Knightsbridge EMPDL LED Emergency Downlight Installation Guide
- September 24, 2024
- Knightsbridge
Table of Contents
EMPDL LED Emergency Downlight
“`html
Product Information
Specifications:
- Product Name: EMPDL
- Manufacturer: ML Accessories Limited
- Model Number: DCSEP21_V2
- Warranty: Refer to warranty section
Product Usage Instructions:
Safety Precautions:
Before installation, ensure the area is clear of any joists,
gas/water pipes, or electrical cables. Refer to Fig. 1, Fig. 2, and
Fig. 3 for guidance on placement.
Installation:
Install the product ensuring it is not in contact with any
obstructions such as joists, gas/water pipes, or electrical cables.
Perform an emergency duration test after installation to verify
functionality.
Maintenance:
Do not attempt high voltage or insulation resistance testing
without disconnecting the product from the circuit to prevent
irreparable damage. Clean the luminaire with a soft dry cloth only;
avoid aggressive cleaning products or solvents.
Battery Maintenance:
Ensure charge and discharge cycles are completed periodically to
maintain battery capacity.
FAQ:
Q: Can the light source be replaced?
A: No, the light source of this luminaire is not replaceable.
When it reaches its end of life, the entire luminaire should be
replaced.
Q: How should I clean the product?
A: Clean the product with a soft dry cloth only. Avoid using
aggressive cleaning products or solvents as they may damage the
product.
Q: What should I do if subjected to high voltage testing?
A: Disconnect the product from the circuit before subjecting it
to any high voltage or insulation resistance testing to prevent
irreparable damage.
“`
INSTALLATION & MAINTENANCE MANUAL
EMPDL
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by
the end user for future reference and maintenance. These instructions should
be used to aid installation of the following product: EMPDL
SAFETY
· This product must be installed in accordance with the latest edition of the
IEE Wiring Regulations (BS7671) and current Building Regulations. If in any
doubt, consult a qualified electrician
· Please isolate mains prior to installation or maintenance · Check the total
load on the circuit (including when this luminaire is fitted) does not exceed
the rating of the
circuit cable, fuse or circuit breaker · Please note the IP (Ingress
Protection) rating of this product when deciding the location for installation
· Allow 50mm above and around the fitting for air dissipation (do not cover
the fitting with insulation) · This product is for indoor use only · This
product is Class II double insulated · This product is IP20 rated
INSTALLATION
· Provide power to the required point of installation · Cut a suitable hole in
the mounting surface as per the cut-out details (see Fig. 1) ensuring not to
infringe
with any joists, gas / water pipes or electrical cables
Fig. 1
· · This fitting will suit 70mm 130mm cut-outs when using the adaptor ring
(see Fig. 2) ·
Fig. 2
· Connect the luminaire to the mains supply via a suitable junction box (not
supplied) ensuring the correct polarity is observed: L – Live (brown), N –
Neutral (blue) (see Fig. 3)
·
Fig. 3
· Connect the battery via the plug and socket to the inverter
· · Place the battery and inverter into the ceiling void ensuring that there is at least 50mm of clearance above
·
and around them
· Lift both of the spring clips on the sides of the luminaire and push into the ceiling
· · Switch on and check for correct operation, ensuring the green indicator LED is illuminated
· ·
· We recommend, on commissioning the installation, a minimum charge period of 24-36 hours before
carrying out an emergency duration test
· · If the batteries have been left in a discharged state for an extended period, we recommend that one or more
charge and discharge cycles are completed which should help to restore the battery capacity
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
The light source of this luminaire is not replaceable; when the light source
reaches its end of life the whole luminaire should be replaced. Clean with a
soft dry cloth only, do not use aggressive cleaning products or solvents which
may damage the product.
Installing in areas where the temperature consistently drops below 0°C may
shorten the battery life. This product is non-dimmable. This product should be
recycled in the correct manner when it reaches the end of its life. Check
local authorities for where facilities exist. The batteries in this luminaire
are Nickel Cadmium and must be disposed of correctly. Please contact the local
authorities for the disposal of this toxic waste.
WARRANTY
This product has a warranty of 3 years (excluding battery) from date of
purchase. Failure to install this product in accordance with the current
edition of the IEE Wiring Regulations (BS7671), improper use, or removal of
the batch code will invalidate the warranty. If this product should fail
within its warranty period, it should be returned to the place of purchase for
a free of charge replacement. ML Accessories does not accept responsibility
for any installation costs associated with the replacement product. Your
statutory rights are not affected. ML Accessories reserve the right to alter
product specification without prior notice.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266 · Daily check
check LED charge indicator is illuminated · Monthly functional test – simulate
a mains supply failure for approx. 30 seconds by operation of key switch
or switching off circuit breaker. Ensure normal supply is restored after test
and ensure charge indicator is illuminated · Annual three hour duration test –
simulate a mains supply failure for three hour continuous test by operation of
key switch or switching off circuit breaker. Ensure normal supply is restored
after test and ensure charge indicator is illuminated · If the luminaire fails
any of the above tests, please contact a qualified electrician. See below for
test record sheet
INTERNATIONAL CONTACT DETAILS
0~ 45°C TA
54
ML Accessories Limited LU5 4LT www.mlaccessories.co.uk
DCSEP21_V2
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>