
Compressor oil can be lost at the same time as refrigerant and eventually lead
to compressor failure. (Time spent on leak test will eventually reduce the
time spent on the evacuation process).
Ensure that all service valves are open during the leak test process. It is
important to recheck all joints within the unit as well as the external
joints.
a. The unit is shipped with a holding charge of dry nitrogen and should be
leak free.
b. Ensure that the test pressure do not exceed the system design pressures.
c. Do not expose system pressure control LP to test pressures above the design
pressure. This can damage the pressure controls.
d. Using an approved, calibrated electronic gas leak detector, leak test the
entire system paying attention to all joints (you might have to charge small
quantity of refrigerant before charging the Nitrogen to enable this
procedure).
e. Periodically check functionality of the electronic leak detector during
this process.
f. To further check system integrity, spray a soapy water solution over joins
then visually inspect for bubbles.
g. Leave the system under pressure for a designated period (24 Hours).
h. Check and record the ambient temperatures and the system pressure with
calibrated approved instruments. This process is to be carried out every 8-12
hours during the pressure testing process.
i. If the test pressures cannot be maintained, repeat the leak testing process
employing the isolation of sections of the system to determine the source of
leaks. Repair the leak and repeat the leak testing process until system can
be signed off as leak free and approved by authorized personnel.
j. Record findings and confirm pressure testing process completion.
Evacuation
a. After the system is leak checked, connect approved dual stage vacuum pump
sized to application with preferably fresh oil to evacuate the system.
b. Ensure all inline system shut-off valves and solenoid valves are fully
open.
c. Evacuate the system to 300 microns.
d. A triple evacuation is recommended in case of using analog gauges as we
might not know the exact vacuum level being achieved
Charging and commissioning
Reminder
- The scroll compressor design requires system charging with liquid refrigerant into the liquid line.
- Do not vapor charge the Water Cooled Scroll unit. After ensuring all valves are opened and system is evacuated properly, only then start the refrigerant charging process. Also ensure that LP cutout is not by-passed during the charging process.
Step-by-step:
-
Ensure that there is no power supply to the Water Cooled Scroll unit.
The liquid line solenoid needs to be kept open for the charging process and this may require a temporary power feed to it. -
Connect the refrigerant cylinder to main service hose and purge line at the manifold end.
-
Ensure correct orientation of the refrigerant cylinder. Follow cylinder labeling/instructions so that liquid refrigerant can be charged into the system. This will be charged through the high-pressure side of the manifold and Water Cooled Scroll unit liquid service valve. Ensure that at least 70-80% of the required refrigerant charging is done by this method.
-
The compressor can then be started, and the unit continued to be charged (with the controlled liquid refrigerant through the suction service valve). The quantity of charge should always be measured. See note.
-
The system needs to be operated down to its design evaporating temperature before you can be sure the charge is correct. It is at this point that the normal refrigeration operational checks can be carried out – such as checking the liquid line sight glass for bubbles and the operating pressures.
Refrigerant charging is regarded full/complete when the operating tempera-ture of the system has been stable for some time and the liquid line sight glass is clear.
h. Maintenance
Water Quality
Ensure that the water quality is maintained to reduce the amount of scaling
inside the condenser
Electrical Connections
Check tightness of electrical connections periodically
Routine Leak Test
All joints should be checked for leaks during site visits. All joints should
be leak tested once a year.
TURN OFF OR DISCONNECT THE ELECTRICAL POWER SOURCE BEFORE CLEANING THE
CONDENSER COIL OR DOING MAINTENANCE.
System Start-Up and Operational Check Sheet
Facility/Customer Name : | Client Details |
---|---|
Address | |
Contact Details: | |
Installer : | |
Installation Date : | |
Condensing Unit Info | |
CDU Model : | |
Serial Number : | |
CDU Location : | |
Indoor Unit Make/Model : | |
Room/Case ID : | System |
Details
---|---
Pipe Length (approx.) :|
OAT @ Start-Up/Check :|
PSI Leak Test :| PSIG
Duration :| Hours
System is Leak Tight :| Y I N
Triple Evacuation :| Y I N
Micron Gauge Reading :| microns
Total Evacuation :| PSIG @ # of Hrs
Refrigerant :|
Total Charge :| Kg.
Sight Glass Clear :| Y I N
Evap Fans Running :| Y I N
Liquid Line Insulation :| Y I N
Sound and Vibration|
|
System Operation
COMP Voltage :| V
COMP Current :| A
Suction Pressure :| PSIGIBar
Liquid Line Pressure :| PSIGIBar
COMP Suction Temp :| °C
COMP Disch Temp :| °C
Liquid Line Temp :| °C
Compressor SH :| K
Subcooling :| K
Adjustable LP Setpoint :| PSIG
Design/Operating Temp:| °C
Actual Room/Case Temp :| °C
Condenser Fins :|
Disclaimer
Technical data given was correct at the time of printing. Products,
specifications and data in this literature are subject to change without prior
notice. Updates will be done periodically. Should you need clarification of a
specific data, value or information, kindly contact Emerson representative.
Contact list
United Arab Emirates
Jebel Ali Free Zone
P.O. Box 26382, Dubai
United Arab Emirates
Toll Free: 8000 441 3428
Tel: +971 4 8118100
Fax: +971 4 8865465| Saudi Arabia
P.O. Box 34332 – 3620
2nd Industrial City, 67 St.
Dammam, Saudi Arabia
Toll Free: 8008 443 426
Tel: +966 3 8147560
Fax: +966 3 8147570
---|---
South Africa
11 Quark Crescent
Linbro Business Park
Sandton 2065, South Africa
Toll Free: 0800 980 3711
Tel: +27 11 451 3700
Fax: +27 11 451 3800| Egypt
P.O.Box 11799
11 Mustafa Refaat Street
Sheraton, Heliopolis
Cairo, Egypt
Tel: +20 2 226 5854
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>