condair RS Series Electrode Boiler Steam Humidifier Instruction Manual
- September 21, 2024
- condair
Table of Contents
- RS Series Electrode Boiler Steam Humidifier
- Product Information: Steam Humidifier Condair RS Series
- Specifications:
- Product Overview:
- Models Overview:
- Identification of the Unit:
- 1. Receiving and Storage:
- 2. Mounting and Installation Work:
- 3. Steam Installation:
- 4. Water Installation:
- 5. Electrical Installation:
- Q: What should I do if I have questions after reading the
RS Series Electrode Boiler Steam Humidifier
Product Information: Steam Humidifier Condair RS Series
Specifications:
- Product: Steam humidifier Condair RS series
- Functions: Humidification, Dehumidification, and Evaporative
Cooling
Product Overview:
Models Overview:
- Units Small (S) and Medium (M)
- Units Large (L)
Identification of the Unit:
- Product Designation
- Options
- Accessories
Installation Instructions:
1. Receiving and Storage:
Inspection: Upon receipt, inspect the unit for
any visible damage.
Storage and Transportation: Store and transport
the unit following manufacturer guidelines.
2. Mounting and Installation Work:
Safety Notes: Follow safety guidelines during
mounting and installation work.
Installation Overviews: Detailed steps for
mounting and installation provided in the manual.
3. Steam Installation:
Includes instructions on installing steam distributors, steam
lines, condensate lines, and common errors to avoid.
4. Water Installation:
Detailed overview of water installation with additional
requirements for specific options.
5. Electrical Installation:
Guidelines for electrical installation including wiring
diagrams, external connections, fuses, and inspection.
FAQ:
Q: What should I do if I have questions after reading the
documentation?
A: Contact your Condair representative for
assistance.
2582419-F EN 2406
INSTALLATION MANUAL
Steam humidifier Condair RS series
Humidification, Dehumidification and Evaporative Cooling
Thank you for choosing Condair
Installation date (MM/DD/YYYY): Commissioning date (MM/DD/YYYY): Site: Model:
Serial number:
Contact Condair Ltd. 2740 Fenton Road, Ottawa, Ontario K1T3T7 TEL:
1.866.667.8321, FAX: 613.822.7964 EMAIL: na.info@condair.com, WEBSITE:
www.condair.com Proprietary Notice This document and the information disclosed
herein are proprietary data of Condair Ltd. Neither this document, nor the
information contained herein shall be reproduced, used, or disclosed to others
without the written authorization of Condair Ltd., except to the extent
required for installation or maintenance of recipient’s equipment. Liability
Notice Condair Ltd. does not accept any liability due to incorrect
installation or operation of the equipment or due to the use of
parts/components/equipment that are not authorized by Condair Ltd. Copyright
Notice © Condair Ltd. All rights reserved. Technical modifications reserved
Contents
1
Introduction
1.1
Before You Begin
1.2
Notes on the Installation Manual
2
For Your Safety
3
3.1 3.1.1 3.1.2 3.2 3.3 3.4 3.5
Product Overview
Models Overview Units Small (“S”) and Medium (“M”) Units Large (“L”)
Identification of the Unit Product Designation Options Accessories
4
Receiving and Storage
4.1
Inspection
4.2
Storage and Transportation
5
5.1
5.2
5.3 5.3.1 5.3.2 5.3.2.1 5.3.2.2 5.3.3
5.4 5.4.1 5.4.2 5.4.3 5.4.4 5.4.5 5.4.6
5.5
5.6 5.6.1 5.6.2 5.6.3 5.6.3.1 5.6.3.2 5.6.3.3 5.6.4
5.7 5.7.1 5.7.2
Mounting and Installation Work
Safety Notes on Mounting and Installation Work
Installation Overviews
Mounting the Unit Notes on Locating the Unit Mounting the Humidifier
Standard Mounting Wall Support Mounting (option)
Inspecting the Installed Unit
Steam Installation Overview Steam Installation for Duct Humidification
Installing the Steam Distributors Overview Steam Installation for Room
Humidification Positioning and Mounting the Blower Packs Installing the Steam
and Condensate lines Common Steam and Condensate Line Errors
Inspecting the Steam Installation
Water Installation Overviews Water Installation Overviews Water Installation
(with RS-RO option installed) Notes on Water Installation
Water Supply (Potable, RO or DI water) Additional Requirements for RS-RO
Option Water Supply Water Drain
Inspecting the Water Installation
Notes on Humidity Control Systems/Humidity Control Control Device Locations
Admissible Control Signals
2582419-F EN 2406
5 5 5
7
9 9 9 10 11 12 13 14
15 15 15
16 16 17 19 19 21 21 24 26 27 27 27 28 29 30 35 36 37 37 38 40 40 41 42 42 44
44 44
Contents 3
5.8
Electrical Installation
45
5.8.1
Notes on Electrical Installation
45
5.8.2 46
Wiring Diagram Condair RS – Small and Medium Units
5.8.3 47
Wiring Diagram Condair RS – Large Units
5.8.4
Installation Work External Connections
48
5.8.5
Connecting Multiple Units Using Linkup
53
5.8.6
Fuses “F3” Voltage Supply
54
5.8.7
Inspecting the Electrical Installation
55
6
Appendix
56
6.1
Unit Dimensions
56
4 Contents
2582419-F EN 2406
1 Introduction
1.1 Before You Begin
Thank you for purchasing the Condair RS steam humidifier.
The Condair RS steam humidifier incorporates the latest technical advances and
meets all recognized safety standards. Nevertheless, improper use of the
Condair RS steam humidifier may result in danger to the user or third parties
and/or damage to property.
To ensure a safe, proper, and economical operation of the Condair RS steam
humidifier, please observe and comply with all information and safety
instructions contained in the present documentation as well as in the separate
documentations of the components installed in the humidification system.
If you have questions after reading this documentation, please contact your
Condair representative. They will be glad to assist you.
1.2 Notes on the Installation Manual
Limitation The subject of this installation manual is the Condair RS steam
humidifier in its different versions.The various options and accessories are
only described insofar as is necessary for proper operation of the equipment.
Further information on options and accessories can be obtained in their
respective instructions.
This installation manual is restricted to the installation of the Condair RS
steam humidifier and is meant for well trained personnel being sufficiently
qualified for their respective work.
This installation manual is supplemented by various separate items of
documentation (operation manual, spare parts list, etc.), which are included
in the delivery as well. Where necessary, appropriate crossreferences are made
to these publications in the installation manual.
2582419-F EN 2406
Introduction 5
Symbols used in this manual
CAUTION!
The catchword “CAUTION” used in conjunction with the caution symbol in the
circle designates notes in this installation manual that, if neglected, may
cause damage and/or malfunction of the unit or damage to property.
WARNING!
The catchword “WARNING” used in conjunction with the general caution symbol
designates safety and danger notes in this installation manual that, if
neglected, may cause injury to persons.
DANGER!
The catchword “DANGER” used in conjunction with the general caution symbol
designates safety and danger notes in this installation manual that, if
neglected, may lead to severe injury or even death of persons.
Safekeeping Please safeguard this installation manual in a safe place, where
it can be immediately accessed. If the equipment changes hands, the
documentation must be passed on to the new operator. If the documentation gets
misplaced, please contact your Condair representative for replacement.
6 Introduction
2582419-F EN 2406
2 For Your Safety
General Every person, who is in charge of the installation work on the Condair
RS must have read and understood this installation manual and the Condair RS
operation manual before carrying out any work. Knowing and understanding the
contents of the installation manual and the operation manual is a basic
requirement for protecting personnel against any kind of danger, to prevent
faulty operation, and to operate the unit safely and correctly. All icons,
signs and markings applied to the Condair RS must be observed and kept in
readable state.
Qualification of personnel All installation work described in this
installation manual may only be carried out by specialists who are well
trained and adequately qualified and are authorized by the customer. For
safety and warranty reasons any action beyond the scope of this manual must be
carried out only by qualified personnel authorized by Condair. It is assumed
that all persons working with the Condair RS are familiar and comply with the
appropriate regulations on work safety and the prevention of accidents.
Intended use The Condair RS steam humidifier is intended exclusively for air
humidification via a steam distributor or pack approved by Condair within
specified operating conditions (see Condair R manual).Any other type of
application, without the written consent of Condair, is conside conforming
with the intended purpose and may lead to hazardous operation of the Condair
RS and w warranty.Operation of the equipment in the intended manner requires
that all the information contained in thi installation manual are observed (in
particular the safety instructions).
Danger that may arise from the Condair RS: DANGER! Danger of electric shock!
The Condair RS is mains powered. Live parts may be exposed when the unit is
open. Touching live parts may cause severe injury or danger to life.
Prevention: The Condair RS must be connected to the mains only after all
mounting and installation work has been completed, all installations have been
checked for correct workmanship and the unit is closed and properly locked.
2582419-F EN 2406
For Your Safety 7
Preventing unsafe operation All persons working with the Condair RS are
obliged to report any alterations to the unit, modifications, or unsafe issues
that may affect safety to the owner without delay and to secure the Condair RS
against accidental power-up.
Prohibited modifications to the unit No modifications must be undertaken on
the Condair RS without the express written consent of Condair.For the
replacement of defective components use exclusively original accessories and
spare parts available from your Condair representative.
8 For Your Safety
2582419-F EN 2406
3 Product Overview
3.1 Models Overview
Condair RS steam humidifiers are available in different housing sizes (S, M and L) with different heating voltages and steam capacities ranging from 10 lbs/hr up to a maximum of 180 lbs/hr (5 … 80 kg/h).
3.1.1
Units Small (“S”) and Medium (“M”)
Housing size
Conda
ir RS 10
208 V/1~ 240 V/1~ 480 V/1~ 600 V/1~ 208 V/3~ 240 V/3~ 480 V/3~ 600 V/3~ lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) 10.9 (4.9) 10.9 (4.9) 9.7 (4.4) 11.4 (5.2) 10.9 (4.9) 10.9 (4.9) 11.3 (5.1) 11.1 (5.0)
S
15
15.9 (7.2) 14.5 (6.6) 14.1 (6.4) 14.7 (6.7) 15.9 (7.2) 14.5 (6.6) 14.6 (6.6) 17.6 (8.0)
20
21.2 (9.6) 21.2 (9.6) 18.8 (8.5) 19.6 (8.9) 21.2 (9.6) 21.2 (9.6) 19.4 (8.8) 22.8 (10.3)
30
31.8 (14.4) 31.8 (14.4) 31.5 (14.3) 31.4 (14.2) 28.8 (13.1) 31.8 (14.4) 31.5 (14.3) 31.4 (14.2)
45
47.7 (21.6) 47.9 (21.7) 45.2 (20.5) 47.1 (21.4)
M
65
71.6 (32.5) 71.9 (32.6) 63.0 (28.6) 70.6 (32.0)
90
94.6 (42.9) 94.3 (42.8)
S
M
Fig. 1: Overview units small (“S”) and medium (“M”)
2582419-F EN 2406
Product Overview 9
3.1.2 Units Large (“L”)
Housing size
Conda
ir RS
…90…
L
…130…
…180…
208 V/1~ 240 V/1~ 480 V/1~ 600 V/1~ 208 V/3~ 240 V/3~ 480 V/3~ 600 V/3~
lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h) lbs/hr (kg/h)
95.4 (43.3) 94.6 (42.9)
143.2 (65.0) 141.8 (64.3) 126.0 (57.2) 141.2 (64.1)
189.2 (85.8) 188.6 (85.5)
L
MoBdule
MoAdule
Fig. 2: Overview units large (“L”)
10 Product Overview
2582419-F EN 2406
3.2 Identification of the Unit
The identification of the unit is found on the specification label.
MODEL: RS 010
VOLTS: 208
AMPS: 17.8
KW:
3.7
MAX:
25
Circuit Protection
SER: XXXXXXX
PHASE: 1
HZ: 60
11/14
Type designation
Serial number Electrical supply requirements Current draw Power consumption
Max. external fuse Month/Year
Fig. 3: Specification label location and details (right side and underside of unit)
2582419-F EN 2406
Product Overview 11
3.3 Product Designation
The product designation and the most important unit data are found on the
specification label fixed on the right side of the Condair RS.
Notes regarding the specification label can be found in the Condair RS
operation manual.
Key model designation
Product designation Steam capacity in lbs/hr:
Heating voltage: 208V/1~/50…60Hz: 208V/1~ 240V/1~/50…60Hz: 240V/1~
480V/1~/50…60Hz: 480V/1~ 600V/1~/50…60Hz: 600V/1~ 208V/3~/50…60Hz: 208V/3~
240V/3~/50…60Hz: 240V/3~ 480V/3~/50…60Hz: 480V/3~ 600V/3~/50…60Hz: 600V/3~
Example: Condair RS 65 480V/3~
12 Product Overview
2582419-F EN 2406
3.4
Options
Precision
Provides capability of humidifier to achieve ± 1% humidity control*. Solid
State Relays allow for rapid response upon call for humidity, adapting rapidly
to humidity demand. This allows for quick response and tight control of
humidity. Also supplied are two fill valves for quicker response (turbo mode).
- Humidity control is dependent on a variety of factors, including design of piping from humidifier to distributor, duct characteristics from distributor to space, control devices and location. In-field results may vary. Relative humidity levels in the supply duct will vary greater than in-space tolerance levels.
Scale tank
Provides a separate reservoir underneath the steam cylinder for scale collection. The addition of this option reduces maintenance time significantly. Minerals removed from the water during steam production will collect in the scale reservoir rather than in the tank. For the double tank humidifiers (RS 135 and 180), order two for each humidifier.
Built-on Blower Pack
For direct dispersion into a conditioned environment.
Remote operating and fault indication
PCB with relay contacts for the connection of remote displays for “Operation”, “Steam”, “Fault” and “Service”.
Accessory Board
PCB with relay contacts for the connection of remote fan enable (cylinder A/B) as well as hygiene flush (cylinder A/B).
BACnet MSTP BTL
PCB to provide BTL certified BACnet MSTP. This option also enables full Master functionality when using BACnet MSTP.
BACnet IP BTL
PCB to provide BTL certified BACnet IP.
LonWorks board
Supplementary board to connect the Condair RS to a building management system via LonWorks.
Mounting bars
Provides two mounting bars which fit into each other for wall mounting. One bar is fastened to the humidifier, the other bar is fastened to the wall. The unit can then be “hung” onto the wall by engaging the two mounting bars.
Note: without this option, the unit may still be wall mounted using the keyhole cutouts on the back of humidifier housing.
Single units “S” 10 15 20
Condair RS Single units “M” 30 45 65 90
1x P
1x SC
1x BOBP 1xRFI 1x ACC
1x BAC-BTL-MSTP 1x BAC-BTL-IP 1x LON
1x MP-S
1x MP-M
Large units “L” 90 130 180
2x SC N/A
1x MP-L
2582419-F EN 2406
Product Overview 13
Pressure compensation kit
Provides extension for the fill cup to overcome back pressure (including duct
static pressure) in excess of 5-1/2″ water column. Longer hoses included. Two
required for double tank humidifiers.
RS-RO
Secondary inlet valve for dedicated drain water cooling using potable water.
This option is used when treated RO/DI water is being supplied to the steam
tank.
Single units “S” 10 15 20
Condair RS Single units “M” 30 45 65 90
1x OPS
1xRS-RO
Large units “L” 90 130 180
2x OPS
3.5
Accessories
Pure water system Condair RO-A Pure water system for operating the Condair RS
with RO water.
Single units “S” 10 15 20
Condair RS Single units “M” 30 45 65 90
Large units “L” 90 130 180
1xRO-A40
1xRO-A100
14 Product Overview
2582419-F EN 2406
4 Receiving and Storage
4.1 Inspection
Upon receiving: Inspect shipping boxes for damage.
Any damages of the shipping boxes must be reported to the shipping company
without delay. Check packing slip to ensure all parts have been delivered.
All material shortages are to be reported to your Condair supplier within 48
hours after receipt of the goods. Condair Ltd. assumes no responsibility for
any material shortages beyond this period. The standard delivery includes the
Condair RS steam humidifier with the options ordered (seeSection 3.4) packed
in cardboard boxes along with the installation manual (this document),
operation manual and spare parts list. Unpack the parts/components and check
for any damage. If parts/components are damaged, notify the shipping company
immediately. Check whether the components are suitable for installation on
your site according to model key shown on the specification label.
4.2 Storage and Transportation
Storing Until installation store the Condair RS in its original packaging in a
protected area meeting the following requirements: Room temperature: 41 …
104 °F (5 … 40 °C) Room humidity: 10 … 75 %rh
Transportation For optimum protection always transport the unit and components
in their original packaging and use appropriate lifting/transporting devices.
WARNING!
It is the customer’s responsibility to ensure that operators are trained in
handling heavy goods and that the operators comply with the appropriate
regulations on work safety and the prevention of accidents.
Packaging Keep the original packaging of the components for later use. In case
you wish to dispose of the packaging, observe the local regulations on waste
disposal. Please recycle packaging where possible.
2582419-F EN 2406
Receiving and Storage 15
5 Mounting and Installation Work
5.1 Safety Notes on Mounting and Installation Work
Qualification of personnel All mounting and installation work must be carried
out only by well qualified personnel authorized by the owner. It is the
owner’s responsibility to verify proper qualification of the personnel.
General notes Strictly observe and comply with all information given in the
present installation manual regarding the mounting of the unit and the
installation of water, steam and electricity. Observe and comply with all
local regulations dealing with water, steam and electrical installations.
Safety Some installation work requires removal of the unit covers. Please note
the following:
DANGER! Danger of electric shock! The Condair RS is mains powered. Live parts
may be exposed when the unit is open. Touching live parts may cause severe
injury or danger to life. Prevention: The Condair RS must be connected to the
mains only after all mounting and installation work has been completed, all
installations have been checked for correct workmanship and the unit is closed
and properly locked. CAUTION!
The electronic components inside the humidifier are very sensitive to
electrostatic discharge. Prevention: To protect these components against
damage caused by electrostatic discharge (ESD protection) appropriate measures
must be taken when the unit is open for installation work. A wrist strap
should be worn to connect the maintenance specialist with a common ground
point. For more information, refer to ANSI/ESD-S20.20.
16 Mounting and Installation Work
2582419-F EN 2406
5.2 Installation Overviews
Typical installation for duct humidification
Return duct Supply duct
Humidity sensor or humidity controller
Coarlcmuilna.te7d.8a7b.s..o9rp.8ti4omnftidn(i.2s9.t4a.8n.4.c.ef3tHhB(m3uuN)mmmtiof
iiBaddnNiitytiyysousbcnseoktnnrnustocrowtoiornllnoerr
High limit humidistat (external safety chain)
Pmax 6.03″ wc (1500 Pa) Pmin -4.02″ wc (-1000 Pa)
Air proving switch (external safety chain)
ømin: 8″ (200 mm)
Condsensate line Min. downslope 1.2°
condensate to drain
No restrictions
Condensate trap ømin 8″ (200 mm)
min. 12″ (300 mm)
(30R0mimn:m)11.9″
min. 12″ (300 mm)
Steam line As short as possible Adequate upslope (min. 10°)/downslope
(2.0°) No restrictions Condensate trap at the lowest point Hose or fixed
pipe
Electrical isolator voltage supply (supplied by others)
Water drain connector ø1.18″ (ø30 mm) Water supply connector 1/2″ NPT
Water supply pipe
Filter valve or Shut-off valve and 125 µm filter (recommended, supplied by
others)
30 … 80 psi (2.0…5.5 bar) 33.8 … 77.0 °F (1…25 °C)
ømin: 1.57″ (40 mm)
Fig. 4: Typical installation for duct humidification
Drain hose (supplied) internal diameter ø1.18″ (ø30 mm) Drain hose must be
led to the left constant downslope (min 1.2°) to funnel if using DI or RO
water, use supplied drain hose or stain-
less steel pipe only able to withstand max. temperature of 140 °F (60 °C)
must not touch funnel, 1″ (2.5 cm) air gap
Open funnel with trap (supplied by others, located with 8″ (20 cm) lateral
off-set to the unit)
Note: For water supply connection of units equipped with RS-RO option, refer to Fig. 6.
2582419-F EN 2406
Mounting and Installation Work 17
Typical installation for room humidification
Condsensate line Min. downslope 1.2° No restrictions Condensate trap
ømin 8″ (200 mm)
ømin: 8″ (200 mm)
condensate to drain
BP BP
Blower Pack (mounted remotely from the steam humidifier)
Steam line As short as possible Adequate upslope (min. 10°)/downslope
(2.0°) No restrictions Condensate trap at the lowest point Hose or fixed
pipe (with same inner diameter as
steam outlet)
High limit humidistat (external safety chain)
Humidity sensor or humidity controller
Electrical isolator voltage supply (supplied by others)
Water drain connector ø1.18″ (ø30 mm) Water supply connector 1/2″ NPT
Water supply pipe)
Filter valve or Shut-off valve and 125 µm filter (recommended, supplied by
others)
30 … 80 psi (2.0…5.5 bar) 33.8 … 77.0 °F (1…25 °C)
ømin: 1.57″ (40 mm)
Fig. 5: Typical installation for room humidification
Drain hose (supplied) internal diameter ø1.18″ (ø30 mm) Drain hose must be
led to the left constant downslope (min 1.2°) to funnel if using DI or RO
water, use supplied drain hose
or stainless steel pipe only able to withstand max. temperature of 140 °F (60
°C) must not touch funnel, 1″ (2.5 cm) air gap
Open funnel with trap (supplied by others, located with 8″ (20 cm) lateral
off-set to the unit)
Note: For water supply connection of units equipped with RS-RO option, refer to Fig. 6.
Water supply connector G 3/4″ (RO water)
Adapter G 3/4″ / 1/2″ NPT (supplied with O-ring or gasket)
Connection fitting 1/2″ NPT / 1/2″ NPT (by others)
Water supply pipe (min. inner diameter 1/2″ (8 mm), supplied by others)
Filter valve or Shut-off valve and 125 µm filter (recommended, supplied by
others)
30 … 80 psi (2.0…5.5 bar) 33.8 … 77.0 °F (1…25 °C)
Shut-off valve
Water supply connector G 3/4″ (RS-RO option) for potable water supply for
drain water cooling Adapter G 3/4″ / 1/2″ NPT (supplied with O-ring or gasket)
Union 1/2″ NPT / 1/2″ NPT (supplied by others)
Condair RO-A pure water system (Accessory)
Fig. 6: Water supply connections for units installed with RS-RO option 18 Mounting and Installation Work
2582419-F EN 2406
min. 15.75″ min. 400 mm
5.3 Mounting the Unit 5.3.1 Notes on Locating the Unit
00m” m 00m” m
Y
min. 9m14inm. 3m6″
X
Z
min. 600 mm
min. 23.62″
Fig. 7: Minimal distances to be observed
Housing
Housing dimensions in inch (mm)
Net weight in lbs (kg) Operating weight in lbs (kg)
Small (“S”) RS 10…20
X 16.5″ (420) Y 14.6″ (370) Z 26.4″ (670)
60 (27.2) 89 (40.2)
Medium (“M”) RS 30…90
20.9″ (530) 16.0″ (406) 30.7″ (780)
89 (40.3) 145 (65.8)
Large (“L”) RS 90…180
29.4″ (1000) 16.0″ (406) 30.7″ (780)
179 (81.0) 291 (132.0)
2582419-F EN 2406
Mounting and Installation Work 19
The installation site of the Condair RS depends largely on the location of the steam distributor/blower
pack (see Section 5.4.3 and Section 5.4.4).
To ensure proper
functioning of
the
stoteoabmtahinumanidiofipetriamnadl efficiency, the following points must be considered and observed when choosing
the location for the steam humidifier:
Install the steam humidifier so that:
the length of the steam line is kept as short as possible,
the minimum bend radius for steam hoses (R= 12″ / 300 mm) and for solid steam pipes (5 x internal diameter)
the minimum upslope 10° and downslope 2° of the steam hose is maintained. For details of mounting the Condair RS, refer toSection 5.3.2 .
CAUTION!
Do not mount the steam humidifier directly to the ventilation duct.
The back panel of the Condair RS retains heat during operation (max. surface
temperature of the metal housing approx. 140 – 158 °F / 60 – 70 °C). Make
sure, therefore, that the construction (wall, pillar, etc.) to which the unit
is to be mounted, does not consist of heat-sensitive material.
Install the Condair RS in such a manner that it is freely accessible with
sufficient space available for maintenance purposes. The minimum distances
shown in the adjacent illustration must be maintained.
As a safeguard, the humidifier should be installed in a drip-proof location.
Admissible ambient conditions must be complied with.
Do not mount the Condair RS to hot or very cold walls or near vibrating
components.
The steam humidifier Condair RS must only be installed in rooms with a floor
drain.
CAUTION!
If for some reason the Condair RS must be installed in a location without
floor drain, it is mandatory to provide a leakage monitoring device to safely
interrupt the water supply in case of Wlehaeknagmeo.unting the Condair RS
use only the mounting materials supplied with the unit. If mount- ing with the
materials supplied is not possible in your particular case, select a method of
mounting that is of similar stability.
The Condair RS is designed for installation and operation within buildings
(admissible temperature range 41… 104 °F / 5…40 °C). For outdoor operation the
Condair RS must be placed in a weather protective housing. If ambient
temperatures near or below the freezing point have to be expected, the
protective housing must be equipped with a thermostat controlled heating of
sufficient capacity. The water supply pipe must be equipped with heat-tracing
and must be insulated up to the protec- tive housing. For outdoor operation,
the Keep Warm function must be enabled. The installation of a normally open
valve inside the building envelope that will drain water in case of power
failure is highly recommended.
20 Mounting and Installation Work
2582419-F EN 2406
5.3.2
Mounting the Humidifier 5.3.2.1 Standard Mounting
Mark the mounting hole locations “A” and “B” on 2×4 wooden studs (or equivalent) in the mounting surface, as shown, and mount the Condair RS unit using 1/4 × 2 inch lag bolts and washers.
Overview standard mounting single units Small and Medium
c d
A A
Dimension
“a” in inch/mm “b” in inch/mm “c” in inch/mm “d” in inch/mm
Housing size
Small
Medium
2.1″ (54.0) 2.1″ (54.0)
17.6″ (446.0) 21.9″ (556.0)
3.2″ (80.2) 3.5″ (88.6)
12.0″ (304.8) 16.0″ (406.4)
Weights
Net weight in lbs/kg Operating weight in lbs/kg
Housing size
Small
Medium
60 / 27.2
89 / 40.3
89 / 40.2
145 / 65.8
a
b
B B
Fig. 8: Overview standard mounting single units Small and Medium
2582419-F EN 2406
Mounting and Installation Work 21
Overview standard mounting single units Large
d A
A
B B
c d
A
B
Dimension
“a” in inch/mm “b” in inch/mm “c” in inch/mm “d” in inch/mm
Weights
Net weight in lbs/kg Operating weight in lbs/kg
Housing size Large
6.5″ (164.0) 16.8″ (426.0) 4.6″ (117.2) 16.0″ (406.4)
Housing size Large
179 (81.0) 291 (132.0)
a
b
Fig. 9: Overview standard mounting single units Large 22 Mounting and Installation Work
2582419-F EN 2406
Mounting procedure standard mounting
1. Mark the attachment points “A” and “B” at the desired position in the
mounting surface with the help of a level.
2. Install 1/4 × 2 in lag bolts and washers at attachment points “A”. Allow
the heads of the bolts to extend 1/4 in (5 mm) from the mounting surface so
that the humidifier can be hung on the bolts.
3. Unlock the screws on the front panels of the unit, and remove the front
panels. 4. Carefully raise the unit and hang it on the installed lag bolts. 5.
Install additional 1/4 × 2 in lag bolts and washers through the rear panel of
the humidifier into the
mounting surface at attachment points “B”. 6. Align the unit with the help of
a level, then tighten the lag bolts. 7. Install the front panels and fasten
them securely.
2582419-F EN 2406
Mounting and Installation Work 23
5.3.2.2 Wall Support Mounting (option)
Mark the mounting hole locations “A” on 2×4 wooden studs (or equivalent) in
the mounting surface, as shown, and mount the wall support for the Condair RS
unit using 1/4 × 2 in lag bolts and washers.
Overview wall support mounting single units Small and Medium
c b
A A
Dimension
“a” in inch/mm “b” in inch/mm “c” in inch/mm
Housing size
Small
Medium
7.6″ (193.5) 7.6″ (193.5)
12.0″ (304.8) 16.0″ (406.4)
2.3″ (57.6) 2.4″ (61.8)
Weights
Net weight in lbs/kg Operating weight in lbs/kg
Housing size
Small
Medium
60 / 27.2
89 / 40.3
89 / 40.2
145 / 65.8
a
B B B
Fig. 10: Overview wall support single units Small and Medium
24 Mounting and Installation Work
2582419-F EN 2406
Overview wall support mounting single units Large
b
A
A
c bA
Dimension
“a” in mm “b” in mm “c” in mm Weights
Net weight in lbs/kg Operating weight in lbs/kg
Housing size Large
10.4″ (263.5) 16.0″ (406.4) 4.6″ (117.2)
Housing size Large
179 (81.0) 291 (132.0)
a
B B B
Fig. 11: Overview wall support mounting single units Large
2582419-F EN 2406
Mounting and Installation Work 25
Procedure 1. Mark the attachment points “A” for the wall support at the
desired position with the help of a level. 2. Attach the wall support to 2×4
wooden studs (or equivalent) in the mounting surface with 1/4 × 2 in
lag bolts and washers. Adjust the wall support horizontally using a level, and
tighten the bolts. 3. Unlock the screws on the front panels of the unit, and
remove the front panels. 4. Carefully raise the unit and hang it on the wall
support. 5. Secure the unit to the wall support with the supplied pop-rivets
at points “B”. 6. Install the front panels and fasten them securely.
5.3.3 Inspecting the Installed Unit
Check the following points: Is the unit installed in the correct place (see
Section 5.3.1)? Is the supporting surface stable enough? Is the unit correctly
aligned, vertically and horizontally? Is the unit properly secured (see
Section 5.3.2)?
26 Mounting and Installation Work
2582419-F EN 2406
5.4 Steam Installation 5.4.1 Overview Steam Installation for Duct Humidification
Supply duct
Pmax 6.03″ wc (1500 Pa) Pmin -4.02″ wc (-1000 Pa)
Coarlmcuinla.te7d.8a7b.s..o9rp.8ti4omnftidn(2i.s.94ta.8.n.4.ce3ftBm(3N)tmiof
)BaNnyisobusntkrnuoctwionn
Steam line As short as possible Adequate upslope (min. 10°)/downslope
(2.0°) No restrictions Condensate trap at the lowest point Hose or fixed
pipe (with same inner diameter as
steam outlet)
min. 12 ” (300 mm)
(30R0mimn:m)12″
min. 12 ” (300 mm)
Condsensate line Min. downslope 1.2° No restrictions Condensate trap ømin 8″ (200 mm)
ømin: 8″ (200 mm) condensate to drain
Fig. 12: Overview steam installation for duct humidification
5.4.2 Installing the Steam Distributors
Detailed information on the installation of steam distribution pipes and SAM-e
steam distribution system can be found in the separate mounting instructions
for these products.
2582419-F EN 2406
Mounting and Installation Work 27
5.4.3 Overview Steam Installation for Room Humidification
BP
Condsensate line Min. downslope 1.2° No restrictions Condensate trap
ømin 8″ (200 mm)
ømin: 8″ (200 mm)
condensate to drain
Blower Pack (mounted separated from the steam humidifier)
Steam line As short as possible Adequate upslope (min. 10°)/downslope
(2.0°) No restrictions Condensate trap at the lowest point Hose or fixed
pipe (with same inner diameter as steam outlet)
BP
Blower Pack (mounted directly on steam humidifier)
Fig. 13: Overview steam installation for room humidification
28 Mounting and Installation Work
2582419-F EN 2406
5.4.4 Positioning and Mounting the Blower Packs
The blower packs can either be mounted directly on the humidifier or
separately above the humidifier to the wall. To allow the steam coming from
the blower pack to spread out evenly, without condensing on obstacles
(ceilings, joists, pillars, etc.), the following minimum dimensions must be
observed when selecting the location for the blower pack. Even small objects
that encroach into the steam distribution area may create condensation and
reduce efficiency.
D
D D
D
B
B
A A
C C
WARNING! Risk of burn injuries!
The blower pack discharges hot steam and presents a burn hazard. Care must be
taken when the humidifier is in operation and when in the vicinity of the
blower pack.
Humidifier Model
RS 010 RS 015 RS 020 RS 030 RS 045
Max. Capacity lb/hr (kg/h)
up to 11.4 (5.2) up to 17.6 (8.0) up to 22.8 (10.3) up to 31.8 (14.4) up to
47.9 (21.7)
Fan Speed
Low High Low High Low High Low High Low High
Min. Clearance Required in inch (cm)
A
B
C
D
18 (46)
12 (31)
96 (244)
12 (31)
6 (16)
12 (31)
96 (244)
12 (31)
75 (191)
12 (31)
96 (244)
12 (31)
60 (153)
12 (31)
96 (244)
12 (31)
75 (191)
12 (31)
96 (244)
12 (31)
60 (153)
12 (31)
96 (244)
12 (31)
86 (219)
12 (31)
96 (244)
12 (31)
71 (181)
12 (31)
96 (244)
12 (31)
174 (442)
12 (31)
96 (244)
12 (31)
132 (336)
12 (31)
96 (244)
12 (31)
2582419-F EN 2406
Mounting and Installation Work 29
Humidifier Model RS 065 RS 090
Max. Capacity lb/hr (kg/h)
up to 71.9 (32.6)
up to 95.4 (43.3)
Fan Speed
Low High Low High
Min. Clearance Required in inch (cm)
A
B
C
D
189 (481)
48 (122)
96 (244)
30 (77)
153 (389)
12 (31)
96 (244)
30 (77)
248 (630)
84 (214)
96 (244)
30 (77)
218 (554)
12 (31)
96 (244)
30 (77)
Note: Sound measurement at low speed: 57.4 dB; high speed: 64.1 dB taken 3 ft
(1 m) from the blower pack.
Note: The minimum spaces in the table apply for a room atmosphere of 72ºF
(21ºC), and max 40% RH. For lower temperatures and/or higher humidity the
clearance values will increase, and should be adjusted accordingly.
Note: In order to achieve a uniform distribution of the humidity within the
room, additional factors such as the room size, the room height, etc., must be
taken into consideration besides observing the minimum distances for the
blower packs. If you have questions concerning the direct room humidification,
please contact your Condair representative.
Further information is provided in the separate installation and operating
instructions for the corresponding blower pack.
5.4.5 Installing the Steam and Condensate lines
Installations notes
Use original steam and condensate hose from your Condair representative or
solid steam pipes from copper (MED-L) or stainless steel (min. AISI 304)
exclusively. Steam and condensate lines of other material may cause undesired
operational malfunctions. For installations with reverse osmosis or de-ionized
water supply, do not use copper steam lines.
Initially, lead the steam line upright upwards min. 12″ (300 mm) above the
humidifier. Then lead the steam line with a minimum upslope of 10° and/or a
minimum downslope of of 2° to the steam distributor.
The condensate hose from the steam distributor is led down to the humidifier
with a minimum downslope of 1.2°, via a condensate trap (min. hose bend
diameter Ø8″ (ø200 mm)) and there it is to be connected to the appropriate
connector on top of the unit. Important! Before putting the unit into
operation, the condensate trap of the condensate hose must be filled with
water.
The steam line should be kept as short as possible, as per Table 1 on page
31. Ensure the the minimum bend radii are observed: 12″ (300 mm) for steam
hoses or 5x internal diameter for solid pipes. Important! Allowance must be
made for a pressure loss from elbows, according to equivalent length tables.
Important! When deciding on the length and layout of steam hoses, it should
be noted that steam hoses may become shorter and/or longer depending on
temperature and age.
The steam hose must be secured to the steam distributor and humidifier steam
outlet by means of hose clamps. Solid steam pipes should be connected to the
steam distributor and steam humidifier with short lengths of steam hose
secured with hose clamps. Caution! Do not overtighten the hose clamp on the
steam connector of the steam humidifier.
Steam lines made of solid pipes (copper or stainless steel) must be
insulated over the entire length to minimize condensate formation. Condensate
created due to thermal loss in steam lines will reduce the operational
efficiency of the humidification system and reduce the moisture supply to the
conditioned environment.
30 Mounting and Installation Work
2582419-F EN 2406
DANGER!
Reducing the cross section or the complete closure of the steam line will
cause an excessive increase in pressure in the steam cylinder when the unit is
operating and could lead to the risk of scalding accidents. All installations
must comply with the following instructions.
When installing, make sure the steam line is open over the entire length and
through the whole cross section. Any sealing plugs, adhesive sealing sheets
etc. must be removed before connecting the steam pipe. Reductions in cross
section by kinking or crushing must be avoided.
Steam hoses must be prevented from sagging (condensate pockets); if
necessary, support steam hose with pipe clamps, trough, or wall brackets, and
install a condensate drain at any low points in the steam line.
It is not permitted to install a stop valve (e.g. a manually controlled
isolation valve, solenoid valve, etc.) in the steam line, due to an
inadmissible increase of pressure in the steam cylinder if the valve is closed
during the operation.
Table 1: Recommended Steam Line Material*, Maximum Length, Losses
Maximum Steam Line
Humidifier Model
Length**
ft
m
MED-L Copper Tube
Stainless Steel Tube
RS 010 RS 015
24
7.3
(1 line) 1.5″ ID MED-L (1 line) 1.75″ OD SS
25
7.6
Tubing (1.625″ OD) Tubing (0.065″ thick)
RS 020
27
8.2
RS 030
30
9.1
RS 045
35
10.7
RS 065
45
13.7
RS 090 (M)
50
15.2
RS 090 (L)***
35
RS 130***
45
10.7 (2 lines) 1.5″ ID MED-L (2 lines) 1.75″ OD SS
13.7
Tubing (1.625″ OD) Tubing (0.065″ thick)
RS 180***
50
15.2
Condair Steam Hose
All Models
10
3
P/N 1328820
Possible Steam Losses
(based on 1″ insulated copper pipe)
lb/hr per ft kg/hr per m
0.11
0.16
0.15
0.22
Notes: The use of steam line other than copper, stainless steel tube, or Condair supplied steam line will void the warranty and may adversely affect the operation of the humidifier. Long steam runs affect accuracy of humidifier and its ability to quickly respond to changes in demand. When tight control is required, ensure steam line run is as short as possible. Steam line per boiling tank. Do not combine steam lines except at distributor using a Condair adapter designed for that purpose and only if humidifiers operate in parallel.
2582419-F EN 2406
Mounting and Installation Work 31
Installation examples
min. 12″ (300 mm) min. 12″ (300 mm)
Ømin. 8″ (Ømin. 200 mm)
Rmin. 12″ (300 mm)
Fig. 14: Steam distributor mounted more than 20″ (500 mm) above the top edge of the humidifier
32 Mounting and Installation Work
2582419-F EN 2406
max. 13 ft (4 m) min. 12″ (300 mm)
min. 12″ (300 mm)
Rmin. 12″ (300 mm)
Ømin. 8″ (Ømin. 200 mm)
Ensure adequate cooling according to local codes
Obstacle
Rmin. 12″ (300 mm)
min. 12″ (300 mm) Rmin. 12″ (300 mm) min. 12″ (300 mm) min. 12″ (300 mm)
Ømin. 8″ (Ømin. 200 mm)
Ømin. 8″ (Ømin. 200 mm)
Install condensate drain (full size T) at the lowest point. Ensure proper
slope is maintained for the steam lines upstream and downstream of the T.
Ensure adequate cooling according to local codes
Fig. 15: Steam distributor mounted less than 20″ (500 mm) above the top edge of the humidifier
2582419-F EN 2406
Mounting and Installation Work 33
min. 12″ (300 mm) min. 12″ (300 mm)
Ømin. 8″ (Ømin. 200 mm)
Rmin. 5 x D
Steam line must be insulated over the entire length!
Fig. 16: Steam line with solid piping and insulation
34 Mounting and Installation Work
2582419-F EN 2406
5.4.6 Common Steam and Condensate Line Errors
2 3
4 5 1
Wrong
Correct
1 Steam line not led at least 12″ (300 mm) perpendicularly Lead steam line at least 12″ (300 mm) perpendicularly up-
upwards before first bend (forming of condensate).
wards before first bend.
2 Minimum bend radius of steam hose/solid steam line not The minimum bend radius of 12″ (300 mm) for steam hoses
maintained (forming of condensate).
or 5 times steam line internal diameter for solid steam lines
must be maintained.
3 Condensate trap not sufficiently high and installed too near The condensate trap must be at least 12″ (300 mm) below
at the steam distributor.
the connector on the steam distributor and it must have a
minimum height of 8″ (200 mm) in form of a hose loop ø8″
(ø200 mm).
4 No condensate trap installed at vertical transition.
Install condensate trap at all low points and before vertical transitions.
5 Steam line and condensate hose not sloped.
Install steam line always with constant upslope of min. 10° or downslope of min. 2.0° and condensate hose with constant downslope of min. 1.2°.
Fig. 1: Common steam and condensate line errors
2582419-F EN 2406
Mounting and Installation Work 35
5.5 Inspecting the Steam Installation
Use the following check list to ensure that the steam installation was
performed correctly: Steam distributor
Steam distributors (steam distribution pipe or SAM-e steam distribution
system) correctly positioned and secured (screws tightened)? Are the outlet
orifices at right angles to the air flow for horizontal installation, or at 45
degree angle for vertical installation? Steam hose Steam hose material:
copper (potable water only), stainless steel or Condair plastic hose? Maximum
length, as per table shown in Section 5.4.5? Minimum bend radius of 12″ (300
mm) (5 x internal diameter with fixed piping)? Have the instructions for hose
layout been followed? Steam hose: no sagging (condensate pocket) or condensate
drain with trap (hose bend with a minimum diameter of 8″ (200 mm)) installed
at the lowest point and filled with water? Fixed steam lines: properly
insulated? Correct installation material used? Minimum internal diameter
maintained? Steam hose or steam hose pieces securely attached with clamps?
Heat expansion during operation and shortening of the hose with ageing taken
into consideration? Condensate hose Downslope of at least 1.2°? Trap min.
ø8″ (ø200 mm) in place and filled with water? Condensate hose correctly
connected and supported and not kinked?
36 Mounting and Installation Work
2582419-F EN 2406
5.6 Water Installation 5.6.1 Overviews Water Installation
Note: with RS-RO Option installed see Section 5.6.2.
Water drain connector ø1.18″ (ø30 mm) Water supply connector G 3/4″
Water supply pipes (min. inner diameter 1/2″ (12 mm), supplied by others)
Filter valve or
Shut-off valve and 5 micron filter (recommended, supplied by others)
30 … 80 psi (2.0…5.5 bar) 33.8 … 77.0 °F (1…25 °C)
B A
A
G 3/4″ 1/2″ NPT
B
Adapter G 3/4″ / 1/2″ NPT (supplied with O-ring or gasket) 1/2″ pipe with 1/2″
NPT female connection Union 1/2″ NPT / 1/2″ NPT
Hose clamp Drain hose (supplied)
ømin: 1.57″ (40 mm)
Drain hose (supplied): internal diameter ø1.18″ (ø30 mm) Drain hose must
be led to the left constant downslope (min 1.2°) to funnel use supplied
drain hoses or steel pipes only, able to withstand
max. temperature of 140 °F (60 °C) must not touch funnel
Open funnel with trap (supplied by others)
Fig. 17: Overview water installation for single units Small and Medium
Water drain connector ø1.18″ (ø30 mm) Water supply connector G 3/4″
Water supply pipes (min. inner diameter 1/2″ (12 mm), supplied by others)
Filter valves or
Shut-off valves and 5 micron filters (recommended, supplied by others)
30 … 80 psi (2.0…5.5 bar) 33.8 … 77.0 °F (1…25 °C)
A
G 3/4″ 1/2″ NPT
Adapter G 3/4″ / 1/2″ NPT (supplied with O-ring or gasket)
1/2″ pipe with 1/2″ NPT female connection
Union 1/2″ NPT / 1/2″ NPT
B
A B
B
Hose clamp
Drain hose (supplied)
A
ømin: 1.57″ (40 mm)
Drain hoses (supplied): internal diameter ø1.18″ (ø30 mm) Drain hoses must
be led to the left constant downslope (min 1.2°) to funnel use supplied
drain hoses or steel pipes only, able to
withstand max. temperature of 140 °F (60 °C) lead each drain line in a
separate funnel must not touch funnel
Open funnel with trap (supplied by others)
Fig. 18: Overview water installation for single units Large
2582419-F EN 2406
Mounting and Installation Work 37
5.6.2 Overviews Water Installation (with RS-RO option installed)
A
G 3/4″ 1/2″ NPT
B
Adapter G 3/4″ / 1/2″ NPT (supplied with O-ring or gasket)
1/2″ pipe with 1/2″ NPT female connection
Union 1/2″ NPT / 1/2″ NPT
Water drain connector ø1.18″ (ø30 mm)
RO/DI water supply connector G 3/4″
Hose clamp
RO/DI water supply pipe
Drain hose (supplied) (min. inner diameter 1/2″ (12 mm), supplied by others)
Potable water supply pipe for drain water cooling
(min. inner diameter 1/2″ (12 mm), supplied by others)
Filter valve or Shut-off valve and 5 micron filter (recommended, supplied by
others)
30 … 80 psi (2.0…5.5 bar) 33.8 … 77.0 °F (1…25 °C)
Shut-off valve
B
A
A
Drain cooling water supply connector G 3/4″
ømin: 1.57″ (40 mm)
Drain hose (supplied) internal diameter ø1.18″ (ø30 mm) drain hose must be
led to the left constant downslope (min 1.2°) to
funnel use supplied drain hose or stainless
steel pipe only, able to withstand max. temperature of 140 °F (60 °C) must
not touch funnel
Open funnel with trap (supplied by others)
Condair RO-A pure water system (Accessory)
Fig. 19: Overview water installation for single units Small and Medium (with RS-RO option installed)
38 Mounting and Installation Work
2582419-F EN 2406
A
G 3/4″ 1/2″ NPT
B
Adapter G 3/4″ / 1/2″ NPT (supplied with O-ring or gasket)
1/2″ pipe with 1/2″ NPT female connection
Union 1/2″ NPT / 1/2″ NPT
Water drain connectors ø1.18″ (ø30 mm)
Hose clamp
RO water supply connectors G 3/4″
Drain hose (supplied)
RO water supply pipe (min. inner diameter 1/2″ (12 mm), supplied by others)
Potable water supply pipes for drain water cooling (min. inner diameter 1/2″
(12 mm), supplied by others)
Filter valves or Shut-off valves and 5 micron filters (recommended, supplied by others)
Shut-off valve
30 … 80 psi (2.0…5.5 bar) 33.8 … 77.0 °F (1…25 °C)
B A
B
A
A
A
Drain cooling water supply connector G 3/4″
ømin: 1.57″ (40 mm)
Drain hoses (supplied) internal diameter ø1.18″ (ø30 mm) Drain hoses must
be led to the left constant downslope (min 1.2°) to funnel use supplied
drain hoses or stainless
steel pipes only, able to withstand max. temperature of 140 °F (60 °C) lead
each drain line in a separate funnel must not touch funnel
Open funnel with trap (supplied by others)
Condair RO-A pure water system (Accessory)
Fig. 20: Overview water installation for single units Large (with RS-RO option installed)
2582419-F EN 2406
Mounting and Installation Work 39
5.6.3 Notes on Water Installation
5.6.3.1 Water Supply (Potable, RO or DI water)
The water supply is to be carried out according to Fig. 17 and Fig. 18 or Fig.
19 and Fig. 20 and the applicable local regulations for water installations.
The indicated connection specifications must be observed.
The installation of a filter valve (alternatively a shut-off valve and a 5
micron water filter can be used) should be made as close as possible to the
steam humidifier.
Admissible mains pressure 30 … 80 psi (2.1…5.5 bar) For mains pressures >
145.0 psi (>10 bar), the connection must be made via a pressure reducing valve
(adjusted to 30.0 psi (2.1 bar)). For mains pressures <30.0 psi (2.1 bar)
please contact your Condair supplier.
Note: The water supply system must be free of pressure bumps (hammer-free).
The installation of a check valve in the water supply line is therefore not
permitted, as this can lead to pressure bumps in the water system and damage
the inlet valve. If a pipe disconnector is to be installed in the inlet water
system, a model with overpressure protection must be installed. If water
hammers cannot be avoided in the supply line, a pressure shock absorber must
be installed.
Supply rates:
RS Small Medium Large
Max. fill rates 3.70 gal/min (14 l/min) 3.70 gal/min (14 l/min) 2 x 3.70 gal/min (2 x 14 l/min)
Notes on water quality:
For the water supply of the Condair RS, use exclusively potable drinking
water in accordance with the applicable local regulations or water from a RO
system or de-ionized water system.
The use of additives such as corrosion inhibitors, disinfectants, etc. is
not allowed, since these additives may endanger health and affect proper
operation.
Conductivity should be between 1 and 1500 S/cm. Note that conductivity less
than 1 S/cm is very aggressive water (this is equivalent to a resistivity of 1
M or greater). It is recommended to blend such water with other less-treated
water to ensure the supply is not overly aggressive.
Hardness should be between 0 and 12 grains/gallon.
Silica content should be between 0 and 12 ppm.
pH should be between 6.5 and 7.5.
Chloride content should be between 0 and 50 ppm.
The connection material must be pressure-proof and certified for use in
drinking water systems. When connected to a RO or DI water source, use only
installation materials that are acceptable for the treated water.
Important! Before connecting the water line(s), the line(s) must be well
flushed out.
CAUTION!
The thread at the humidifier connection is made of plastic. To avoid
overtightening, the adapter and the union nut of the water pipe must be
tightened by hand only.
40 Mounting and Installation Work
2582419-F EN 2406
5.6.3.2 Additional Requirements for RS-RO Option Water Supply
With the RS-RO option installed the water supply and the drain cooling water
supply are to be carried out according to Fig. 19 and Fig. 20 and the
applicable local regulations for water installations. The indicated connection
specifications must be observed.
RO water supply:
The RO water supply must be connected to the inlet connector(s) according to
Fig. 19 and Fig. 20. Use only installation material that is approved for RO or
DI water to connect the RO-A pure water system to the Condair RS. All water
supply requirements outlined in Section 5.6.3m.1ust also be adhered to with
the RO or DI water supply.
Note: Detailed information regarding the installation of the RO-A pure water
system can be found in the separate installation and operation manual of the
Condair RO-A.
Drain cooling water supply:
The seperate drain cooling water supply must be connected to the optional
drain water cooling inlet valve(s) provided with the RS-RO option according to
Fig. 19 and Fig. 20. Please observe the following notes regarding the drain
cooling water supply installation.
Admissible mains pressure 30 … 80 psi (2.1…5.5 bar) For mains pressures >
145.0 psi (>10 bar), the connection must be made via a pressure reducing valve
(adjusted to 30.0 psi (2.1 bar)). For mains pressures <30.0 psi (2.1 bar)
please contact your Condair supplier.
Note: The water supply system must be free of pressure bumps (hammer-free).
The installation of a check valve in the water supply line is therefore not
permitted, as this can lead to pressure bumps in the water system and damage
the inlet valve. If a pipe disconnector is to be installed in the inlet water
system, a model with overpressure protection must be installed. If water
hammers cannot be avoided in the supply line, a pressure shock absorber must
be installed.
Supply rates:
RS with RS-RO option
Small Medium Large
Max. fill rates
Inlet RO
Drain water cooling (potable)
0.32 gal/min (1.2 l/min)
3.70 gal/min (14 l/min)
0.53 gal/min (2 l/min)
3.70 gal/min (14 l/min)
2 x 0.53 gal/min (2 x 2 l/min)
2 x 3.70 gal/min (2 x 14 l/min)
Notes on water quality: For the drain cooling water supply, use
exclusively potable drinking water in accordance with the applicable local
regulations.
The use of additives such as corrosion inhibitors, disinfectants, etc. is
not allowed.
The connection material must be pressure-proof and certified for use in
drinking water systems.
Important! Before connecting the water line, the line must be well flushed
out.
CAUTION!
The thread at the humidifier connection(s) is/are made of plastic. To avoid
overtightening, the adapter(s) and the union nut(s) of the water pipe must be
tightened by hand only.
2582419-F EN 2406
Mounting and Installation Work 41
5.6.3.3 Water Drain The water drain is to be carried out according to the
figures found in Section 5.6.1 and the applicable local regulations for water
installations. The indicated connection specifications must be observed.
Draining rate: approx. 6.7 gal/min (25.4 l/min) per 33.07 lbs/hr (15 kg/h)
steam capacity The draining temperature is 140 °F (60°C) or less. Use
temperature-resistant installation materials only! When operating the
Condair RS with RO water use only installation material that is approved for
RO water. Make sure that the drain pipes, the funnel(s) and the siphon(s)
are correctly fixed and easily acces-
sible for inspections and cleaning purposes. Always lead the supplied drain
hose from the connector to the left down to the funnel (see Fig.
17). On large units with two steam cylinders each drain line must be led into
a separate funnel with trap (see Fig. 18). Attach drain line(s) in such a
way, that it/they cannot slip out of the funnel(s) and that it/they cannot
bottom out in the funnel(s). The open end of the drain line(s) must not
touch the funnel(s) (min. air gap 1″ (2.5 cm)).
5.6.4 Inspecting the Water Installation
Check the following topics: Water supply
Has filter valve or shut-off valve and 5 µm water filter respectively been
installed in supply line to each unit module? Has acceptable water pressure
(30 … 80 psi (2.1…5.5 bar)) and acceptable water temperature 33.8 … 77.0 °F
(1…25 °C)) been connected? Does the water supply capacity match the humidifier
and is the minimum inside diameter of the supply pipe maintained throughout
the entire length (min. internal diameter of 1/2″ (12 mm) for systems with
optional drain water cooling recommended)? Are all components and pipes
properly secured and are all threaded connections securely tightened? Is the
water system properly sealed? Does the water supply installation meet the
requirements of the local regulations for water installations? For RO or DI
water supply: Has installation material been approved for use with treated
water? Water Supply (with RS-RO option installed) RO water supply:
Has RO-A pure water system been installed according to the notes in the
separate Condair RO-A installation and operation manual. Has RO water supply
been connected to the water inlet connector according to Fig. 19 and Fig. 20
and has installation material been used approved for use with RO water?
42 Mounting and Installation Work
2582419-F EN 2406
Drain cooling water supply (potable drinking water):
Has filter valve or shut-off valve and 5 µm water filter respectively been
installed in supply line to each unit module?
Has acceptable water pressure (30 … 80 psi (2.1…5.5 bar)) and acceptable water
temperature 33.8 … 77.0 °F (1…25 °C)) been connected?
Does the drain cooling water supply capacity match the humidifier and is the
minimum inside diameter of the supply pipe maintained throughout the entire
length (min. internal diameter of 12 mm for systems with optional drain water
cooling recommended)?
Are all components and pipes properly secured and are all threaded connections
securely tightened?
Is the drain cooling water system properly sealed?
Does the drain cooling water supply installation meet the requirements of the
local regulations for water installations?
Water Drain
Is the minimum inside diameter of the drain pipe(s) of ø1.18″ (30 mm)
maintained throughout the entire length?
Has/have drain pipe(s) been installed with a downslope of at least 1.2°?
Has the heat resistance of the material used been verified to be at least 212
°F/100 °C (140 °F/60 °C for systems with optional drain water cooling)?
If Condair RS is operated with RO or DI water: Has installation material been
used approved for the treated water?
Is/are the drain hose(s) properly secured (hose clamps at unit connection
tightened)?
Is there an air gap (min. 1″ (2.5 cm)) between the open end of the drain line
and the funnel?
Does the water drain installation meet the requirements of the local
regulations for water installations?
2582419-F EN 2406
Mounting and Installation Work 43
5.7 Notes on Humidity Control Systems/Humidity Control 5.7.1 Control Device
Locations
The following schematic describes a potential system setup with respect to
control devices.
4
3
1
21
Fig. 21: System Setup Schematic 1 Humidistat 2 Humidity sensor 3 High limit
humidistat 4 Air proving switch
Notes: · Locate the air proving switch in the same duct as the humidifier’s
distributor so that it can sense air
flow (or lack thereof). · Locate the high limit humidistat downstream of the
humidifier’s distributor so that it can sense a duct
that is over-humidified. Recommended setting is 85% RH. Locate it downstream
of the distributor at least 5x the absorption distance. If the absorption
distance is not known, locate at least 10 feet (3m) downstream of the
distributor. Can be a humidistat (modulating or On/Off), or a humidity sensor.
· Humidity sensors and humidistats can be modulating or On/Off. Preferred
location is in the return duct, as the supply air is well mixed with the room
air at this location. Avoid placing near discharge diffuser, near doorways, in
sunlight, or in airflow “dead-zones”.
5.7.2 Admissible Control Signals
Control with external controller Control signals 0…5 VDC 1…5 VDC
0…10 VDC (Potentiometer 140 … 10 k) 2…10 VDC 0…20 VDC 0…16 VDC 3.2…16 VDC 0 …
20 mA 4 … 20 mA
Digital signals (building automation) Humidistat (24 V On/Off)
Control with internal PI controller Humidity sensor signals 0…5 VDC 1…5 VDC
0…10 VDC (Potentiometer 140 … 10 k) 2…10 VDC 0…20 VDC 0…16 VDC 3.2…16 VDC 0 …
20 mA 4 … 20 mA
Digital signals (building automation)
44 Mounting and Installation Work
2582419-F EN 2406
5.8 Electrical Installation
5.8.1 Notes on Electrical Installation
DANGER! Danger of electric shock
The Condair RS is mains powered. Live parts may be exposed when the unit is
open. Touching live parts may cause severe injury or danger to life.
Prevention: The Condair RS unit must be connected to the mains only after all
mounting and installa-tion work has been completed, all installations have
been checked for correct workmanship and the unit is closed and properly
locked.
CAUTION!
The electronic components inside the unit are very sensitive to electrostatic
discharge. Before carrying out installations work inside the unit, appropriate
measures must be taken to protect the electronic components against damage
caused by electrostatic discharge (ESD protection).
All work concerning the electrical installation must be performed only by
skilled and qualified technical personnel (e.g. electrician with appropriate
training) authorized by the owner. It is the owner’s responsibility to verify
proper qualification of the personnel.
The electrical installation must be carried out according to the
corresponding wiring diagram (see Sections 5.8.2 and 5.8.3), the notes on
electrical installation as well as the applicable local regulations. All
information given in the wiring diagrams and notes must be followed and
observed.
All cables must be lead into the unit, via appropriate cable strain relief
or grommets. The cable for the heating voltage supply must be lead into the
unit from the bottom via the cable opening equipped with the clamp. Fix the
cable with the clamp strap.
Make sure the cables are adequately clamped, do not rub on any components or
become a tripping hazard.
Observe and maintain maximum cable length and required cross section per
wire according to local regulations.
The mains supply voltages (heating and control voltage supply) must match
the respective voltage stated on the specification label.
2582419-F EN 2406
Mounting and Installation Work 45
5.8.2 Wiring Diagram Condair RS – Small and Medium Units
ACCESSORY BOARD
Control compartment SD
JP4 JP7
JP8
3V
BAT CR2032 JP11
Control board
(USB)
(RJ45)
Options
H1
Error Service Steam Unit On 1 2 3 4 5 6 7 8 9 10
H2
Hyg. Valve A
FAN B
Hyg. Valve B FAN A
1 2 3 4 5 6 7 8 9 10
SAB
LinkUp
BMS
24VGND GND + GND + GND + REMOTE BOARD
Ethernet (RJ45) IP-Netzwerk / BMS BACnet IP RS 485 BACnet MSTP
JP2 JP1
PWRIC RS485-1 RS485-2 24V GND GND D+ D GND D+ D
LEVEL UNIT
POWER BOARD
SW1
DRAIN DRAIN INLET VALVE 2VALVE 1 VALVE
Driver board
F1
PWR SUPPLY
F2
CONTROL LIMIT BLOWER ENABLE 24VDC V+ INGND IN GND 24V IN 24V IN 24V GND
MODULE B
MAINS SUPPLY L N SC1SC2PEPE
HEAT GR. CONT- PUMP 2+3 ACTOR AC
SWITCH
K1 L1 L2 L3
X1
X7
X10
X11
X12
X9
X8
Safety circuit BP
Safety circuit BP
Limit signal (GND)
Control signal (V+)
Limit signal (IN)
Control signal (IN)
Control signal (GND)
External Safety Loop
T1
24VAC
123456789
XE2
J3
J1 T2
K2
IN (4) GND (3)
+ Y
A1
+ Z
A4
L1 N PE
B3
M
V+ (6) IN (4) GND (3)
JP2
JP1
B2
A2
140…10k
V+ (6) IN (4)
B1 A3
On/Off
JP2
JP1
XE1 L1 L2 L3
Q3
F3
L1 L2 L3 GND 208 – 600 V/3~/50..60 Hz Q3
F3
L1 N
GND
208 – 600 V/1~/50..60 Hz
A1 Continuous humidity controller (active) or humidity sensor A2 Ohmic humidity controller (passive), set jumper JP1 and remove jumper JP2 A3 Dry Contact On/Off Humidity Controller, set jumper JP1 A4 Limiter signal B1 Ventilation interlock B2 Airflow monitor B3 Safety humidistat F1 Internal fuse 24V supply (1 A, slow acting) F2 Internal fuse 24V supply (4 A, slow acting) F3 External fuse heating voltage supply (see table in Section 5.8.6) F5 Internal fuse control module (200 mA, quick acting)H1 Remote operating and fault indication (option)H2 Accessory board (option) for the control of an external fan of the AHU as well as the optional external valve for the water supply line flushingJ1 Jumper wire, if no blower pack is connectedJ3 Jumper wire, if no monitoring devices are connected to SC1 and SC2JP4 Jumper for activating the terminating resistor for Modbus network (Jumper must be connected, if Condair RS is the last unit in the Modbus network)JP7 Jumper for activating Modbus or BACnet MSTP communication via RS485 interface (J6). If jumper is not in place no communication will take place through the RS485 interfaceJP8 Jumper for activating the terminating resistor for LinkUp system (Jumper must be connected, if Condair RS is the last unit in the LinkUp system)K1 Mains contactor (heating voltage)K2 External safety circuit (safety humidistat, airflow monitor, etc.) M Motor Blowepack Q3 External main switch heating voltage supply SW1 Rotary switch module identification (must be left on position “0”) T1 Transformer control voltage supply Module A T2 Transformer blower pack supply XE1 Supply voltage terminal block XE2 Control terminal block
Fig. 22: Wiring diagram Condair RS – Single units Small and Medium
46 Mounting and Installation Work
2582419-F EN 2406
5.8.3 Wiring Diagram Condair RS – Large Units
ACCESSORY BOARD
Control compartment Module A SD
JP4 JP7
JP8
3V
BAT CR2032 JP11
Control board
(USB)
(RJ45)
Options
H1
Error Service Steam Unit On 1 2 3 4 5 6 7 8 9 10
SAB
LinkUp
BMS
24VGND GND + GND + GND + REMOTE BOARD
X8
X8 X9 X12 X11 X10 X7 X1
JP2 JP1
PWRIC RS485-1 RS485-2 24V GND GND D+ D GND D+ D
JP2 JP1
PWRIC RS485-1 RS485-2 24V GND GND D+ D GND D+ D
Module B
LEVEL UNIT
POWER BOARD
SW1
DRAIN DRAIN INLET VALVE 2VALVE 1 VALVE
Driver board module B
F1
PWR SUPPLY
F2
CONTROL LIMIT BLOWER ENABLE 24VDC V+ INGND IN GND 24V IN 24V IN 24V GND
MODULE B
MAINS SUPPLY L N SC1SC2PEPE
LEVEL UNIT
POWER BOARD
SW1
DRAIN DRAIN INLET VALVE 2VALVE 1 VALVE
Driver board module A
F1
PWR SUPPLY
F2
CONTROL LIMIT BLOWER ENABLE 24VDC V+ INGND IN GND 24V IN 24V IN 24V GND
MODULE B
MAINS SUPPLY L N SC1SC2PEPE
X1
X7
X10
X11
X12
X9
Safety circuit BP
Safety circuit BP
Limit signal (GND)
Control signal (V+)
Limit signal (IN)
Control signal (IN)
Control signal (GND)
External Safety Loop
T1
24VAC
123456789
XE2
J3
J1
H2
Hyg. Valve A
FAN B
Hyg. Valve B FAN A
1 2 3 4 5 6 7 8 9 10
Ethernet (RJ45) IP-Netzwerk / BMS BACnet IP RS 485 BACnet MSTP
K2
IN (4) GND (3)
+ Y
A1
+ Z
A4
B3
V+ (6) IN (4) GND (3)
JP2
JP1
B2
A2
140…10k
V+ (6) IN (4)
B1 A3
On/Off
JP2
JP1
HEAT GR. CONT- PUMP 2+3 ACTOR AC
HEAT GR. CONT- PUMP 2+3 ACTOR AC
SWITCH
SWITCH
K1 L1 L2 L3 T2
K1 L1 L2 L3
XE1 L1 L2 L3
Q3
F3
L1 L2 L3 GND 208 – 600 V/3~/50..60 Hz Q3
F3
L1 N
GND
208 – 600 V/1~/50..60 Hz
A1 Continuous humidity controller (active) or humidity sensor A2 Ohmic
humidity controller (passive), set jumper JP1 and remove jumper JP2 A3 Dry
Contact On/Off Humidity Controller, set jumper JP1 A4 Limiter signal B1
Ventilation interlock B2 Airflow monitor B3 Safety humidistat F1 Internal fuse
24V supply (1 A, slow acting) F2 Internal fuse 24V supply (4 A, slow acting)
F3 External fuse heating voltage supply (see table in Section 5.8.6) F5
Internal fuse control module (200 mA, quick acting) H1 Remote operating and
fault indication (option) H2 Accessory board (option) for the control of an
external fan of the AHU as well
as the optional external valve for the water supply line flushing J1 Jumper
wire, do not remove J3 Jumper wire, if no monitoring devices are connected to
SC1 and SC2
Fig. 23: Wiring diagram Condair RS – Large units
JP4 Jumper for activating the terminating resistor for Modbus network (Jumper must be connected, if Condair RS is the last unit in theModbus network)JP7 Jumper for activating Modbus or BACnet MSTP communication via RS485 interface (J6). If jumper is not in place no communication will take place through the RS485 interfaceJP8Jumper for activating the terminating resistor for LinkUp system(Jumper must be connected, if Condair RS is the last unit in the LinkUp system)K1 Mains contactor (heating voltage) unit A/unit BK2 External safety circuit (safety humidistat, airflow monitor, etc.)Q3 External main switch heating voltage supplySW1 Rotary switch module identification (Master Module A: 0, Module B: 1)T1 Transformer control voltage supply Module AT2 Transformer control voltage supply Module BXE1 Supply voltage terminal blockXE2 Control terminal block
2582419-F EN 2406
Mounting and Installation Work 47
5.8.4 Installation Work External Connections
Connecting the external safety chain
24VAC External Safety Loop Control signal (GND) Control signal (IN) Limit signal (IN) Control signal (V+) Limit signal (GND) Safety circuit BP Safety circuit BP
J3
Control compartment
123456789
XE2
K2 B3
B2
Do not apply extraneous voltage via K1!
The potential-free contacts of external monitoring devices (e.g. ventilation
interlock, safety high limit humidistat, airflow monitor, etc.) are connected
in series (safety chain “K2”) to the terminals “1” and “2” of the control
terminal block “XE2” inside the control compartment in accordance with the
wiring diagram. The connecting cable must be led through a cable gland into
the control compartment.
Caution! A high limit humidistat is highly recomended to prevent risk of over-
humidification and potential damage to property.
Note: If, for whatever reason, no external monitoring devices are connected, a
jumper wire “J3” must be installed on the contacts “1” and “2” of the control
terminal block.
CAUTION! Do not apply any extraneous voltage to
B1
contacts “1” and “2” via the contacts of the external
monitoring devices.
Connecting the demand or humidity signal
24VAC External Safety Loop Control signal (GND) Control signal (IN) Limit signal (IN) Control signal (V+) Limit signal (GND) Safety circuit BP Safety circuit BP
JP2 JP1
123456789
XE2
The signal cable of an external controller or of a humidity sensor (if the internal P/PI controller is used) are to be connected according to the wiring diagram to the terminals “3” (GND) and “4” (IN) of the control terminal block “XE2” inside the control compartment. The admissible signal values can be found in the technical data table in the operation manual. The connecting cable must be led through a cable gland into the control compartment.
Control compartment
Note: The admissible humidity control signal values can be found in the technical data table in the operation manual.
IN (4) GND (3)
+ A1
Y
If a shielded signal cable is used, connect the shielding to terminal “3”
(GND). Caution! If the shielding of the control signal is already connected to
a potential or a grounded conductor, do not connect it to terminal “3” (GND).
Ensure that JP1 is connected.
48 Mounting and Installation Work
2582419-F EN 2406
JP1
JP2
24VAC External Safety Loop Control signal (GND) Control signal (IN) Limit signal (IN) Control signal (V+) Limit signal (GND) Safety circuit BP Safety circuit BP
Ohmic humidity controller (passive)
Driver board
123456789
XE2
Control compartment
The signal cable of an ohmic humidity controller (140…10k) is to be connected
according to the wiring diagram to the terminals “3” (GND), “4” (IN) and “6”
(V+) of the control terminal block “XE2” inside the control compartment. The
connecting cable must be led through a cable gland into the control
compartment.
Note: When connecting an ohmic humidity controller Jumper “JP2” must be
removed and Jumper “JP1” must be connected on the driver board and the control
signal type must be set to 0-10V in the control settings of the control
software.
V+ (6) IN (4) GND (3)
JP2
JP1
A2
140…10k
JP1
JP2
24VAC External Safety Loop Control signal (GND) Control signal (IN) Limit signal (IN) Control signal (V+) Limit signal (GND) Safety circuit BP Safety circuit BP
Dry Contact On/Off Humidity Controller
Driver board
123456789
XE2
Control compartment
The signal cable of Dry Contact On/Off Humidity Controller is to be connected
according to the wiring diagram to the terminals “4” (IN) and “6” (V+) of the
control terminal block “XE2” inside the control compartment. The connecting
cable must be led through a cable gland into the control compartment.
Note: When connecting a Dry Contact On/Off Humidity Controller Jumper, “JP1”
must be connected on the driver board and the control signal type must be set
to 0-10V in the control setting of software.
V+ (6) IN (4)
JP2
JP1
A3
On/Off
2582419-F EN 2406
Mounting and Installation Work 49
24VAC External Safety Loop Control signal (GND) Control signal (IN) Limit signal (IN) Control signal (V+) Limit signal (GND) Safety circuit BP Safety circuit BP
Limiter signal
123456789
XE2
Control compartment
The signal cable of an external limiter (P/PI continuous controller) is to be
connected according to the wiring diagram to the terminals “5” (Limit signal
IN) and “7” (Limit signal GND) of the control terminal block “XE2” inside the
control compartment . The connecting cable must be led through a cable gland
into the control compartment.
Note: The limiter must be activated and configured via the control software.
The admissible limiter signal values can be found in the technical data table
in the operation manual.
IN (5) GND (7)
+ A4
Y
Connecting the remote operating and fault indication (Option)
H1
F1 (100 mA)
Error Service Steam Unit On 1 2 3 4 5 6 7 8 9 10
Control compartment
The remote operating and fault indication board contains four potential-free
relay contacts for the connection of the following operating and fault
indications: “Error” (Terminal 1 and 2/3):
This relay is activated if an error is present. “Service” (Terminal 4 and
5/6):
This relay is activated when the set maintenance interval has elapsed. Note:
this relay can be configured in the control software to close either when
maintenance is required or when maintenance is required and when a warning is
indicated. “Steam” (Terminal 7 and 8): This relay closes as soon as the
Condair RS humidi-fies. “Unit on” (Terminal 9 and 10): This relay closes as
soon as the voltage supply to the control compartment of the Condair RS is
switched on.
The connecting cable must be led through a cable gland or grommet into the control compartment.
The maximum contact loading is 24V/8A. Appropriate suppressor modules are to be used for the switching of relays and miniature contactors.
50 Mounting and Installation Work
2582419-F EN 2406
Connecting the optional accessory board
H2
F1 (100 mA)
Hyg. Valve A
FAN B
Hyg. Valve B FAN A
1 2 3 4 5 6 7 8 9 10
Control compartment
The optional accessory board contains four potential-free relay contacts to
activate external fans of the AHU and the optional valves for flushing the
water supply lines: “Hyg. Valve A” (Terminal 1 and 2):
This relay activates the optional valve for flushing the water supply line
connected to module A. “Hyg. Valve B” (Terminal 4 and 5): This relay
activates the optional valve for flushing the water supply line connected to
module B. “FAN B” (Terminal 7 and 8): This relay activates an external fan
of the AHU if module B is producing steam. “FAN A” (Terminal 9 and 10): This
relay activates an external fan of the AHU if module A is producing steam.
The connecting cable must be led through a cable gland or grommet into the control compartment.
The maximum contact loading is 24V/8A.
2582419-F EN 2406
Mounting and Installation Work 51
Connecting the voltage supply
K1 L1 L2 L3
XE1 L1 L2 L3
Control compartment
Q3
F3
L1 L2 L3 GND
208 – 600 V/3~/50..60 Hz Q3
F3
L1 N
GND
208 – 600 V/1~/50..60 Hz
The voltage supply (L1, L2, L3 and GND or L1 and) is to be connected in
accordance with the wiring diagram to the corresponding terminals of the main
contactor in the control compartment. The earth conductor is to be connected
to the earth terminal right beside the phase terminals. The supply wiring is
to be fed into the unit via the clamp strap on the bottom of the unit.
The installation of the fuses F3 and the electrical isolator “Q3” (all pole
disconnecting device with a minimum contact clearance of 3 mm) in the mains
supply line are mandatory. Note: a table with the values for the fuses “F3″ is
to be found in Section 5.8.6.
For safety reasons the additional installation of a residual current circuit
breaker in the mains supply line (supplied by others) is recommended. However,
the local electrical installation regulations must be observed and adhered to.
The electrical isolator must be mounted in direct proximity of the control
compartment (max. distance 40″ (1 m)) and must be easily accessible in a
height between 24″ (0.6 m) and 75″ (1.9 m) (recommended: 67” (1.7 m)).
CAUTION! Make sure the voltage indicated on the specification label meets the
local mains voltage. Otherwise, do not connect the unit.
The cross-section of the mains cable must comply with the applicable local
regulations.
Connecting the Blower Pack BP See separate documentation for blower pack BP.
52 Mounting and Installation Work
2582419-F EN 2406
5.8.5 Connecting Multiple Units Using Linkup
The integrated controller in the Condair RS steam humidifier allows up to six
integrated controllers (for a maximum of 12 steam cylinders) to be connected
in a “main-extension” configuration using Condair’s Linkup system. All the
humidifiers within this setup must share the same location, and all linked
units will be controlled by one set of control signals connected to the main
unit. Refer to Fig. 24 and connect multiple unit using Linkup as follows:
1. Connect all control signals for the entire Linkup configuration to the low
voltage terminal strip A in the main unit.
2. Install a jumper wire between the terminal points “1” and “2” in the low
voltage terminal strip on all extension units.3. Connect a multi-strand
twisted pair shielded cable (18-24 AWG, 120 Z) between the J10 connectors on
the control board of each Condair EL steam humidifier in the Linkup system.
IMPORTANT! Do not reverse polarity.
4. Install the termination jumper JP8 in the control board of the last
extension unit in the Linkup system. 5. Finally, refer to the Operation Manual
to set up the multi-unit configuration in the control software.
1
2
3
24VGND GND + GND + GND + REMOTE BOARD
ACCESSORY BOARD
24VGND GND + GND + GND + REMOTE BOARD
ACCESSORY BOARD
24VGND GND + GND + GND + REMOTE BOARD
ACCESSORY BOARD
BMS
LinkUp
SD
JP4 JP7
JP8
3V
BAT CR2032 JP11
CONTROL BOARD
Low Voltage Terminal Strip
SAB
LinkUp
BMS
SD
JP4 JP7
JP8
3V
BAT CR2032 JP11
CONTROL BOARD
Low Voltage Terminal Strip
SAB
12345 67 89 All inputs
12345 67 89
4
Fig. 24: Multi-Unit Linkup Connections
1 Main unit (all control signals to unit) 2 Extension unit #1 (no control signals to unit) 3 Extension unit #X (no control signals to unit) 4 Jumper (on all extension units) 5 Termination jumper, JP8 (only on last unit in Linkup chain)
2582419-F EN 2406
SD
BMS
LinkUp
JP4
JP7 JP8
3V
BAT CR2032 JP11
SAB
LinkUp GND +
JP8 CONTROL BOARD
Low Voltage Terminal Strip
5
12345 67 89
4
Mounting and Installation Work 53
5.8.6 Fuses “F3” Voltage Supply
208 V/1~/50…60 Hz 240 V/1~/50…60 Hz 480 V/1~/50…60 Hz 600 V/1~/50…60 Hz
Max. output (kW) Max. Current (A) Max. external fuse F3 (A) Max. output (kW) AL min. in mm2 Max. external fuse F3 (A) Max. output (kW) AL min. in mm2 Max. external fuse F3 (A) Max. output (kW) Max. Current (A) Max. external fuse F3 (A)
RS 10 RS 15 RS 20 RS 30 RS 45 RS 65 RS 90 RS 130 RS 180
3.7 17.8 25 3.7 2.5 5.4 26 35 4.9 4 7.2 34.7 45 7.2 10 10.8 52 70 10.8 16
20 3.3 2.5 30 4.8 2.5 40 6.4 2.5 60 10.7 4
15 3.9 6.5 15
15
5 8.3 15
20 6.7 11.1 15
30 10.7 17.8 25
208 V/3~/50…60 Hz 240 V/3~/50…60 Hz 480 V/3~/50…60 Hz 600 V/3~/50…60 Hz
Max. output (kW) Max. Current (A) Max. external fuse F3 (A) Max. output (kW) Max. Current (A) Max. external fuse F3 (A) Max. output (kW) Max. Current (A) Max. external fuse F3 (A) Max. output (kW) Max. Current (A) Max. external fuse F3 (A)
RS 10 RS 15 RS 20 RS 30 RS 45 RS 65 RS 90 RS 130 RS 180
3.7 10.3 15 3.7 8.9 15 3.8 4.6 15 3.8 3.6 15
5.4 15 20 4.9 11.9 15
5
6
15
6 5.8 15
7.2 20 25 7.2 17.3 25 6.6 7.9 15 7.7 7.4 15
9.8 27.2 35 10.8 26 35 10.7 12.9 20 10.7 10.3 15
16.2 45 60 16.1 38.7 50 15.4 18.5 25 16 15.4 20
24.3 67.5 90 24.1 58 80 21.4 25.8 35 24 23.1 30
32.4 90 50 32.2 77.4 40 32.1 38.7 125 32 30.8 100
48.6 135 175 48.2 116 150 42.8 51.6 70 48 46.2 60
64.2 77.3 100 64 61.7 80
54 Mounting and Installation Work
2582419-F EN 2406
5.8.7 Inspecting the Electrical Installation
Check the following points: Does the supply voltage comply with the voltage
stated on the specification label? Is the voltage supply correctly fused? Are
all components correctly connected according to the wiring diagram? Are all
connecting cables fastened? Are the connecting cables free of tension (passed
through cable glands?) Does the electric installation meet the applicable
local regulations for electric installations? Is the unit reassembled
correctly and the front panel fixed with the screw?
2582419-F EN 2406
Mounting and Installation Work 55
6 Appendix
6.1 Unit Dimensions
6.83 (173.5) 2.82 (71.7)
AA
CONDENSATE OUT ø 0.31 (8) 2x MARKED “A”
8.54 (217) 3.24 (82.4) 1.76 (44.7)
14.33 (364)
0.28 (7)
4.87 (123.8)
STEAM OUT ø 1.77 (45)
16.54 (420)
3.16 (80.2) 2.27 (57.6)
12.00 (304.8) 12.00 (304.8)
1.38 (35) 2.27 (57.6)
0.59 (15) 2.13 (54) 19.69 (500) 7.62 (193.5) 2.13 (54)
38.85 (986.7) 26.40 (670.5)
10.63 (270)
2.24 (57)
WATER FILL NPT 1/2″
8.76 (222.5)
SECONDARY WATER FILL (RS-RO OPTION) NPT 1/2″)
3.82 (97) 1.73 (44)
11.91 (302.5)
8.33 (211.5)
2.01 (51)
WATER DRAIN Ø 1.22 (31)
Fig. 25: Unit dimensions unit “Small” – dimensions in Inch (mm)
56 Appendix
2582419-F EN 2406
7.16 (181.8)
2.43 (61.8)
6.44 (163.5)
A
A
CONDENSATE OUT ø 0.31 (8) 2xMARKED “A”
9.13 (232) 3.24 (82.4)
1.76 (44.7)
15.98 (406)
0.28 (7)
STEAM OUT ø 1.77 (45)
20.87 (530)
3.48 (88.5) 16.00 (406.5)
2.43 (61.8)
16.00 (406.5)
1.38 (35)
2.43 (61.8)
24.02 (610) 7.62 (193.5) 2.13 (54)
43.19 (1097) 30.71 (780)
2.13 (54)
0.59 (15)
10.63 (270)
WATER FILL NPT 1/2″
13.09 (332.5)
2.24 (57)
SECONDARY WATER FILL (RS-RO OPTION) NPT 1/2″)
3.82 (97) 1.73 (44)
12.26 (311.5)
2.01 (51) 12.66 (321.5)
WATER DRAIN Ø 1.22 (31)
Fig. 26: Unit dimensions unit “Medium”- dimensions in Inch (mm)
2582419-F EN 2406
Appendix 57
20.49 (520.5)
16.49 (418.8) 6.44 (163.5) 2.43 (61.8)
A
A
A
A
CONDENSATE OUT ø 0.31 (8) 4X MARKED “A”
9.13 (232) 3.24 (82.4) 1.76 (44.7)
178.8
535.8
15.98 (406)
0.28 (7)
39.37 (1000)
STEAM OUT ø 1.77 (45) 2X
4.61 (117) 16.00 (406.5)
16.00 (406.5) 2.76 (70)
10.37(263.5) 6.46 (164)
23.23 (590)
43.19 (1097) 30.71 (780)
2.13 (54)
10.63 (270)
WATER FILL NPT 1/2″ 2X
27.15 (689.5) 13.09 (332.5)
0.59 (15)
4.21 (107)
SECONDARY WATER FILL (RS-RO OPTION) NPT 1/2″)
12.26 (311.5)
3.82 (97) 1.73 (44)
2.01(51) 12.66(321.5)
16.06 (408) 26.71 (678.5)
WATER DRAIN Ø 1.22 (31) 2X
Fig. 27: Unit dimensions unit “Large”- dimensions in Inch (mm)
58 Appendix
2582419-F EN 2406
Warranty
Condair Inc. or Condair Ltd. (depending on the entity that supplied the
product, and hereinafter collectively referred to as CONDAIR) warrant for a
period of two years after installation or 30 months from the manufacturer’s
ship date, whichever date is earlier, that CONDAIR’s manufactured and
assembled products, not otherwise expressly warranted, are free from defects
in materials and workmanship. Notwithstanding the foregoing, the products
listed below have an alternate warranty period: · GS/GSTC Series heat
exchanger(s) are warranted to be free from defects in materials and
workmanship for a period of 3
years from installation or 40 months from the manufacturer’s ship date,
whichever is earlier. · SAM-e Short Absorption Manifolds, except for the
coupling seals, are warranted to be free from defects in materials and
workmanship for a total period of 10 years from the manufacturer’s ship date.
· Humilife RH humidifiers are warranted to be free from defects in materials
and workmanship for a period of 5 years from
the manufacturer’s ship date. CONDAIR may, at its discretion, replace
individual components or Humilife RH units as a whole. · Spare Parts used for
repairs are warranted for the balance of the term of the warranty on the
original humidifier or 90 days, whichever is longer. · No warranty is made
against corrosion, deterioration, or suitability of substituted materials used
as a result of compliance with government regulations.
CONDAIR’s obligations and liabilities under this warranty are limited to
furnishing replacement parts to the customer, F.O.B. CONDAIR’s factory. The
replacement parts are warranted for the balance of the term of the warranty on
the original humidifier or 90 days, whichever is longer. Procedure: 1.
Customer Requests Warranty as per instructions on the CONDAIR Warranty Form.
2. CONDAIR reviews the warranty claim and will respond in one of two ways:
a. Warranty Accepted Replacement Part or credit granted. b. Warranty
Declined Response with justification will be provided to the customer. 3. In
some cases, CONDAIR may request the part to be returned, freight prepaid by
the customer, as part of the warranty acceptance or warranty determination
process. Some reasons include: a. Part must be analyzed to determine the root
cause of failure. b. Part must be returned to the supplier for
claim/investigation.
When parts are requested to be returned, replacement parts will be sent by
CONDAIR to the customer against an invoice from CONDAIR paid by the customer.
The cost of the replacement parts will be reimbursed to the customer with a
credit note after the parts are received and analyzed by CONDAIR, if the
warranty is accepted.
The warranties set forth herein are in lieu of all other warranties expressed
or implied by law. No liability whatsoever shall be attached to CONDAIR until
said products have been paid for in full and then said liability shall be
limited to the original purchase price for the product. Any further warranty,
with the exception of a purchased extended warranty described below, must be
in writing, and signed by an officer of CONDAIR.
CONDAIR makes no warranty and assumes no liability unless the equipment is
installed in strict accordance with the installation manual in effect at the
date of purchase, and by properly qualified and licensed professionals capable
of installing such equipment.
CONDAIR makes no warranty and assumes no liability whatsoever for
consequential damage or damage resulting directly from misapplication,
incorrect sizing, or lack of proper maintenance of the equipment.
CONDAIR makes no warranty and assumes no liability whatsoever for damage to
the products, humidifier, supply lines, drain lines, steam distribution
systems, or the building as a whole caused by freezing.
CONDAIR reserves the right to change the design, specifications, and
performance criteria of its products without notice or obligation.
Extended Warranty
Extended warranties are available to purchase under the conditions listed
above. Extended warranties must be purchased at the time of the original
equipment order.
www.condairparts.com
Buy authentic Condair parts factory direct.
U.S.A. 1021 6th Street Racine, WI 53403
CANADA 2740 Fenton Road Ottawa, Ontario K1T 3T7
TEL: 1.866.667.8321 EMAIL: na.info@condair.com WEBSITE: www.condair.com