HWAM 97-9721 Wood Burning Stove Insert Instruction Manual
- September 28, 2024
- Hwam
Table of Contents
97-9721 Wood Burning Stove Insert
“`html
Product Information
Specifications
-
Model: HWAM I 40/56
-
Thermal Output: 7.1 kW
-
Fuel Types: Wood
-
Distance to Furnishings Front: 1300 mm
-
Distance to Furnishings Side: 800 mm
-
CO Emission at 13% O2: 0.085% / 1056
mg/m3 -
Particles at 13% O2: 13 mg/m3
-
OGC at 13% O2: 67 mg/m3
-
Nox at 13% O2: 95 mg/m3
-
Energy Efficiency: 79%
-
Flue Gas Temperature (EN 13229): Measurement
point and outlet socket -
Cleanability: Pass
-
Mechanical Resistance: Pass
-
Laboratory Registration Number: NB 1235
-
Test Report: 300-ELAB-2659-EN
Product Usage Instructions
Installation
Before installing the insert, ensure that the floor can support
the insert, chimney, and any other necessary parts. Contact an
authorized HWAM retailer or recommended fitter for
installation.
Safety Precautions
Ensure that all glass parts are heat-resistant. Consult your
local chimney sweep or glass producer to determine the safe
distance between the insert and any flammable materials like
glass.
Maintenance
Regularly clean the insert following the manufacturer’s
guidelines. Ensure proper ventilation and airflow around the unit
for efficient operation.
FAQ (Frequently Asked Questions)
Q: Can this appliance be used continuously?
A: The appliance is capable of intermittent operation. Follow
the user manual for usage instructions.
Q: What type of fuel should be used?
A: Only use the recommended fuel types specified in the user
manual to ensure safe and efficient operation.
Q: Where can I find the Declaration of Performance?
A: The Declaration of Performance can be downloaded from
www.hwam.com/dop/i40-56.
“`
Installation instructions EN
I 40/56
23.04.2024 / 97-9721 www.hwam.com
TABLE OF CONTENTS
TECHNICAL DATA……………………………………………………………………………………………. 4 In general
…………………………………………………………………………………………………………. 4
Safety………………………………………………………………………………………………………………… 4 Room requirements
…………………………………………………………………………………………. 4 Technical measures and data – right
hinged door and top flue outlet…………. 4 Technical measures and data – right
hinged door and back outlet ……………… 5 Technical measures and data – left hinged
door and top flue outlet……………. 6 Technical measures and data – left hinged
door and back outlet………………….7 Type plate and serial number
…………………………………………………………………………. 8 Floor plate
………………………………………………………………………………………………………… 8 Requirements for chimney and flue
duct……………………………………………………….. 9
INSTALLATION AND CONNECTION………………………………………………………………. 9 In general
…………………………………………………………………………………………………………. 9 Installation in rooms with non-
combustible material …………………………………….. 9 Installation in rooms with combustible
material…………………………………………….. 9 Built-in example – right hinged door and top
flue outlet……………………………….10 Built-in example – right hinged door and back
outlet ……………………………………14 Built-in example – left hinged door and top flue
outlet …………………………………16 Built-in example – left hinged door and back
outlet………………………………………18 Installation instructions – top flue outlet
…………………………………………………………19 Installation instructions – back outlet
…………………………………………………………….25 Product information
EcoDesign………………………………………………………………………31
Technical data
In general Congratulations on your new HWAM insert. We are pleased that you
have chosen a HWAM insert and confident that it will give you much pleasure.
To ensure optimum operation and safety, we recommend that the installation
should be carried out by an authorised HWAM retailer or a fitter recommended
by the retailer. For an overview of HWAM retailer, visit www.hwam.com under
“Retailer locations”.
Safety The installation of your HWAM insert must always comply with all
European, national and local building regulations. The installation must be
carried out in accordance with the instructions in the installation and user
manuals and subsequently registered with the local authorities. Upon
installation, the chimney sweep must approve the installation before you can
start using the insert. All HWAM insert packaging material must be handled in
accordance with local waste management regulations.
Room requirements Always ensure a supply of fresh combustion air to the room
where the insert is to be installed. The insert uses approx. 10-24 m3 of air
per hour (depending on the setting of the air control lever). A window that
can be opened or an adjustable air valve will be sufficient. It must not be
possible to block the adjustable air valve/grate. In newly built/airtight
dwellings, we recommend that a fresh air system should be installed for the
direct supply of external air to the combustion. This fresh-air system may be
bought separately.
Before installing the insert, make sure that the floor can carry the insert,
the chimney and any other parts required for the installation.
Please be aware that not all glass parts are heat-resistant. For this reason,
a glass wall should sometimes be treated as a flammable wall, in which case we
ask you to contact your local chimney sweep or glass producer to hear at what
distance the insert should be kept from glass.
Technical measures and data – right hinged door and top flue outlet HWAM
I40/56c weighs 109 kg, and HWAM I40/56m weighs 106 kg (total weight). The
following sketches show the different dimensions of the outer casing as well
as the connecting dimensions for flue duct and fresh air system.
402
364
733
369
364
149
144
3
120 33
766
390
390
596 596 530
3 3 596 530 164
3 3
2 5 228 165
310 418
418 Page 4 of 16 pages
2 5 228 165
Right hinged door and back outlet
402
364
596
766 390
733
369 149
364 144 3
120 33
390
530
596
380
310
418
418
3 3 596 530 380 164
3 3
Page 5 of 16 pages
596
228 165 2 5
Left hinged door and top flue outlet
364
402
766 390
733
364 144 3
369 149
120 33
390
3 3 164
530 596
3 3 530 596
310
418
418
Page 6 of 16 pages
596
228 165 2 5
Left hinged door and back outlet
364
402
766 390
733
364
144 3
369 149
120 33
390
3 3 164
380 530 596 3 3
380 530 596
418
310
418
Page 7 of 16 pages
Test results from nominal test EN 13229 Nominal heating effect Flue gas temperature EN 13240 measurement point Flue gas temperature measured in the outlet socket Exhaust gas flow Efficiency Annual efficiency (EcoDesign) PM OGC NOx CO at 13% O2 CO at 13% O2 Energy efficiency index Energy efficiency class
7,1 kW 282ºC 337ºC 6,3 g/s 79 % 69 % 13 mg/m3 67 mg/m3 95 mg/m3 1056 mg/m3
0,0845 %
105 A
The declaration of performance can be downloaded from our website, www.hwam.com/dop
Type plate and serial number The insert comes with type plate and serial number on a pull-out plate between the insert and the cassette.
HWAM I 40/56
23 EN 13229:2001 / A2:2004 Inset appliances fired by solid fuel
Roomheater burning solid fuel without water supply
Thermal output:
7.1 kW
Fuel types
wood
Combustible materials minimum distance to non-combustible insulation:
– Side
50 mm
– Behind
50 mm
Information about insulation and other dimensions see installation instructions
Distance to furnishings front
1300 mm
Distance to furnishings side
800 mm
CO Emission at 13% O2 Particles at 13% O2 OGC at 13% O2 Nox at 13% O2 Energy effiency Flue gas temperature EN 13229 measurement point Flue gas temperature measured in the outlet socket Surface temperature Cleanability Mechanical resistance (to carry a chimney/flue) Laboratory registration number Test report
0.085 % / 1056 mg/m3 13 mg/m3 67 mg/m3 95 mg/m3
79 %
282 °C
337 °C
Pass
Pass
Pass
NB 1235
300-ELAB-2659-EN
The appliance is capable of intermittent operation. The appliance can be used in a shared flue. Follow the user’s manual and use only recommended fuel. Declaration of Performance: www.hwam.com/dop/i40-56
HW Nyda DK
HWAM A/S Nydamsvej 53 – DK 8362 Hørning Tel.: (+45) 86 92 18 33 Fax: (+45) 86
92 22 18
EAN
S.nr.:
Locate the unique serial number of your insert and make a note of it below so that it is always easily accessible. The serial number must always be provided when contacting your HWAM retailer.
Serial number (starts with “G5”):
Floor plate European, national and local regulations must be observed in terms of the size and thickness of a non-combustible floor covering the floor in front of the combustion chamber opening. Ask your HWAM retailer for assistance. Dimensions of the combustion chamber opening can be seen in the illustrations below.
Right hinged door
Left hinged door
300 Combustion chamber opening 118
300 Combustion chamber
opening
118
676
90
Combustion chamber opening
676
Combustion chamber opening
90
B
Page 8 of 16 pages
Fyråbning i 40-56
Requirements for chimney and flue duct The height of the chimney must ensure
sufficient draught and prevent any smoke nuisance. As a general rule,
satisfactory draught conditions are achieved if the chimney is 4 m above the
stove and at least 80 cm above the ridge. If the chimney is placed at side
walls, the top of the chimney should always be higher than the ridge or the
tallest point of the roof. Always be aware of any national and/or local
regulations applying to thatched roofs and the location of the chimneys. The
insert requires a minimum draught of 12 Pa (measured at EN 13229 measurement
point). If measured just above the smoke flue socket, the chimney draught must
be 18 – 20 Pa. The chimney must have a minimum clearing of Ø150 mm. The
chimney must be provided with an easily accessible cleaning door. The chimney
and flue duct must be of flue class T400 and be CE marked. Furthermore, it
must have obtained the classification of G in soot fire testing. The required
distance to combustible material must be complied with in accordance with the
brand label. Ask your HWAM retailer for further information.
Installation and connection
In general HWAM I40/56 consists of a separate outer casing as well as a
separate insert that is pushed into place and connected when the outer casing
has been properly installed. We recommend installing a fresh air system that
provides external air directly to the combustion (may be purchased separately
as an accessory). Installation in rooms with non-combustible material If the
insert is installed in rooms where there is no combustible material, we
recommend a distance between masonry and the outer casing of 5 mm as a
minimum. This should prevent the brickwork from cracking when the outer casing
expands during use. The masonry above the casing must therefore be load
bearing. Installation in rooms with combustible material If the insert is
installed adjacent to combustible walls, a ventilated installation of non-
combustible material such as calcium silicate or other material with a thermal
conductivity (EN 12667 @ 10 °C) of less than 0.068 W/m x K must be built.
Requirements for this installation appear from the illustrations in this
installation guide. IMPORTANT For an installation height of 150 – 340 mm above
the floor, a non-combustible construction of at least 600 mm is required in
front of the insert. It is still considered a combustible floor even if an
ember catching, non-combustible floor plate is placed on top of the
combustible floor.
Page 9 of 16 pages
Min. 188
Built-in example – right hinged door
Min. 830 Min. 50
Min. 50
Min. 130
Distance from furniture to side glass min. 800
Min. 700
Min. 185*
Min. 1200
Min. 335*
Loft
Distance from furniture to glass pane
SECTION E-E
Min. 850 Distance from furniture to frontal glass min. 1200
Min. 1820
Combustible material
3
Fire wall – min. 50 mm Calcium Silicate
B-B
Insulated chimney
Min. 340
Min. 50
Min. 830
Sheet1
Min. 50
Brændbart materiale
Distance from
Brandmur – min. 50mm kafulcrniuitumresiltiokasitde
glass min. 800
Isoleret skorsten
i40-56 topafgang Min. 350
Gulv
S
Status: Com-Released
Part: Format:
HWAM A/S
Nydamsvej 53-55
DK – 8362 Hørning
A3
Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18
Scale: Thickness:
1:15 Created by:
mm Created date:
1
Weight:
kg. Tolerance: DS/EN
Material:
Distance from furniture to frontal
glass min. 1200
N B-B
Page 10 of 16 pages
Min. 188
Ceiling
H
Built-in example – left hinged door
w
Min. 300
Min. 700
Min. 830
Min. 185*
Min. 335*
Convection opening
M
Min. 50 min. 750 cm²
5 c
Min. 1750
Min. 50
Min. 1200
Distance from
2
furniture to side
c
glass min. 800
Distance from furniture to glass pane
Min. 130
Distance from furniture to frontal
glass min. 1200
Min. 350
Min. 850
SECTION E-E
3
B
Sheet1
Combustible material Fire wall – min. 50 mm Calcium Silicate Insulated chimney
Brændbart materiale
Floor
Convection opening min. 500 cm²
SECTION C-C
Status: Com-Released
Part: Format:
CAD-0190810 A3
HWAM A/S Nydamsvej 53-55 DK – 8362 Hørning Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18
Scale:
1:15 Created by:
Min. 830 Weight:
Created date: 3891.81 kg. Tolerance:
Material:
Rev. Date
Init. Com
C 10-10-2019 nis Frigiv B 27-05-2019 nis Frigiv A 27-05-2019 nis Frigiv
nis Item: 27-05-2019
Configuration name:
UK – HwMoademl: I40-55 sikker
Min. 50
Brandmur – minD. i5st0amncme kfraolmciumsilikat
furniture to side
Isoleret skorstenglass min. 800
i40-56 topafgang -Venstrehængt
Status: Com-Udvikling
Part: Format:
HWAM A/S
Nydamsvej 53-55
DK – 8362 Hørning
A3
Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18
Scale: Thickness:
1:15 Created by:
mm Created date:
05-
Weight:
kg. Tolerance: DS/EN 2
Material:
Min. 350
Distance from furniture to frontal
glass min. 1200 Min. 50
Page 11 of 16 pages
Built-in example – top flue outlet Distance from furniture to glass pane
Min. 350
3
Sheet1
SECTION E-E
Combustible material
Floor
Convection opening min. 500 cm²
SECTION C-C
Fire wall – min. 50 mm Calcium Silicate Insulated chimney
When running a pipe through a combustible wall, the approval of the specific
pipe must be observed
Status: Com-Released
Rev. Date
Init. Comm
Part: Format:
CAD-0190810 A3
HWAM A/S Nydamsvej 53-55 DK – 8362 Hørning Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18
C 10-10-2019 nis Frigivet B 27-05-2019 nis Frigivet A 27-05-2019 nis Frigivet
Scale:
1:15 Created by:
nis Item:
Created date:
27-05-2019
Weight: Material:
3891.81 kg. Tolerance:
Configuration name:
Hollow spaces mUaKy – HwMoademl: I40-55 sikkerh
not be filled with
isolating material
Ceiling
Min. 150
Min. 150
Convection opening min. 562,5 cm²
Min. 40 mm insolated chimney
Min. 1820 Min. 400
Min. 340
Convection opening min. 375 cm²
Floor
Min. 490
SECTION A-A
Status: Com-Released
Rev. Date
Init. Comment
Part: Format:
HWAM A/S
Nydamsvej 53-55
DK – 8362 Hørning
A3
Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18
C 03-07-2023 jwa x B 07-02-2023 jwa x A 22-02-2022 jwa x
Scale: Thickness: Weight: Material:
1:15 mm kg.
Created by: Created date: Tolerance:
jwa Item: Afstand til brændbart og indbygning af i40-
16-02-2022
56
DS/EN 22768P-mageCo1n2figoufra1ti6onpnaagmees:
Model:
HWAM I40/56
Item number:
–
Drawing number:
CAD-0198503
Built-in example – back outlet Distance from furniture to glass pane SECTION E-E
3
Sheet1
Combustible material Fire wall – min. 50 mm Calcium Silicate Insulated chimney
Ceiling
Min. 350
Floor
Convection opening min. 500 cm²
SECTION C-C
Status: Com-Released
Part: Format:
CAD-0190810 A3
HWAM A/S Nydamsvej 53-55 DK – 8362 Hørning Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18
Scale:
1:15 Created by:
Created date:
Weight: 3891.81 kg. Tolerance:
Material:
Rev. Date
Init. Comm
C 10-10-2019 nis Frigivet B 27-05-2019 nis Frigivet A 27-05-2019 nis Frigivet
nis Item: 27-05-2019
Configuration name:
UK – HwMoademl: I40-55 sikkerh
Hollow spaces may not be filled with isolating material
Min. 150 Min. 150
Min. 1820 Min. 400
Convection opening min. 562,5 cm²
40 mm insolated chimney
Convection opening min. 375 cm²
When running a pipe through a combustible wall, the approval of the specific pipe must be observed
Min. 340
Floor
Min. 490
SECTION C-C
Status: Com-Udvikling
Rev. Date
Init. Comment
Part: Format:
HWAM A/S
Nydamsvej 53-55
DK – 8362 Hørning
A3
Tel. (+45) 86 92 18 33 Fax (+45) 86 92 22 18
01 05-07-2023 jwa Created
Scale:
1:15 Created by:
jwa Item: Afstand til brændbart og indbygning af i40- Item number:
Thickness:
mm Created date:
05-07-202P3age 13 o5f61-6Vpenasgtersehængt
–
Weight: Material:
kg. Tolerance:
DS/EN 22768-m Configuration name: Model:
Drawing number:
HWAM I40/56 CAD-0200956
Installation instructions – top flue outlet Install the outer casing and the
insert as shown in the following illustrations. Before mounting, any
preliminary steps before the installation of fresh air system must have been
completed. Polystyrene from packaging may be placed on the floor and serve as
protection for the insert when it is lifted out of the casing.
Note: It is VERY important to secure the outer casing to the support with
screws. Otherwise it may fall out during servicing when the insert is turned
out of the casing.
Important: The screws for illustration 20 and 21 are in the bag in the burning
chamber.
1
2
3
4
5
6
Page 14 of 16 pages
7
8
9
10
11
12
Page 15 of 16 pages
13
14
15
16
17
18
19
20
Page 16 of 16 pages
21
22
23
24
25
26
Page 17 of 16 pages
27
28
29
30
31
32
33
34
Page 18 of 16 pages
35
36
37
38
39
Page 19 of 16 pages
Installation instructions – back outlet Install the outer casing and the
insert as shown in the following illustrations. Before mounting, any
preliminary steps before the installation of fresh air system must have been
completed. Polystyrene from packaging may be placed on the floor and serve as
protection for the insert when it is lifted out of the casing.
Note: It is VERY important to secure the outer casing to the support with
screws. Otherwise it may fall out during servicing when the insert is turned
out of the casing.
Important: The screws for illustration 20 and 21 are in the bag in the burning
chamber. Installation instructions – top flue outlet
1
2
3
4
5
6
Page 20 of 16 pages
7
8
9
10
11
12
Page 21 of 16 pages
13
14
15
16
17
18
19
20
Page 22 of 16 pages
21
22
23
24
25
26
Page 23 of 16 pages
27
28
29
30
31
32
33
34
Page 24 of 16 pages
35
36
37
38
39
Page 25 of 16 pages
Product information on solid fuel local space heaters according to Comission regulation (EU) 2015/1185
Model
Direct heat output [kW] Indirect heating functionality Indirect heat output
[kW] Type of heat output/room temperature control
HWAM I 40/56
7,1 No –
Two ore more manual stages, no temperature control
Space heating performance at nominal heat output
Fuel
Preferred fuel
Seasonal space heating energy efficiency [%]
Wood logs with moisture content 12-18 %
Yes
79
Emissions
mg/m3 (13% O2)
Particulate matter (PM)
13
Organic gaseous compounds (OGC)
67
Carbon monoxide (CO)
1056
Nitrogen oxides (NO)
95
Characteristics when operating with the prefered fuel only
Nominal heat output [kW]
7,1
Electric power consumption nominal heat output [kW]
–
Electric power consumption minimum heat output [kW]
–
Electric power consumption standby mode [kW]
–
Useful efficiency at nominal heat output [%]
79
Energy efficiency index
105
Energy efficiency class
A
Specific Precautions during Assembling, Installing & Maintenance: See
installation instructions for more information
Product End-of-Life/Recycling: To dispose of the stove after the product life
has expired, please observe the following information
· Dispose of the items correctly i.e. separate the parts to be disposed of in
material groups · Always dispose of items in a way that is as sustainable as
possible and that is in line with the current environmental protection,
reprocessing/recycling and disposal technology
HWAM A/S · Nydamsvej 53 · DK-8362 Hørning Page 26 of 16 pages