HWAM 97-9721 Wood Burning Stove Insert Instruction Manual

September 28, 2024
Hwam

97-9721 Wood Burning Stove Insert

“`html

Product Information

Specifications

  • Model: HWAM I 40/56

  • Thermal Output: 7.1 kW

  • Fuel Types: Wood

  • Distance to Furnishings Front: 1300 mm

  • Distance to Furnishings Side: 800 mm

  • CO Emission at 13% O2: 0.085% / 1056
    mg/m3

  • Particles at 13% O2: 13 mg/m3

  • OGC at 13% O2: 67 mg/m3

  • Nox at 13% O2: 95 mg/m3

  • Energy Efficiency: 79%

  • Flue Gas Temperature (EN 13229): Measurement
    point and outlet socket

  • Cleanability: Pass

  • Mechanical Resistance: Pass

  • Laboratory Registration Number: NB 1235

  • Test Report: 300-ELAB-2659-EN

Product Usage Instructions

Installation

Before installing the insert, ensure that the floor can support
the insert, chimney, and any other necessary parts. Contact an
authorized HWAM retailer or recommended fitter for
installation.

Safety Precautions

Ensure that all glass parts are heat-resistant. Consult your
local chimney sweep or glass producer to determine the safe
distance between the insert and any flammable materials like
glass.

Maintenance

Regularly clean the insert following the manufacturer’s
guidelines. Ensure proper ventilation and airflow around the unit
for efficient operation.

FAQ (Frequently Asked Questions)

Q: Can this appliance be used continuously?

A: The appliance is capable of intermittent operation. Follow
the user manual for usage instructions.

Q: What type of fuel should be used?

A: Only use the recommended fuel types specified in the user
manual to ensure safe and efficient operation.

Q: Where can I find the Declaration of Performance?

A: The Declaration of Performance can be downloaded from
www.hwam.com/dop/i40-56.

“`

Installation instructions EN

I 40/56

23.04.2024 / 97-9721 www.hwam.com

TABLE OF CONTENTS
TECHNICAL DATA……………………………………………………………………………………………. 4 In general …………………………………………………………………………………………………………. 4 Safety………………………………………………………………………………………………………………… 4 Room requirements …………………………………………………………………………………………. 4 Technical measures and data – right hinged door and top flue outlet…………. 4 Technical measures and data – right hinged door and back outlet ……………… 5 Technical measures and data – left hinged door and top flue outlet……………. 6 Technical measures and data – left hinged door and back outlet………………….7 Type plate and serial number …………………………………………………………………………. 8 Floor plate ………………………………………………………………………………………………………… 8 Requirements for chimney and flue duct……………………………………………………….. 9
INSTALLATION AND CONNECTION………………………………………………………………. 9 In general …………………………………………………………………………………………………………. 9 Installation in rooms with non- combustible material …………………………………….. 9 Installation in rooms with combustible material…………………………………………….. 9 Built-in example – right hinged door and top flue outlet……………………………….10 Built-in example – right hinged door and back outlet ……………………………………14 Built-in example – left hinged door and top flue outlet …………………………………16 Built-in example – left hinged door and back outlet………………………………………18 Installation instructions – top flue outlet …………………………………………………………19 Installation instructions – back outlet …………………………………………………………….25 Product information EcoDesign………………………………………………………………………31

Technical data
In general Congratulations on your new HWAM insert. We are pleased that you have chosen a HWAM insert and confident that it will give you much pleasure. To ensure optimum operation and safety, we recommend that the installation should be carried out by an authorised HWAM retailer or a fitter recommended by the retailer. For an overview of HWAM retailer, visit www.hwam.com under “Retailer locations”.
Safety The installation of your HWAM insert must always comply with all European, national and local building regulations. The installation must be carried out in accordance with the instructions in the installation and user manuals and subsequently registered with the local authorities. Upon installation, the chimney sweep must approve the installation before you can start using the insert. All HWAM insert packaging material must be handled in accordance with local waste management regulations.
Room requirements Always ensure a supply of fresh combustion air to the room where the insert is to be installed. The insert uses approx. 10-24 m3 of air per hour (depending on the setting of the air control lever). A window that can be opened or an adjustable air valve will be sufficient. It must not be possible to block the adjustable air valve/grate. In newly built/airtight dwellings, we recommend that a fresh air system should be installed for the direct supply of external air to the combustion. This fresh-air system may be bought separately.
Before installing the insert, make sure that the floor can carry the insert, the chimney and any other parts required for the installation.
Please be aware that not all glass parts are heat-resistant. For this reason, a glass wall should sometimes be treated as a flammable wall, in which case we ask you to contact your local chimney sweep or glass producer to hear at what distance the insert should be kept from glass.
Technical measures and data – right hinged door and top flue outlet HWAM I40/56c weighs 109 kg, and HWAM I40/56m weighs 106 kg (total weight). The following sketches show the different dimensions of the outer casing as well as the connecting dimensions for flue duct and fresh air system.

402

364

733

369

364

149

144

3

120 33

766

390

390

596 596 530
3 3 596 530 164
3 3
2 5 228 165

310 418

418 Page 4 of 16 pages

2 5 228 165

Right hinged door and back outlet

402

364

596

766 390

733

369 149

364 144 3

120 33

390

530

596

380

310

418

418

3 3 596 530 380 164
3 3

Page 5 of 16 pages

596
228 165 2 5

Left hinged door and top flue outlet

364

402

766 390

733

364 144 3

369 149

120 33

390

3 3 164
530 596
3 3 530 596

310

418

418

Page 6 of 16 pages

596
228 165 2 5

Left hinged door and back outlet

364

402

766 390

733

364
144 3

369 149

120 33

390

3 3 164
380 530 596 3 3
380 530 596

418

310

418

Page 7 of 16 pages

Test results from nominal test EN 13229 Nominal heating effect Flue gas temperature EN 13240 measurement point Flue gas temperature measured in the outlet socket Exhaust gas flow Efficiency Annual efficiency (EcoDesign) PM OGC NOx CO at 13% O2 CO at 13% O2 Energy efficiency index Energy efficiency class

7,1 kW 282ºC 337ºC 6,3 g/s 79 % 69 % 13 mg/m3 67 mg/m3 95 mg/m3 1056 mg/m3 0,0845 %
105 A

The declaration of performance can be downloaded from our website, www.hwam.com/dop

Type plate and serial number The insert comes with type plate and serial number on a pull-out plate between the insert and the cassette.

HWAM I 40/56

23 EN 13229:2001 / A2:2004 Inset appliances fired by solid fuel

Roomheater burning solid fuel without water supply

Thermal output:

7.1 kW

Fuel types

wood

Combustible materials ­ minimum distance to non-combustible insulation:

– Side

50 mm

– Behind

50 mm

Information about insulation and other dimensions see installation instructions

Distance to furnishings front

1300 mm

Distance to furnishings side

800 mm

CO Emission at 13% O2 Particles at 13% O2 OGC at 13% O2 Nox at 13% O2 Energy effiency Flue gas temperature EN 13229 measurement point Flue gas temperature measured in the outlet socket Surface temperature Cleanability Mechanical resistance (to carry a chimney/flue) Laboratory registration number Test report

0.085 % / 1056 mg/m3 13 mg/m3 67 mg/m3 95 mg/m3
79 %
282 °C
337 °C
Pass
Pass
Pass
NB 1235
300-ELAB-2659-EN

The appliance is capable of intermittent operation. The appliance can be used in a shared flue. Follow the user’s manual and use only recommended fuel. Declaration of Performance: www.hwam.com/dop/i40-56

HW Nyda DK

HWAM A/S Nydamsvej 53 – DK 8362 Hørning Tel.: (+45) 86 92 18 33 Fax: (+45) 86 92 22 18
EAN

S.nr.:

Locate the unique serial number of your insert and make a note of it below so that it is always easily accessible. The serial number must always be provided when contacting your HWAM retailer.

Serial number (starts with “G5”):

Floor plate European, national and local regulations must be observed in terms of the size and thickness of a non-combustible floor covering the floor in front of the combustion chamber opening. Ask your HWAM retailer for assistance. Dimensions of the combustion chamber opening can be seen in the illustrations below.

Right hinged door

Left hinged door

300 Combustion chamber opening 118
300 Combustion chamber
opening
118

676

90

Combustion chamber opening

676

Combustion chamber opening

90

B

Page 8 of 16 pages

Fyråbning i 40-56

Requirements for chimney and flue duct The height of the chimney must ensure sufficient draught and prevent any smoke nuisance. As a general rule, satisfactory draught conditions are achieved if the chimney is 4 m above the stove and at least 80 cm above the ridge. If the chimney is placed at side walls, the top of the chimney should always be higher than the ridge or the tallest point of the roof. Always be aware of any national and/or local regulations applying to thatched roofs and the location of the chimneys. The insert requires a minimum draught of 12 Pa (measured at EN 13229 measurement point). If measured just above the smoke flue socket, the chimney draught must be 18 – 20 Pa. The chimney must have a minimum clearing of Ø150 mm. The chimney must be provided with an easily accessible cleaning door. The chimney and flue duct must be of flue class T400 and be CE marked. Furthermore, it must have obtained the classification of G in soot fire testing. The required distance to combustible material must be complied with in accordance with the brand label. Ask your HWAM retailer for further information.
Installation and connection
In general HWAM I40/56 consists of a separate outer casing as well as a separate insert that is pushed into place and connected when the outer casing has been properly installed. We recommend installing a fresh air system that provides external air directly to the combustion (may be purchased separately as an accessory). Installation in rooms with non-combustible material If the insert is installed in rooms where there is no combustible material, we recommend a distance between masonry and the outer casing of 5 mm as a minimum. This should prevent the brickwork from cracking when the outer casing expands during use. The masonry above the casing must therefore be load bearing. Installation in rooms with combustible material If the insert is installed adjacent to combustible walls, a ventilated installation of non- combustible material such as calcium silicate or other material with a thermal conductivity (EN 12667 @ 10 °C) of less than 0.068 W/m x K must be built. Requirements for this installation appear from the illustrations in this installation guide. IMPORTANT For an installation height of 150 – 340 mm above the floor, a non-combustible construction of at least 600 mm is required in front of the insert. It is still considered a combustible floor even if an ember catching, non-combustible floor plate is placed on top of the combustible floor.
Page 9 of 16 pages

Min. 188

Built-in example – right hinged door
Min. 830 Min. 50

Min. 50

Min. 130

Distance from furniture to side glass min. 800

Min. 700

Min. 185*

Min. 1200

Min. 335*
Loft

Distance from furniture to glass pane
SECTION E-E

Min. 850 Distance from furniture to frontal glass min. 1200

Min. 1820

Combustible material

3

Fire wall – min. 50 mm Calcium Silicate

B-B

Insulated chimney

Min. 340

Min. 50

Min. 830
Sheet1
Min. 50
Brændbart materiale
Distance from
Brandmur – min. 50mm kafulcrniuitumresiltiokasitde
glass min. 800
Isoleret skorsten
i40-56 topafgang Min. 350

Gulv

S

Status: Com-Released

Part: Format:

HWAM A/S

Nydamsvej 53-55

DK – 8362 Hørning

A3

Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18

Scale: Thickness:

1:15 Created by:

mm Created date:

1

Weight:

kg. Tolerance: DS/EN

Material:

Distance from furniture to frontal
glass min. 1200

N B-B

Page 10 of 16 pages

Min. 188

Ceiling

H

Built-in example – left hinged door

w

Min. 300

Min. 700

Min. 830

Min. 185*

Min. 335*

Convection opening

M

Min. 50 min. 750 cm²

5 c

Min. 1750
Min. 50

Min. 1200

Distance from

2

furniture to side

c

glass min. 800

Distance from furniture to glass pane

Min. 130

Distance from furniture to frontal
glass min. 1200
Min. 350
Min. 850

SECTION E-E

3
B
Sheet1

Combustible material Fire wall – min. 50 mm Calcium Silicate Insulated chimney
Brændbart materiale

Floor

Convection opening min. 500 cm²
SECTION C-C

Status: Com-Released

Part: Format:

CAD-0190810 A3

HWAM A/S Nydamsvej 53-55 DK – 8362 Hørning Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18

Scale:

1:15 Created by:

Min. 830 Weight:

Created date: 3891.81 kg. Tolerance:

Material:

Rev. Date

Init. Com

C 10-10-2019 nis Frigiv B 27-05-2019 nis Frigiv A 27-05-2019 nis Frigiv

nis Item: 27-05-2019

Configuration name:
UK – HwMoademl: I40-55 sikker

Min. 50

Brandmur – minD. i5st0amncme kfraolmciumsilikat
furniture to side
Isoleret skorstenglass min. 800
i40-56 topafgang -Venstrehængt

Status: Com-Udvikling

Part: Format:

HWAM A/S

Nydamsvej 53-55

DK – 8362 Hørning

A3

Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18

Scale: Thickness:

1:15 Created by:

mm Created date:

05-

Weight:

kg. Tolerance: DS/EN 2

Material:

Min. 350

Distance from furniture to frontal
glass min. 1200 Min. 50

Page 11 of 16 pages

Built-in example – top flue outlet Distance from furniture to glass pane

Min. 350

3
Sheet1

SECTION E-E
Combustible material

Floor

Convection opening min. 500 cm²
SECTION C-C

Fire wall – min. 50 mm Calcium Silicate Insulated chimney
When running a pipe through a combustible wall, the approval of the specific pipe must be observed

Status: Com-Released

Rev. Date

Init. Comm

Part: Format:

CAD-0190810 A3

HWAM A/S Nydamsvej 53-55 DK – 8362 Hørning Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18

C 10-10-2019 nis Frigivet B 27-05-2019 nis Frigivet A 27-05-2019 nis Frigivet

Scale:

1:15 Created by:

nis Item:

Created date:

27-05-2019

Weight: Material:

3891.81 kg. Tolerance:

Configuration name:

Hollow spaces mUaKy – HwMoademl: I40-55 sikkerh

not be filled with

isolating material

Ceiling

Min. 150

Min. 150

Convection opening min. 562,5 cm²

Min. 40 mm insolated chimney

Min. 1820 Min. 400

Min. 340

Convection opening min. 375 cm²

Floor

Min. 490

SECTION A-A

Status: Com-Released

Rev. Date

Init. Comment

Part: Format:

HWAM A/S

Nydamsvej 53-55

DK – 8362 Hørning

A3

Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18

C 03-07-2023 jwa x B 07-02-2023 jwa x A 22-02-2022 jwa x

Scale: Thickness: Weight: Material:

1:15 mm kg.

Created by: Created date: Tolerance:

jwa Item: Afstand til brændbart og indbygning af i40-

16-02-2022

56

DS/EN 22768P-mageCo1n2figoufra1ti6onpnaagmees:

Model:

HWAM I40/56

Item number:

Drawing number:
CAD-0198503

Built-in example – back outlet Distance from furniture to glass pane SECTION E-E

3
Sheet1

Combustible material Fire wall – min. 50 mm Calcium Silicate Insulated chimney

Ceiling

Min. 350

Floor

Convection opening min. 500 cm²
SECTION C-C

Status: Com-Released

Part: Format:

CAD-0190810 A3

HWAM A/S Nydamsvej 53-55 DK – 8362 Hørning Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18

Scale:

1:15 Created by:

Created date:

Weight: 3891.81 kg. Tolerance:

Material:

Rev. Date

Init. Comm

C 10-10-2019 nis Frigivet B 27-05-2019 nis Frigivet A 27-05-2019 nis Frigivet

nis Item: 27-05-2019

Configuration name:
UK – HwMoademl: I40-55 sikkerh

Hollow spaces may not be filled with isolating material

Min. 150 Min. 150

Min. 1820 Min. 400

Convection opening min. 562,5 cm²

40 mm insolated chimney

Convection opening min. 375 cm²

When running a pipe through a combustible wall, the approval of the specific pipe must be observed

Min. 340

Floor

Min. 490

SECTION C-C

Status: Com-Udvikling

Rev. Date

Init. Comment

Part: Format:

HWAM A/S

Nydamsvej 53-55

DK – 8362 Hørning

A3

Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18

01 05-07-2023 jwa Created

Scale:

1:15 Created by:

jwa Item: Afstand til brændbart og indbygning af i40- Item number:

Thickness:

mm Created date:

05-07-202P3age 13 o5f61-6Vpenasgtersehængt

Weight: Material:

kg. Tolerance:

DS/EN 22768-m Configuration name: Model:

Drawing number:
HWAM I40/56 CAD-0200956

Installation instructions – top flue outlet Install the outer casing and the insert as shown in the following illustrations. Before mounting, any preliminary steps before the installation of fresh air system must have been completed. Polystyrene from packaging may be placed on the floor and serve as protection for the insert when it is lifted out of the casing.
Note: It is VERY important to secure the outer casing to the support with screws. Otherwise it may fall out during servicing when the insert is turned out of the casing.
Important: The screws for illustration 20 and 21 are in the bag in the burning chamber.

1

2

3

4

5

6

Page 14 of 16 pages

7

8

9

10

11

12

Page 15 of 16 pages

13

14

15

16

17

18

19

20

Page 16 of 16 pages

21

22

23

24

25

26

Page 17 of 16 pages

27

28

29

30

31

32

33

34

Page 18 of 16 pages

35

36

37

38

39

Page 19 of 16 pages

Installation instructions – back outlet Install the outer casing and the insert as shown in the following illustrations. Before mounting, any preliminary steps before the installation of fresh air system must have been completed. Polystyrene from packaging may be placed on the floor and serve as protection for the insert when it is lifted out of the casing.
Note: It is VERY important to secure the outer casing to the support with screws. Otherwise it may fall out during servicing when the insert is turned out of the casing.
Important: The screws for illustration 20 and 21 are in the bag in the burning chamber. Installation instructions – top flue outlet

1

2

3

4

5

6

Page 20 of 16 pages

7

8

9

10

11

12

Page 21 of 16 pages

13

14

15

16

17

18

19

20

Page 22 of 16 pages

21

22

23

24

25

26

Page 23 of 16 pages

27

28

29

30

31

32

33

34

Page 24 of 16 pages

35

36

37

38

39

Page 25 of 16 pages

Product information on solid fuel local space heaters according to Comission regulation (EU) 2015/1185

Model
Direct heat output [kW] Indirect heating functionality Indirect heat output [kW] Type of heat output/room temperature control

HWAM I 40/56
7,1 No –
Two ore more manual stages, no temperature control

Space heating performance at nominal heat output

Fuel

Preferred fuel

Seasonal space heating energy efficiency [%]

Wood logs with moisture content 12-18 %

Yes

79

Emissions

mg/m3 (13% O2)

Particulate matter (PM)

13

Organic gaseous compounds (OGC)

67

Carbon monoxide (CO)

1056

Nitrogen oxides (NO)

95

Characteristics when operating with the prefered fuel only

Nominal heat output [kW]

7,1

Electric power consumption nominal heat output [kW]

Electric power consumption minimum heat output [kW]

Electric power consumption standby mode [kW]

Useful efficiency at nominal heat output [%]

79

Energy efficiency index

105

Energy efficiency class

A

Specific Precautions during Assembling, Installing & Maintenance: See installation instructions for more information
Product End-of-Life/Recycling: To dispose of the stove after the product life has expired, please observe the following information
· Dispose of the items correctly i.e. separate the parts to be disposed of in material groups · Always dispose of items in a way that is as sustainable as possible and that is in line with the current environmental protection, reprocessing/recycling and disposal technology

HWAM A/S · Nydamsvej 53 · DK-8362 Hørning Page 26 of 16 pages

. Page 27 of 16 pages

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)