KMC CONTROLS 5901 AFMS Ethernet User Guide
- September 29, 2024
- KMC CONTROLS
Table of Contents
5901 AFMS Ethernet
“`html
Product Information
Specifications:
- Model: AFMS Ethernet Model
- Manufacturer: KMC Controls
- Default IP Address: 192.168.1.251
- Control Mode Options: Damper Position Control
Product Usage Instructions:
Login Window
-
Connect power to the controller following the installation
guide. -
Open a new browser window.
-
Enter the default IP address 192.168.1.251.
-
Wait for the login screen to appear (about 30 seconds after
power-up).
Point-to-Point Checkout Tasks
Follow these steps for each point-to-point checkout task:
Verify Correct Application for the Installation:
- Go to Application > Restore.
- Verify the correct application is configured.
- If needed, change the base application and click Save.
- Wait for the AFMS to restart.
Set Control Mode to Damper Position Control:
-
Go to Application > AFMS > Configure > System
Setup. -
Select “DMPR POSITION CTRL” from the Control Mode drop-down
menu. -
Click Save.
Verify Pressure Transducer Settings:
-
Check signal output type is set to volts for all pressure
transducers. -
Ensure the transducer is set to unipolar mode following the
manufacturer’s instructions.
Frequently Asked Questions (FAQ):
Q: How do I recover an unknown IP address for the AFMS
controller?
A: You can recover an unknown IP address by following the steps
outlined in the manual on page 19. Ensure the controller has
restarted or power has been applied before attempting to access the
login screen.
“`
AFMS Ethernet Model Configuration Web Pages
Application Guide for Checkout and Commissioning
CONTENTS
INTRODUCTION ……………………………………………………………………3 LOGIN
WINDOW…………………………………………………………………….3 POINT-TO-POINT CHECKOUT
TASKS………………………………………….4
Verify Correct Application for the Installation …………………………….4 Set Control Mode
to Damper Position Control ……………………………. 4 Verify Pressure Transducer Settings
……………………………………….4 Make Pressure Transducer Zero Adjustment………………………………5 Set
the Supply Air Differential Pressure Range (5901- AFMS only)……5 Set the Supply
Air Area ……………………………………………………….5 Inspect Pressure Assist Pickup Tubes (PA
only)………………………….5 Calibrate the Supply Air Flow ………………………………………………..5
Calibrate OAD/RAD Diff. Pressure (pressure assist only) ………………. 6 Verify and
Calibrate Outside Air Temperature …………………………….6 Verify and Calibrate Return
Air Temperature………………………………6 Verify and Calibrate Mixed Air
Temperature……………………………….6 DAMPER SPAN CALIBRATION TASKS…………………………………………7 Set
the Damper Stroke Time …………………………………………………7 Set the Actuator Voltage
Range……………………………………………..7 Turn On Learn Damper Span, then
Verify…………………………………..7 Stroke Damper and Visibly Verify
Positions……………………………….7 Set Damper Reverse Action (if needed)…………………………………….8
Stroke Damper and Verify that Reported Damper Position Follows ……8 Set
Inclinometer Action to Reverse (if needed) …………………………..9 LEARNING MODE TASKS
………………………………………………………. 10 Prerequisite Tasks ………………………………………………………….. 10
Starting Learning Mode…………………………………………………….. 10 Verify that AFMS Status is in
Learning Mode …………………………… 11 Verify Learning Mode Completed and Record
Date…………………….. 11 Alternative to Running Learning Mode …………………………………… 12
Access the AFMS Table and Record Data ……………………………….. 12 Set Control Mode
……………………………………………………………. 13 ABOUT TESTING AND BALANCING AFMS …………………………………. 13
KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 /
877-444-5622 / Fax:
574-831-5252 / www.kmccontrols.com
CONTENTS (CONTINUED)
DEVICE WINDOW ………………………………………………………………… 14 SECURITY WINDOW
…………………………………………………………….. 16 FIRMWARE UPDATE WINDOW ………………………………………………… 17
HELP WINDOW …………………………………………………………………… 18 RECOVERING AN UNKNOWN IP
ADDRESS…………………………………. 19 CHANGING YOUR COMPUTER’S ADDRESS ………………………………… 20
Introduction ………………………………………………………………….. 20 Change a Computer’s IP Address
with a Utility …………………………. 20 Change a Computer’s IP Address Manually
……………………………… 21 TROUBLESHOOTING……………………………………………………………. 24 HANDLING
PRECAUTIONS ……………………………………………………. 24 IMPORTANT NOTICES…………………………………………………………..
24 SUPPORT …………………………………………………………………………. 24
2
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
INTRODUCTION
This document guides users through checkout and commissioning of an Airflow
Measurement System. It is designed to aid in completing the tasks on the Note
Sheets for AFMS Checkout and Commissioning.
Ethernet-enabled “E” AFMS models with the latest firmware can be configured
with a web browser from pages served from within the AFMS controller. The AFMS
controller has the following default network address values:
· IP address–192.168.1.251 · Subnet mask–255.255.255.0 · Gateway–192.168.1.1
NOTE: See the AFMS selection guide for a table of other tools that can be used
to configure some or all AFMS parameters.
NOTE: The default IP address of the BAC-5051(A)E router is 192.168.1.252.
LOGIN WINDOW
To log in to an AFMS controller with a web browser:
1. Connect the AFMS to an Ethernet port by doing one of the following: ·
Connect directly to the computer, which typically requires changing the
computer IP address. See Changing Your Computer’s Address on page 20. ·
Connect to a subnet that recognizes address 192.168.1.251.
2. Connect power to the controller. (See the AFMS installation guide.)
3. Open a new browser window.
4. Enter the address 192.168.1.251.
5. In the login window, enter the following: · User name: admin · Password:
admin
NOTE: The login screen will be accessible about 30 seconds after a controller
has restarted or had power first applied. (See also Recovering an Unknown IP
Address on page 19.
6. After logging in, change the controller parameters as needed. · To change
passwords and add users, see Security Window on page 16. · To change the IP
address, see Device Window on page 14.
After login, a ten-minute timeout starts. The timer resets to ten minutes for
any of these conditions:
· A page is refreshed or saved. · The menu (on left side of screen) is clicked
to go to a different page. · The flashing Reset Session Timer (which appears
two minutes before the
end of the timeout period) is pushed.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
3
POINT-TO-POINT CHECKOUT TASKS
The steps for each point-to-point checkout task are presented in subsections
below. Complete each task/subsection in the order presented.
Verify Correct Application for the Installation
NOTE:
Check and (if needed) change the base application under Restore > Factory before configuring setpoints or other system options. Changing the base application will reset setpoints and system options to their factory defaults.
Under Application > Restore, next to Factory, verify that the correct
application is configured for the AFMS installation:
· AMSO [English]: Standard outside air damper application with English units ·
AMSO [Metric]: Standard outside air damper application with Metric units ·
AMSOP [English]: Pressure assist outside air damper application with
English units · AMSOP [Metric]: Pressure assist outside air damper application
with Metric
units · AMSRP [English]: Pressure assist return air damper application with
English
units · AMSRP [Metric]: Pressure assist return air damper application with
Metric
units
If you need to change the configured application:
1. Next to Factory, select the correct application for the AFMS installation.
2. Click Save.
NOTE: A window appears with “REMINDER: Changing the Factory Base App will reconfigure all settings in the Application. Continue?”
3. Click OK.
4. In the reminder pop-up, click OK.
5. Wait about 20 seconds for the AFMS to restart, then log in again.
Set Control Mode to Damper Position Control
Under Application > AFMS > Configure, in the System Setup group: 1. For
Control Mode, select DMPR POSITION CTRL from the drop-down menu. 2. Click
Save.
Verify Pressure Transducer Settings
Do the following for all pressure transducers (supply and pressure assist)
that were installed, following their manufacturer’s installation instructions:
1. Verify that the signal output type is set to volts.
2. Verify that the transducer is set to unipolar mode.
3. If the transducer has several pressure range options, verify that the
correct range is set (according to the pressure range of the unit).
4
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
Make Pressure Transducer Zero Adjustment
Zero out all pressure transducers (supply and pressure assist) that were
installed, following their manufacturer’s installation instructions.
You will need to expose the transducer high and low ports to ambient pressure
by temporarily removing the tubing from the ports. After zeroing the
transducer, reconnect each tube to the correct port.
Set the Supply Air Differential Pressure Range (5901AFMS only)
Under Application > AFMS > Configure, in the General group:
1. For SA DP Range, enter the maximum inches of water column that the supply air pressure transducer can measure.
NOTE:
For example, a TPE-1475-21, can measure up to 2″ wc, so enter 2. A TPE-1475-22 can measure up to 10″ wc, so enter 10. (A 9311-AFMS can measure up to 2″ wc.) Some AFMS installations may use other pressure transducers.
2. Click Save.
Set the Supply Air Area
Under Application > AFMS > Configure, in the General group:
1. For Supply Air Area: · If the supply air pickup tubes were installed on
the supply air fan bell, enter the square foot measurement of the fan inlet. ·
If the supply air pickup tubes were installed in the supply air duct, enter
the square foot measurement of the duct cross-section where the tubes are
located.
NOTE: For assistance calculating the area, use the Free Area Calculator in the
Note Sheets for AFMS Checkout and Commissioning.
2. Click Save.
Inspect Pressure Assist Pickup Tubes (PA only)
For pressure assist applications, ensure that the pickup tubes were installed
in the correct location per the AFMS installation guide.
Calibrate the Supply Air Flow
Under Application > AMFS > Tune, in the Calibration group:
1. Do any of the following: · In the Offset column for Supply Air Flow, enter
the CFM offset (determined by a TAB technician) for the supply air pressure
transducer. · In the Multiplier column for Supply Air Flow, enter the
multiplier (determined by a TAB technician) for the supply air pressure
transducer.
2. Click Save.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
5
Calibrate OAD/RAD Diff. Pressure (pressure assist only)
For pressure assist applications, under Application > AFMS > Tune, in the Calibration group:
1. In the Offset column for OAD Diff. Pressure / RAD Diff. Pressure, enter
the differential pressure offset (determined by a TAB technician) for the
or
pressure assist pressure transducer.
2. Click Save.
Verify and Calibrate Outside Air Temperature
Under Application > AFMS > Tune, in the Calibration group: 1. Locate the OAT
sensor’s reading, next to Outside Air Temp. 2. Using a NIST-traceable
instrument, measure the temperature near the OAT
sensor. 3. Compare the two values. 4. Enter the Offset for Outside Air Temp.
5. Click Save.
Verify and Calibrate Return Air Temperature
Under Application > AFMS > Tune, in the Calibration group: 1. Locate the RAT
sensor’s reading, next to Return Air Temp. 2. Using a NIST-traceable
instrument, measure the temperature near the RAT
sensor. 3. Compare the two values. 4. Enter the Offset for Return Air Temp. 5.
Click Save.
Verify and Calibrate Mixed Air Temperature
Under Application > AFMS > Tune, in the Calibration group:
1. Locate the MAT sensor’s reading, next to Mixed Air Temp.
2. Using a NIST-traceable instrument, measure the temperature near the MAT sensor.
3. Compare the two values.
4. Enter the Offset for Mixed Air Temp.
5. Click Save.
Point-point-checkout is completed. Continue to the Damper Span Calibration Tasks on page 7.
6
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
DAMPER SPAN CALIBRATION TASKS
After completing the Point-to-Point Checkout Tasks on page 4, calibrate the
damper span. The steps for each damper span calibration task are presented in
subsections below. Complete each task/subsection in the order presented.
Set the Damper Stroke Time
Under Application > AFMS > Configure, in the Damper group:
1. For Stroke Time, enter the time (in seconds) that it takes for the
actuator to move the damper from fully closed to fully open.
2. Click Save.
Set the Actuator Voltage Range
Under Application > AFMS > Configure, in the Damper group:
1. For Actuator Voltage, select the voltage range of the damper actuator from
the drop-down menu (2 to 10 volts or 0 to 10 volts).
2. Click Save.
Turn On Learn Damper Span, then Verify
Before the AFMS can run Learn Mode, it must learn the minimum and maximum
incline of the damper using the inclinometer. The Learn Damper Span sequence
will take 3 to 5 minutes to complete.
Under Application > AFMS > Configure, in the Damper group:
1. For Learn Damper Span, select ON from the drop-down menu.
2. Click Save.
3. After 3 to 5 minutes, verify that Damper Span Learned reports LEARNED.
Stroke Damper and Visibly Verify Positions
Under Application > AFMS > Configure, in the System Setup group: 1. Ensure
that DMPR POSITION is set for Control Mode. 2. For Damper Setpoint, enter 0.
3. Click Save. 4. Once the actuator stops moving, visibly verify that the
damper is fully
closed. 5. For Damper Setpoint, enter 50. 6. Click Save. 7. Once the actuator
stops moving, visibly verify that the damper is 50% open/
closed. 8. For Damper Setpoint, enter 100. 9. Click Save.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
7
(if needed) 8
10. Once the actuator stops moving, visibly verify that the damper is fully
open. If the actuator is moving the damper in reverse (i.e. 10 volts =
closed), see the next section, “Set Damper Reverse Action”.
Set Damper Reverse Action (if needed)
If visual inspection (see the previous section) revealed that the damper
actuator moves in reverse action (i.e. 10 volts = closed), under Application >
AFMS > Configure, in the Damper group: 1. For Damper Reverse Action, select
REVERSE from the drop-down menu. 2. Click Save.
Stroke Damper and Verify that Reported Damper Position Follows
1. Go to Application > AFMS > Configure > the System Setup group: 2. Ensure
that DMPR POSITION is set for Control Mode. 3. For Damper Setpoint, enter 0.
4. Click Save. 5. Once the actuator stops moving, visibly verify that the
damper is fully
closed. 6. Go to the Monitor tab. 7. Verify that Damper Position (in the
Operation group) reports a value within
±1% of 0. NOTE: The inclinometer can detect very small movements of the damper
assembly. 8. Go to the Configure tab again. 9. For Damper Setpoint, enter 50.
10. Click Save. 11. Once the actuator stops moving, visibly verify that the
damper is 50% open/
closed. 12. Go to the Monitor tab again. 13. Verify that Damper Position
reports a value within ±1% of 50. 14. Go to the Configure tab again. 15. For
Damper Setpoint, enter 100. 16. Click Save. 17. Once the actuator stops
moving, visibly verify that the damper is now fully
open. 18. Go to the Monitor tab again. 19. Verify that Damper Position reports
a value within ±1% of 100.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
(if needed)
If Damper Position reports values that are the opposite of the entered Damper
Setpoint, see the next section, “Set Inclinometer Action to Reverse”.
Set Inclinometer Action to Reverse (if needed)
For the standard (AMSO) application or OAD Pressure Assist (AMSOP)
application, if the inclinometer was mounted on a horizontal return air damper
blade because the outside air damper blades are vertical, then you need to set
Inclinometer Action to REVERSE.
If testing revealed that Damper Position reports values that are the opposite
of the Damper Setpoint (see the previous section), under Application > AFMS >
Configure, in the Damper group:
1. For Inclinometer Action, select REVERSE from the drop-down menu.
2. Click Save.
Damper span calibration is completed. Continue to the Learning Mode Tasks on
page 10.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
9
LEARNING MODE TASKS
The steps for each learning mode task are presented in subsections below.
Complete each task/subsection in the sequence presented.
Prerequisite Tasks
Before starting Learning Mode, for valid results, ensure that:
· The sensors are calibrated (Point-to-Point Checkout Tasks on page 4). · AFMS
is configured properly (Damper Span Calibration Tasks on page 7). · The supply
air fan is running at a normal, steady rate (without hunting or
sporadic spikes). · If the unit has a heat recovery wheel, it is turned off. ·
If any heating or cooling sources are located upstream of the MAT sensor,
they are turned off. · If the unit has a bypass damper, it is set to 100%
open.
Starting Learning Mode
1. Go to Application > AFMS > Learn.
2. Note whether Learn Ready reports READY or NOT READY.
If READY is displayed, Learning Mode can be started manually. Otherwise, see
Enabling Learning Mode to Auto Start on page 11.
NOTE: In special cases, you may consider the Alternative to Running Learning
Mode on page 12.
Manually Starting Learning Mode
1. Leave Min Delta Temp set to the default or adjust if needed.
NOTE:
If the T becomes less than Min Delta Temp, the AFMS controller will abort Learning Mode. This is to ensure that the controller does not receive unusable learning samples. Setting Min Delta Temp at a 15°F or larger difference is recommended.
2. Leave Time Between Samples (Seconds) set to the default or adjust it if needed.
NOTE:
Most often, Time Between Samples (Seconds) can be left on the default (60
seconds). You might increase the value if the damper Stroke Time is longer
than that of a typical unit, or if the damper actuator requires
extra time to respond. You might decrease it if a large T is present and time
at the site is limited. However, too little time between samples could result
in inaccurate measurements.
3. For Learning Mode, select ACTIVE.
4. Click Save.
5. Wait for Learning Mode to complete.
NOTE: To calculate the total time (in minutes) that Learning Mode should take to complete, multiply Time Between Samples (Seconds) by 91, then divide by 60.
Skip to Verify that AFMS Status is in Learning Mode on page 11.
10
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
Enabling Learning Mode to Auto Start
If Learn Ready reports NOT READY because of currently unfavorable temperatures, you may enable the AFMS to automatically start Learning Mode when it detects favorable temperatures later (overnight is likely).
1. Leave Min Delta Temp set to the default or adjust it if needed.
NOTE:
If the T becomes less than Min Delta Temp, the AFMS controller will abort Learning Mode. This is to ensure that the controller does not receive unusable learning samples. Setting Min Delta Temp at a 15°F or larger difference is recommended.
2. Leave Auto Start Delta Temp set to the default, or adjust it if needed.
NOTE:
When the T reaches the Auto Start Delta Temp, Learning Mode will start. Learning Mode will complete if the T remains greater than the Min Delta Temp for the entire duration. An Auto Start Delta Temp that is at least 20°F more than Min Delta Temp is recommended.
3. Leave Time Between Samples (Seconds) set to the default or adjust it if needed.
NOTE:
Most often, Time Between Samples (Seconds) can be left on the default (60 seconds). You might increase the value if the damper Stroke Time is longer than that of a typical unit, or if the damper actuator requires extra time to respond.
4. For Auto Learn Enable, select ON.
5. Click Save.
6. Wait for Learning Mode to complete during favorable temperatures (overnight is likely).
Skip to Verify Learning Mode Completed and Record Date on page 11.
Verify that AFMS Status is in Learning Mode
Under Application > AFMS > Monitor, in the Operation group, verify whether
AFMS Status reports LEARN MODE.
Verify Learning Mode Completed and Record Date
After the AFMS completes Learning Mode (approximately 2 hours), under
Application > AFMS > Learn: 1. Locate the Date of Last Learn (YYMMDD). 2.
Enter the date into the Note Sheets for AFMS Checkout and Commissioning. Skip
to Access the AFMS Table and Record Data on page 12.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
11
Alternative to Running Learning Mode
While not ideal, the damper characterization data can be calculated and
entered manually in the AFMS Table. This should only be done if–in the
allotted time for setting up the AFMS–the T is unlikely to remain greater than
the Min Delta Temp for the duration of Learning Mode.
To make the calculations, use the %OA/%RA equations found in ASHRAE Standard
111, section 7.6.3.3, “Flow Rate Approximation by Temperature Ratio”.
1. Go to Application > AFMS > Configure.
2. For Damper Setpoint, enter the first damper position (Closed, i.e. 0)
found in the AFMS Table (on the Tune tab).
NOTE: Note: Each subsequent time through this process, enter the next damper
position from the table: 5, 10, 15, 20, 30, 40, 50, 60, 70, 80, 90, 100.
3. Click Save.
4. Go to the Monitor tab.
5. Allow the Outside Air Temp, Return Air Temp, and Mixed Air Temp to
stabilize.
6. Depending on the application, calculate either the OA Fraction or RA
Fraction, using the temperature readings and either the %OA or %RA equation
from the standard.
7. Go to the Tune tab.
8. Enter the result into the OA Fraction column/ RA Fraction column
(depending on the application).
NOTE: For Pressure Assist applications, also enter the Supply Air Flow reading
into the SA Flow column and the OAD Diff. Pressure / RAD Diff. Pressure
reading into the Diff. Pressure column.
9. Select Save.
Repeat those steps for the remaining 12 damper positions listed on the AFMS
Table.
Access the AFMS Table and Record Data
Under Application > AFMS > Tune, in the AFMS Table group:
1. Locate the Characterized Airflow PerformanceTM data, found in:
· The OA Fraction column (for both standard and outside air damper pressure
assist applications)
· The RA Fraction column (for return air damper pressure assist applications
only)
· The SA Flow column (for both types of pressure assist applications only) ·
The Diff. Pressure column (for both types of pressure assist applications
only)
2. Record the data into the Note Sheets for AFMS Checkout and Commissioning:
· For standard applications, use the AFMS Post Table. · For pressure assist
applications, use the AFMS PA Post Table.
12
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
Set Control Mode
Under Application > AFMS > Configure, in the System Setup group:
1. For Control Mode, select from the drop-down menu the option that will be
the AFMS’s normal mode for this installation:
· OA FLOW CTRL: The AFMS modulates the damper actuator to maintain the Outside
Air Flow Setpoint (CFM).
· PASS THROUGH: The AFMS passes control of the damper actuator to another
controller. (The AFMS measures and monitors only.)
· MAT CTRL: The AFMS modulates the damper actuator to maintain the Mixed Air
Temp Setpoint (°F/°C).
2. Click Save.
ABOUT TESTING AND BALANCING AFMS
If everything was installed and configured correctly prior to running Learning
Mode, the AFMS Table data is very reliable. The AFMS uses the same method from
ASHRAE Standard 111 (Section 7.6.3.3, “Flow Rate Approximation by Temperature
Ratio”) that a good tester and balancer should use. Furthermore, as the AFMS
performs the method, it takes the OAT, RAT, and MAT measurements
simultaneously and several times for reliable averages, increasing the
reliability of the data.
However, should verification be required, the following guidelines should be
observed:
· Make measurements using NIST-traceable instruments. · Use the method from
ASHRAE Standard 111, Section 7.6.3.3, “Flow Rate
Approximation by Temperature Ratio” to calculate the table data. · Should an
adjustment be needed, adjust single data items from the AFMS
Table rather than making a linear adjustment.
NOTE: TAB OA Factor (found in the Calibration group under Tune) should be at 1
and not adjusted.
If large adjustments need to be made to the AFMS Table data, one or more of
the sensors may have been installed incorrectly and/or a setting was
misconfigured prior to running Learning Mode. The problem should be corrected
by fixing the installation and/or configuration, then running Learning Mode
again.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
13
DEVICE WINDOW
The Device window identifies the controller as a BACnet device and sets BACnet communication properties. The Device window also configures the controller for the Local Area Network (LAN). The new IP Address, Subnet Mask, and Default Gateway values are supplied by the building’s IT department system administrator.
NOTE:
After changes in the window are saved, the controller will use the new settings and will require you to log in at the new address. If the controller is not on the same subnet as the network gateway router, it will not function correctly.
The Device window shows multiple parameters (which vary depending on whether
IP or Ethernet is selected):
· Device Name–The name must be unique among all devices on the BACnet
internetwork.
· Description–Optional information not included in the device name. ·
Location–An optional value that describes the controller’s physical location.
· Device Instance–A number that identifies the controller on the internetwork.
The device instance must be unique on the internetwork and in the range from
04,194,302. The device instance is assigned by the BACnet system designer.
The default device instance is 1 and must be changed to a unique number to
avoid conflict with other devices. · Number APDU Retries–Indicates the maximum
number of retries that an APDU (Application Layer Data Unit) is retransmitted.
· APDU Timeout–Indicates the time (in milliseconds) between retransmissions of
an APDU requiring an acknowledgment for which no acknowledgment has been
received. · APDU Seg. Timeout–The Segment Timeout property indicates the time
(in milliseconds) between retransmissions of an APDU segment. · Backup Failure
Timeout–The time (in seconds) that the controller must wait before ending a
backup or restore procedure. Use KMC Connect, TotalControl, or Converge to
back up the controller. · IP Address–The internal or private network address
of the controller. (To recover a lost address, see Recovering an Unknown IP
Address on page 19.
14
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
· MAC–The MAC address of the controller. · Subnet Mask–The Subnet Mask
determines which part of the IP address is
used for a network identifier and which part is used for a device identifier.
The mask must match the mask for the network gateway router and other devices
on the subnet. · Default Gateway–The address of the network gateway router.
The controller and gateway router must be part of the same LAN subnet. · UDP
Port–UDP (User Datagram Protocol) is an alternative communications protocol to
TCP used primarily for establishing low-latency and loss-tolerating
“connectionless” connections between applications on the Internet. The port is
the “virtual channel” through which the data is transmitted and received. ·
Restart Device–Restarts the controller. This is similar to restarting the
controller with a BACnet cold start from KMC Connect or TotalControl. A
restart does not change properties or save changes not yet saved.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
15
SECURITY WINDOW
The Security window sets user access to the controller:
· During configuration, the default admin/admin defaults should be changed to
enhance security.
· The user name list must include at least one name with Administrator
privileges.
· User names and passwords are case sensitive.
The controller has multiple levels of user access:
· A View Only user may view configuration pages but not make any changes. · An
Operator may make configuration changes but cannot modify security
settings. · An Administrator may make configuration and security changes. · A
Custom access user has a combination of access options as selected by
an Administrator.
The NetSensor Passwords section provides the viewing of and option to change
the passwords required to access a controller using a Conquest STE-9000 series
NetSensor or the KMC Connect Lite mobile app. These passwords are four digits,
with each digit being a number 0 to 9. If all four numbers are 0, no password
is required of the user for that level. For more information, see the Conquest
Controllers Default Password Technical Bulletin after logging into the KMC
Controls web site.
16
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
FIRMWARE UPDATE WINDOW
The AFMS controller’s firmware can be updated through the web browser after
downloading the latest firmware from KMC Controls. To download from KMC
Controls and install the firmware file onto the computer:
1. Log into the KMC Controls web site and download the latest zipped firmware
file from any AFMS controller’s product page.
2. Find and extract the “Over-The-Network” (not the “HTO-1105_Kit”) EXE file
for the relevant model controller (which must be a “BAC-xxxxCE-AFMS” version
of the firmware).
3. Run the BAC-xxxxCE-AFMS_x.x.x.x_OverTheNetwork.exe file. 4. Click Yes to
allow Windows to install the program. 5. Click OK on the Firmware License
dialog box. 6. Click Unzip in the WinZip Self-Extractor dialog box.
To then load the firmware from the computer into the controller:
1. Log-in to the controller’s web page. See Login Window on page 3. 2. In the
controller’s Firmware window, click Choose File, locate the new firm-
ware zip file (it should be in a subfolder of C:ProgramDataKMC Controls
Firmware Upgrade ManagerBACnet Family), and click Open. 3. After being asked
if you want to proceed with the download, click OK and the new firmware starts
loading into the controller.
NOTE: To cancel the update and leave the devices with the original firmware
intact, click the Cancel or Abort button.
4. After the new firmware is loaded, you will be asked if you want to commit
to the download. To finish the update, click OK.
5. To put the firmware change into effect, the controller will need to be
restarted. When asked if you want to restart the device, click OK.
6. After the controller restarts, you will need to log in again to continue
any additional configuration. See Login Window on page 3.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
17
HELP WINDOW
Go to KMC takes you to the KMC Controls public web site. Use the search to
find the AFMS controller’s product page. Look at the various files that can be
downloaded. You will need an active Internet connection for the link to work.
NOTE: Bulletins and firmware are available only after logging into the web
site.
18
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
RECOVERING AN UNKNOWN IP ADDRESS
If the network address of the controller is lost or unknown, the controller
will respond to the default IP address for approximately the first 20 seconds
after power is applied.
Default Address
Current Address
To discover an unknown IP address: 1. Disconnect the controller from the LAN
and connect the controller as de-
scribed in Login Window on page 3. 2. On the computer, open a browser window
and enter the default address of
192.168.1.251. 3. Reconnect the controller to the power source and immediately
attempt to
connect with the browser. The browser will respond with the controller’s IP
address and subnet mask. 4. Once the address is known, connect the controller
to the relevant IP subnet for normal operation or controller configuration.
NOTE: A controller’s IP address can also be seen in KMC Connect,
TotalControl, and KMC Converge when the controller is properly connected to
the network.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
19
CHANGING YOUR COMPUTER’S ADDRESS
Introduction
To directly connect a computer to a controller, you must temporarily set the
IP address of the computer to be compatible with the IP address of the
controller. The IP address of a computer can be changed by using a utility or
manually.
Change a Computer’s IP Address with a Utility
The easiest method for users who will change their IP address on multiple
occasions is to install an IP address changing utility (such as Simple IP
Config available from GitHub). See the instructions with the software.
In the software:
1. Save a record/setting of your existing computer’s address information.
2. Enter the following for the computer’s temporary new IP address, Subnet
mask, and Gateway:
· IP address–192.168.1.x (where x is a number between 1 and 250) · Subnet
mask–255.255.255.0 · Gateway–Leave empty or unchanged (or if that does not
work, use
192.168.1.***, where the last digits are different than the IP address in the
computer or controller). NOTE: After configuration of the controller is
complete, revert your computer
to the original IP settings.
20
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
Change a Computer’s IP Address Manually
Introduction To change your computer’s IP address manually, follow the
instructions (or the equivalent for your hardware and operating system) for
Windows 10 (Settings) on page 21 or Windows 7 (Control Panel) on page 22.
NOTE: Screens will look different in different versions of Microsoft Windows.
NOTE: Depending on the computer and version of Windows, the exact name
for the connection to the controller may be Ethernet, Local Area Connection,
or something similar.
Windows 10 (Settings) 1. Click the Start button. 2. In the Start menu, click
Settings (the gear icon). 3. In Windows Settings, click Network and Internet.
4. Click Ethernet. 5. Click Network and Sharing Center. 6. Click Connections:
Ethernet. 7. Click Properties. 8. Click Internet Protocol Version 4 (TCP/IPv4)
and then Properties.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
21
NOTE:
If Obtain an IP address automatically is selected, the IP address and Subnet mask of the computer are not shown. They can be seen, however, by running ipconfig from a command prompt. To run ipconfig, type cmd in the Search box, at Command Prompt App press Enter, type in ipconfig at the prompt, and press Enter.
9. Record the existing settings of the Properties dialog.
10. Select Use the following IP address and then enter the following for the
IP address, Subnet mask, and Gateway.
· IP address–192.168.1.x (where x is a number between 2 and 255) · Subnet
mask–255.255.255.0 · Gateway–Leave empty or unchanged (or if that does not
work, use
192.168.1.***, where the last digits are different than the IP address in the
computer or controller).
11. When all information is correct, click OK and OK.
NOTE: The changes should take full effect after a few seconds.
Windows 7 (Control Panel)
1. Click the Start button and select Control Panel. 2. From the Control
Panel:
· (When viewed by icons) click Network and Sharing Center. · (When viewed by
category) click Network and Internet and then Network
and Sharing Center.
OR
22
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
3. Click the local connection for the LAN. Depending on the computer and
version of Windows, the exact name for the connection may be Ethernet, Local
Area Connection, or something similar.
4. In the Local Area Connection (or similar) Status dialog, click Properties.
5. Then click on Internet Protocol Version 4 (TCP/IPv4) and then click Proper-
ties.
NOTE:
If Obtain an IP address automatically is selected, the IP address and subnet mask of the computer are not shown. They can be seen, however, by running ipconfig from a command prompt. To run ipconfig, click the Start button, type cmd in the Search box, press Enter, type in ipconfig at the prompt, and press Enter.
6. Record the existing settings of the Properties dialog. 7. In the
Properties dialog, select Use the following IP address and then enter
the following for the IP address, Subnet mask, and Gateway. · IP
address–192.168.1.x (where x is a number between 1 and 250) · Subnet
mask–255.255.255.0 · Gateway–Leave empty or unchanged (or if that does not
work, use
192.168.1.***, where the last digits are different than the IP address in the
computer or controller) 8. When all information is correct, click OK and
Close.
NOTE: The changes should take full effect after a few seconds.
NOTE: After configuration of the controller is complete, repeat this process using the original IP settings.
KMC AMS Ethernet Model Configuration Web Pages Application Guide, AG240718A
23
TROUBLESHOOTING
· Check that the Ethernet connection cable is plugged into the Ethernet port
and not the Room Sensor port.
· Check the network and connections. · Restart the controller. See the
Resetting Controllers section in the KMC
Conquest Controller Application Guide. · Review IP address and login
information. See Introduction on page 3, Login
Window on page 3, and Changing Your Computer’s Address on page 20. · See
Communication Issues–Ethernet section in the KMC Conquest Control-
ler Application Guide.
HANDLING PRECAUTIONS
For digital and electronic sensors, thermostats, and controllers, take
reasonable precautions to prevent electrostatic discharges to the devices when
installing, servicing, or operating them. Discharge accumulated static
electricity by touching one’s hand to a securely grounded object before
working with each device.
IMPORTANT NOTICES
KMC Controls® and NetSensor® are all registered trademarks of KMC Controls.
KMC ConquestTM, KMC ConnectTM, KMC ConvergeTM, and TotalControlTM are all
trademarks of KMC Controls. All other products or name brands mentioned are
trademarks of their respective companies or organizations.
The material in this document is for information purposes only. The contents
and the product it describes are subject to change without notice.
KMC Controls, Inc. makes no representations or warranties with respect to this
document. In no event shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the use of this document.
The KMC logo is a registered trademark of KMC Controls, Inc. All rights
reserved.
The KMC Connect LiteTM app for NFC configuration is protected under United
States Patent Number 10,006,654.
Pat. https://www.kmccontrols.com/patents/
SUPPORT
Additional resources for installation, configuration, application, operation,
programming, upgrading and much more are available on the KMC Controls web
site (www.kmccontrols.com). Viewing all available files requires logging in to
the site.