DeLOCK Thermostat for DIN Rail User Manual

June 3, 2024
DeLOCK

DeLOCK-logo

DeLOCK Thermostat for DIN Rail

Description

This thermostat by Delock can be used to control filter fans, heat exchangers or to switch signal devices when the temperature is exceeded. The contact closes when the temperature rises. Due to the integrated clips on the back, it can be mounted on a 35 mm DIN rail in a control cabinet.

Specification

  • Connector: 2 pin terminal for 2.5 mm²

  • Switching function: normally open contact

  • Switching capacity: max. AC 250 V, 10 (2) A / 120 VAC, 15 (2) A DC 30 W

  • Switching temperature difference: 7 K (±4 K tolerance)

  • Temperature setting range: 0 °C ~ 60 °C

  • Sensor: thermobimetal

  • DIN rail mounting: 35 mm

  • Protection class: IP20

  • Lifetime: > 100.000 cycles

  • Fire-resistance rating: 94V-0

  • Operating temperature: -45 °C ~ 80 °C

  • Colour:
    housing: grey
    temperature regulator: blue

  • Housing material: plastic

  • Dimensions (LxWxH): ca. 60 x 43 x 33 mm

Package content
  • Thermostat
  • User manual

Safety instructions

  • The installation should only be carried out by qualified electricians in compliance with the usual national power supply guidelines.
  • Protective measures must be ensured.
  • The contact system of the controller is exposed to the influences of the environment. As a result, the contact resistance can change, this can lead to a voltage drop and/or self-heating of the contacts.
  • The device should be installed in the upper area of the control cabinet at the largest possible distance from heaters or other heat-generating components.
  • The technical specifications must be adhered and should not be exceeded.
  • The ventilation slots on the thermostat should not be covered.

Application
The thermostats are used to control filter fans, heat exchangers or to switch signal devices when the temperature is exceeded. Normally open contact (switching contact closes when temperature rises)

Installation and Operation
  1. Attach the device to a 35 mm DIN rail.
  2. Connect the device to a filter fan or a signalling device.
  3. Use the red rotary knob to adjust the temperature as required.

Support Delock
If you have further questions, please contact our customer support [email protected]
You can find current product information on our homepage: www.delock.com

Final clause
Information and data contained in this manual are subject to change without notice in advance. Errors and misprints excepted.

Copyright
No part of this user manual may be reproduced, or transmitted for any purpose, regardless in which way or by any means, electronically or mechanically, without explicit written approval of Delock.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

DeLOCK User Manuals

Related Manuals