TROX FKR-EU Fire Damper Installation Guide

September 21, 2024
TROX

FKR-EU Fire Damper

“`html

Specifications:

  • Product: Fire damper FKR-EU
  • Model: FKR-EU
  • Manufacturer: TROX GmbH
  • Country of Origin: Germany

Product Usage Instructions:

General Information:

This operating and installation manual is intended for use by
fitting and installation companies, in-house technicians, technical
staff, instructed persons, and qualified electricians or air
conditioning technicians. It is essential that these individuals
read and fully understand this manual before starting any work.

Copyright:

This document, including all illustrations, is protected by
copyright. Any use without consent may be an infringement of
copyright, and the violator will be held liable for any damage.

Limitation of Liability:

The manufacturer does not accept any liability for damages
resulting from non-compliance with the manual, incorrect use,
operation by untrained individuals, unauthorized modifications,
technical changes, or use of non-approved replacement parts.

Warranty Claims:

Warranty claims are subject to the respective general delivery
terms. For purchase orders placed with TROX GmbH, refer to the
regulations in section Vl. Warranty claims of the Delivery Terms of
TROX GmbH.

TROX Technical Service:

To ensure that your request is processed as quickly as possible,
please keep the following information ready:

Frequently Asked Questions (FAQ):

Q: Who should use this manual?

A: This manual is intended for fitting and installation
companies, in-house technicians, technical staff, instructed
persons, and qualified electricians or air conditioning
technicians.

Q: What is the scope of delivery?

A: The actual scope of delivery may differ from the information
in this manual for bespoke constructions, additional order options,
or recent technical changes.

Q: What are the warranty claim procedures?

A: Warranty claims are subject to the respective general
delivery terms. For orders placed with TROX GmbH, refer to the
regulations in section Vl of the Delivery Terms.

“`

Installation and operating manual

GB/en

Fire damper
FKR-EU
according to Declaration of Performance DoP / FKR-EU / DE / 004

Read the instructions prior to performing any task!

TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn, Germany Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202-265 E-mail: trox-de@troxgroup.de Internet: http://www.troxtechnik.com
Translation of the original A00000092704-GB, 1, GB/en 03/2022

© 2021 2

Fire damper FKR-EU

General information

General information
About this manual
This operating and installation manual enables operating or service personnel to correctly install the TROX product described below and to use it safely and efficiently.
This operating and installation manual is intended for use by fitting and installation companies, in-house technicians, technical staff, instructed persons, and qualified electricians or air conditioning technicians.
It is essential that these individuals read and fully understand this manual before starting any work. The basic prerequisite for safe working is to comply with the safety notes and all instructions in this manual.
The local regulations for health and safety at work and general safety regulations also apply.
This manual must be given to the system owner when handing over the system. The system owner must include the manual with the system documentation. The manual must be kept in a place that is accessible at all times.
Illustrations in this manual are mainly for information and may differ from the actual design.
Copyright
This document, including all illustrations, is protected by copyright and pertains only to the corresponding product.
Any use without our consent may be an infringement of copyright, and the violator will be held liable for any damage.
This applies in particular to:
Publishing content Copying content Translating content Microcopying content Saving content to electronic systems and editing it

Limitation of liability
The information in this manual has been compiled with reference to the applicable standards and guidelines, the state of the art, and our expertise and experience of many years.
The manufacturer does not accept any liability for damages resulting from:
Non-compliance with this manual Incorrect use Operation or handling by untrained individuals Unauthorised modifications Technical changes Use of non- approved replacement parts
The actual scope of delivery may differ from the information in this manual for bespoke constructions, additional order options or as a result of recent technical changes.
The obligations agreed in the order, the general terms and conditions, the manufacturer’s terms of delivery, and the legal regulations in effect at the time the contract is signed shall apply.
We reserve the right to make technical changes.
Warranty claims
The provisions of the respective general delivery terms apply to warranty claims. For purchase orders placed with TROX GmbH, these are the regulations in section “Vl. Warranty claims” of the Delivery Terms of TROX GmbH, see www.trox.de/en/ .

TROX Technical Service
To ensure that your request is processed as quickly as possible, please keep the following information ready:
Product name TROX order number Delivery date Brief description of the fault

Online Phone

www.troxtechnik.com +49 2845 202-400

Fire damper FKR-EU

3

General information

Safety notes Symbols are used in this manual to alert readers to areas of potential hazard. Signal words express the degree of the hazard. Comply with all safety instructions and proceed carefully to avoid accidents, injuries and damage to property.
DANGER! Imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING! Potentially hazardous situation which, if not avoided, may result in death or serious injury.

Safety notes as part of instructions Safety notes may refer to individual instructions. In this case, safety notes will be included in the instructions and hence facilitate following the instructions. The above listed signal words will be used.
Example:
1. Loosen the screw. 2.
CAUTION!
Danger of finger entrapment when closing the lid.
Be careful when closing the lid.
3. Tighten the screw.

CAUTION! Potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
NOTICE! Potentially hazardous situation which, if not avoided, may result in property damage.

Specific safety notes
The following symbols are used in safety notes to alert you to specific hazards:

Warning signs

Type of danger Warning ­ danger zone.

ENVIRONMENT! Environmental pollution hazard.

Tips and recommendations

Useful tips and recommendations as well as information for efficient and fault-free operation.

4

Fire damper FKR-EU

Table of contents

1 Safety ………………………………………………………. 7
1.1 General safety notes …………………………… 7 1.2 Correct use ………………………………………… 7 1.3 Qualified staff ……………………………………… 8
2 Technical data ………………………………………….. 9
2.1 General data ………………………………………. 9 2.2 FKR-EU with fusible link …………………….. 11 2.3 FKR-EU with spring return actuator …….. 13 2.4 FKR-EU with fusible link and cover grille
on both sides as an upstream shutter for the air transfer unit ……………………………. 19
3 Supply package, transport and storage …… 20
4 Parts and function ………………………………….. 21
4.1 Function in the ventilation system ……….. 21 4.2 FKR-EU with fusible link …………………….. 21 4.3 FKR-EU with spring return actuator …….. 21 4.4 FKR-EU with spring return actuator and
duct smoke detector ………………………….. 22 4.5 FK-EU with fusible link and cover grille on
both sides as an upstream shutter for the air transfer unit .. 23
5 Installation ……………………………………………… 24
5.1 Installation situations …………………………. 24 5.2 Safety notes regarding installation ………. 26 5.3 General installation information …………… 26 5.4 Installation kits ………………………………….. 37 5.4.1 Installation kit TQ for dry mortarless
installation …………………………………….. 37 5.5 Solid walls ……………………………………….. 38 5.5.1 General …………………………………………. 38 5.5.2 Mortar-based installation …………………. 39 5.5.3 Mortar-based installation ­ multiple
occupancy of an installation opening … 43 5.5.4 Dry mortarless installation with fire batt
……………………………………………………… 45 5.6 Lightweight partition walls ………………….. 47 5.6.1 General …………………………………………. 47 5.6.2 Mortar-based installation …………………. 54 5.6.3 Mortar-based installation ­ multiple
occupancy of an installation opening … 59 5.6.4 Dry mortarless installation with installa-
tion kit TQ ……………………………………… 62 5.6.5 Dry mortarless installation without instal-
lation kit ………………………………………… 65 5.6.6 Dry mortarless installation with fire batt
……………………………………………………… 66 5.7 Lightweight partition walls with timber sup-
port structure or half-timbered constructions ………………………………………………… 70 5.7.1 General …………………………………………. 70 5.7.2 Mortar-based installation …………………. 74

5.7.3 Mortar-based installation ­ multiple occupancy of an installation opening … 81
5.7.4 Dry mortarless installation with installation kit TQ ……………………………………… 85
5.7.5 Dry mortarless installation with fire batt ……………………………………………………… 87
5.8 Solid wood walls ……………………………….. 92
5.8.1 General …………………………………………. 92
5.8.2 Mortar-based installation …………………. 93
5.8.3 Dry mortarless installation with installation kit TQ ……………………………………… 95
5.8.4 Dry mortarless installation with fire batt ……………………………………………………… 96
5.9 Shaft walls with metal support structure .. 98
5.9.1 General …………………………………………. 98
5.9.2 Mortar-based installation ……………….. 100
5.10 Shaft walls without metal support structure ……………………………………………… 103
5.10.1 General ……………………………………… 103
5.10.2 Mortar-based installation ……………… 104
5.11 Solid ceiling slabs ………………………….. 105
5.11.1 General ……………………………………… 105
5.11.2 Mortar-based installation into solid ceiling slabs ……………………………….. 106
5.11.3 Mortar-based installation ­ multiple occupancy of an installation opening 112
5.11.4 Mortar-based installation into a concrete base ………………………………….. 114
5.11.5 Mortar-based installation into the concrete base ­ multiple occupancy of an installation opening ……………………… 117
5.11.6 Mortar-based installation into hollow stone ceilings ……………………………… 120
5.11.7 Mortar-based installation into hollow chamber ceilings …………………………. 121
5.11.8 Mortar-based installation into ribbed ceilings ………………………………………. 122
5.11.9 Mortar-based installation into composite ceilings ………………………………… 123
5.11.10 Mortar-based installation in conjunction with wooden beam ceilings …… 124
5.11.11 Mortar-based installation in conjunction with solid wood ceilings ………… 125
5.11.12 Mortar-based installation in conjunction with lightweight ceilings ………… 126
5.12 Solid wood ceilings ………………………… 127
5.12.1 Mortar-based installation into solid wood ceilings ……………………………… 127
5.12.2 Dry mortarless installation with installation kit TQ into solid wood ceilings … 128
5.13 Wooden beam ceilings …………………… 129
5.13.1 Mortar-based installation into wooden beam ceilings …………………………….. 129

Fire damper FKR-EU

5

Table of contents
5.13.2 Dry mortarless installation with installation kit TQ into wooden beam ceilings …………………………………………………. 131
5.13.3 Mortar-based installation into historical wooden beam ceilings …………………. 133
5.14 Fixing the fire damper …………………….. 135 5.14.1 General ……………………………………… 135 5.14.2 Fixing the damper when a fire batt is
used ………………………………………….. 136
6 Accessories …………………………………………. 137
7 Electrical connection ……………………………. 140 7.1 General safety notes ……………………….. 140 7.2 Limit switches (fire dampers with fusible link) ……………………………………………….. 140 7.3 Spring return actuator ………………………. 140 7.4 Spring return actuator and duct smoke detector RM-O-3-D ………………………….. 140
8 Functional test ……………………………………… 141 8.1 General ………………………………………….. 141 8.2 Functional test with automatic control unit ………………………………………………………. 141 8.3 Fire damper with fusible link ……………… 142 8.4 Fire damper with spring return actuator 143 8.4.1 Spring return actuator BFN… …………. 143 8.4.2 Spring return actuator BF… ……………. 145
9 Commissioning …………………………………….. 147
10 Maintenance …………………………………………. 148 10.1 General ………………………………………… 148 10.2 Replacing the fusible link ………………… 149 10.3 Inspection, maintenance and repair measures ……………………………………… 151
11 Decommissioning, removal and disposal . 153
12 Nomenclature ……………………………………….. 154
13 Change history …………………………………….. 159
14 Index…………………………………………………….. 160

6

Fire damper FKR-EU

Safety
Correct use

1 Safety
1.1 General safety notes
Sharp edges, sharp corners and thin sheet metal parts
CAUTION! Danger of injury from sharp edges, sharp corners and thin sheet metal parts! Sharp edges, sharp corners and thin sheet metal parts may cause cuts or grazes. ­ Be careful when carrying out any work. ­ Wear protective gloves, safety shoes and a hard
hat.

If this fire damper is used in Germany:
Do not use it in extract air systems in commercial kitchens.
Not to be used as an air transfer damper.
Do not use in combined penetration seal.
Do not use in fire protection block bulkhead.
Approvals under building regulations may be required for the use of upstream shutters for air transfer units. This must be checked and applied for by others.
Flame-resistant, non-dripping building materials (elastomeric foams) must at least correspond to fire rating class C – s2, d0 according to the specifications of MVV TB (since 2019/1). The applicable local building regulations must be observed.

Electrical voltage
DANGER!
Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage.
­ Only skilled qualified electricians are allowed to work on the electrical system.
­ Switch off the power supply before working on any electrical equipment.
1.2 Correct use
The fire damper is used as an automatic shut-off device to prevent fire and smoke from spreading through ducting.
The fire damper is suitable for supply and extract air in HVAC systems.
The fire damper may be used in potentially explosive atmospheres if appropriate special accessories are used with it and if the product bears the CE conformity marking according to Directive 94/9/EC. Fire dampers for use in potentially explosive atmospheres are marked for the zones for which they have been approved.
Operation of the fire dampers is allowed only in compliance with installation regulations and the technical data in this installation and operating manual.
Modifying the fire damper or using replacement parts that have not been approved by TROX is not permitted.

Incorrect use
WARNING!
Danger due to incorrect use! Incorrect use of the fire damper can lead to dangerous situations.
Never use the fire damper
­ without specially approved attachments in areas with potentially explosive atmospheres
­ as a smoke control damper ­ outdoors without sufficient protection against the
effects of weather ­ in atmospheres where chemical reactions,
whether planned or unplanned, may cause damage to the fire damper or lead to corrosion

Fire damper FKR-EU

7

Safety
Qualified staff
1.3 Qualified staff
WARNING! Danger of injury due to insufficiently qualified individuals! Incorrect use may cause considerable injury or damage to property. ­ Only specialist personnel must carry out work.
Personnel: Skilled qualified electrician Specialist personnel
Skilled qualified electrician Skilled qualified electricians are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to work on electrical systems, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved.
Specialist personnel Specialist personnel are individuals who have sufficient professional or technical training, knowledge and actual experience to enable them to carry out their assigned duties, understand any potential hazards related to the work under consideration, and recognise and avoid any risks involved.

8

Fire damper FKR-EU

Technical data
General data

2 Technical data
2.1 General data

Nominal sizes

315 ­ 800 mm

Casing lengths L

495 and 550 mm

Volume flow rate range

Up to 6000 l/s / up to 21600 m³/h (at 12 m/s)

Differential pressure range

Up to 2000 Pa

Temperature range 1, 3, 4

-20 °C to 50 °C

Release temperature 4

72 °C or 95 °C (for warm air ventilation systems)

Upstream velocity 2, 4

8 m/s with fusible link, 12 m/s with spring return actuator

Closed damper blade air leakage

EN 1751, Class 4

Casing leakage

EN 1751, Class C

EC conformity

Construction Products Regulation (EU) Nr. 305/2011
EN 15650 ­ Ventilation for buildings ­ Fire dampers
EN 13501-3 ­ Classification: Fire resistant ducts and fire dampers
EN 1366-2 ­ Fire resistance tests for installations: Fire dampers 5
EN 1751 Ventilation for buildings ­ Air terminal devices
2006/42/EC – Machinery Directive

Declaration of performance

DoP / FKR-EU / DE / 004

  1. Temperatures may differ for units with attachments. Details for other applications are available on request.

  2. Data applies to uniform upstream and downstream conditions for the fire dampers.

  3. Condensation and the intake of humid fresh air have to be avoided as otherwise operation will be impaired or not possible. 4) For FKR-EU in Ex construction, see the supplementary operating manual. 5) Leakage rate of the fire damper system tested at 300 Pa negative pressure.

Fire damper FKR-EU

9

Technical data
General data
Product sticker

Fig. 1: Product sticker (example)
1 CE mark 2 Manufacturer’s address 3 Number of the European standard and year of its
publication 4 Notified body 5 The last two digits of the year in which the CE
marking was affixed 6 Year of manufacture

7 No. of the declaration of performance 8 Website from which the DoP can be downloaded 9 Regulated characteristics; the fire resistance class
depends on the application and may vary Ä Chapter 5.1 `Installation situations’ on page 24 10 Type 11 Order number

10

Fire damper FKR-EU

2.2 FKR-EU with fusible link
Dimensions and weight

Technical data
FKR-EU with fusible link

Fig. 2: FKR-EU with fusible link
1 Spigot construction 2 Flange construction 3 Keep clear to provide access for operation

A Installation side B Operating side

Weight of FKR-EU with fusible link, see table Ä 12 .

Connecting cable length / cross section Protection level Type of contact Maximum switching current Maximum switching voltage Contact resistance

Limit switch 1 m / 3 × 0.34 mm² IP 66 1 changeover contact, gold-plated 0.5 A 30 V DC, 250 V AC approx. 30 m

Fire damper FKR-EU

11

Technical data
FKR-EU with fusible link

Nominal size DN ÆD A ÆD1 No. of holes Weight of FKR-EU Weight of FKR-EU with spigot and installation kit TQ

Dimensions [mm] / Weight [kg]

315 355

400

450

500

314 354

399

449

499

31

352 392

438

488

538

45 °

8

6.8

7.3

8.5

14.1 16.4

19.5 21.8

25

33.1 37.8

560 630 710 800

559 629 709 799

36

600 670 750 840

30 °

22.5 °

12

16

18 21.3 25.7 28.6

42.6 49.7 58.7 67.3

12

Fire damper FKR-EU

2.3 FKR-EU with spring return actuator
Dimensions and weight

Technical data
FKR-EU with spring return actuator

Fig. 3: FKR-EU with Belimo spring return actuator

1 Spigot construction 2 Flange construction 3 Keep clear to provide access for operation

A Installation side B Operating side

Weight of FKR-EU with fusible link + approx. 1 kg (BFN…) or 3 kg (BF…), see table Ä 12 .

Fire damper FKR-EU

13

Technical data
FKR-EU with spring return actuator

Spring return actuator BFN…

Construction

230-T TR

24-T-ST TR

Supply voltage

230 V AC, 50/60 Hz

24 V AC/DC, 50/60 Hz

Functional range

198 ­ 264 V AC

19.2 ­ 28.8 V AC 21.6 ­ 28.8 V DC

Power rating

Spring winding mechanism / hold position

5 W / 2.1 W

4 W / 1.4 W

Rating

10 VA (Imax 4 A @ 5 ms) 6 VA (Imax 8.3 A @ 5 ms)

Run time

Actuator / spring return

< 60 s / < 20 s

Limit switch

Type of contact

2 changeover contacts

Switching voltage

5 ­ 120 V DC / 5 ­ 250 V AC

Switching current

1 mA ­ 3 (0.5 inductive) A

Contact resistance

< 1 (when new)

IEC protection class / IP protection

II / IP 54

Storage temperature / ambient temperature

-40 to 55 °C / -30 to 55 °C ¹

Ambient humidity

95% rh, no condensation

Connecting cable

Actuator / limit switch

1 m, 2 × 0.75 mm² / 1 m, 6 × 0.75 mm² (free of halogens)

Spring return actuator type BFN… Nominal sizes: nominal width 315 ­ 400 mm.

¹ Up to 75 °C the safe position will definitely be reached.

14

Fire damper FKR-EU

Technical data
FKR-EU with spring return actuator

Spring return actuator BF…

Construction

BF230-TN-2 TR

BF24-TN-ST-2 TR

Supply voltage

230 V AC, 50/60 Hz

24 V AC/DC, 50/60 Hz

Functional range

198 ­ 264 V AC

19.2 ­ 28.8 V AC 21.6 ­ 28.8 V DC

Power rating

Spring winding mechanism / hold position

8.5 W / 3 W

7 W / 2 W

Rating

11 VA

10 VA

Run time

Actuator / spring return

< 120 s / approx. 16 s

Limit switch

Type of contact

2 changeover contacts

Switching voltage

5 ­ 120 V DC / 5 ­ 250 V AC

Switching current

1 mA … 6 A

Contact resistance

< 100 m

IEC protection class / IP protection

II / IP 54

III / IP 54

Storage temperature / ambient temperature

-40 to 50 °C / -30 to 50 °C ¹

Ambient humidity

95% rh, no condensation

Connecting cable

Actuator / limit switch

1 m, 2 × 0.75 mm² / 1 m, 6 × 0.75 mm² (free of halogens)

Spring return actuator type BF… for nominal sizes: nominal width 450 ­ 800 mm.

¹ Up to 75 °C the safe position will definitely be reached.

Fire damper FKR-EU

15

Technical data
FKR-EU with spring return actuator
Dimensions and weight

Fig. 4: FKR-EU with Siemens spring return actuator

1 Spigot construction 2 Flange construction 3 Keep clear to provide access for operation

A Installation side B Operating side

Weight of FKR-EU with fusible link + approx. 1.4 kg (GNA…) or 2.5 kg (GGA…), see table Ä 12 .

16

Fire damper FKR-EU

Technical data
FKR-EU with spring return actuator

Spring return actuator GNA…

Construction

326.1E

126.1E

Supply voltage

230 V AC, 50/60 Hz

24 V AC, 50/60 Hz / 24 ­ 48 V DC

Functional range

198 ­ 264 V AC

19.2 ­ 28.8 V AC 19.2 ­ 57.6 V DC

Power rating

Spring winding mechanism

7 VA / 4.5 W

5 VA / 3.5 W

Hold position

3.5 W

2 W

Run time

Actuator / spring return

90 s / 15 s

Limit switch

Type of contact

2 changeover contacts

Switching voltage

24 ­ 230 V AC / 12 ­ 30 V DC

Switching current

AC: 6 A (inductive 2 A) / DC: 2 A

IEC protection class / IP protection

II / IP 42 or IP 54*

III / IP 42 or IP 54*

Storage temperature / ambient temperature

-20 to 50 °C / -20 to 50 °C

Ambient humidity

< 95% rh, no condensation

Connecting cable

Actuator / limit switch

0.9 m, 2 × 0.75 mm² / 1 m, 6 × 0.75 mm² (free of halogens)

Spring return actuator type GNA… Nominal sizes: nominal width 315 ­ 400 mm.

*Connecting cable at the bottom

Spring return actuator GGA…

Construction

326.1E

126.1E

Supply voltage

230 V AC, 50/60 Hz

24 V AC, 50/60 Hz / 24 ­ 48 V DC

Functional range

198 ­ 264 V AC

19.2 ­ 28.8 V AC 19.2 ­ 57.6 V DC

Power rating

Spring winding mechanism

8 VA / 6 W

7 VA / 5 W

Hold position

4 W

3 W

Run time

Actuator / spring return

90 s / 15 s

Limit switch

Type of contact

2 changeover contacts

Switching voltage

24 ­ 230 V AC / 12 ­ 30 V DC

Switching current

AC: 6 A (inductive 2 A) / DC: 2 A

IEC protection class / IP protection

II / IP 42 or IP 54*

III / IP 42 or IP 54*

Storage temperature / ambient temperature

-20 to 50 °C / -20 to 50 °C

Ambient humidity

< 95% rh, no condensation

Connecting cable

Actuator / limit switch

0.9 m, 2 × 0.75 mm² / 1 m, 6 × 0.75 mm² (free of halogens)

Spring return actuator type GGA… for nominal sizes: nominal width 450 ­ 800 mm.

*Connecting cable at the bottom

Fire damper FKR-EU

17

Technical data
FKR-EU with spring return actuator
FKR-EU with Schischek explosion-proof spring return actuator The FKR-EU can also be supplied with Schischek explosion-proof spring return actuator on request: ExMax-15-BF-TR RedMax-15-BF-TR For further information, see “Supplementary operating manual for explosion-proof fire dampers Type FKR-EU”.

18

Fire damper FKR-EU

Technical data
FKR-EU with fusible link and cover grille on bot…
2.4 FKR-EU with fusible link and cover grille on both sides as an upstream shutter for the air transfer unit
Dimensions and weight

Fig. 5: FKR-EU with fusible link
1 Spigot construction 2 Flange construction 3 Keep clear to provide access for operation

A Installation side B Operating side

Weight of FKR-EU with fusible link, see table Ä 12 .

Note: Approvals under building regulations may be required for the use of air transfer units. This must be checked and applied for by others.

Fire damper FKR-EU

19

Supply package, transport and storage

3 Supply package, transport and storage
Supply package
If attachments and accessories are supplied from the factory with the fire dampers, they are already taken into account in the order code.
Depending on the installation situation, supplementary materials for assembly and fixing may be needed to ensure proper installation, e.g. mortar, screws, mineral wool, etc.
Such materials are not included in the supply package, unless they are expressly described as included in the supply package.
The selection of additional attachments or accessories as well as the identification and provision of materials for assembly and fixing is the responsibility of those involved in the building project and must be done taking into account the required classification.

Packaging Properly dispose of packaging material.

Delivery check Check delivered items immediately after arrival for transport damage and completeness. In case of any damage or an incomplete shipment, contact the shipping company and your supplier immediately.
Fire damper ­ Attachments/accessories, if any
Operating manual (1 per shipment)
Colour hues on the damper blade The blades of fire dampers are treated with a greenish impregnating agent. Resulting colour hues on the damper blade are due to technical reasons and do not constitute a defect of any kind.

Transport on site
If possible, take the product in its transport packaging up to the installation location.
Bearing
For temporary storage please note:
Remove any plastic wrapping. Protect the product from dust and contamination. Store the product in a dry place and away from
direct sunlight. Do not expose the unit to the effects of weather (not
even in its packaging). Do not store the product below -40 °C or above 50
°C.

20

Fire damper FKR-EU

Parts and function
FKR-EU with spring return actuator

4 Parts and function
4.1 Function in the ventilation system
Fire dampers are used as safety related components in ventilation systems. The fire damper is used as a shutoff device to prevent fire and smoke from spreading through ducting. During normal operation the damper blade is open to enable air passage through the ventilation system.
If the temperature increases in the event of a fire, the damper blade closes. Release is triggered at 72 °C ( 95 °C in warm air ventilation systems). If the damper blade closes due to a temperature increase (i.e. in the event of a fire), it must not be reopened.

4.3 FKR-EU with spring return actuator

4.2 FKR-EU with fusible link

Fig. 7: FKR-EU with spring return actuator (Fig. Spigot construction)
1.1 Casing 1.2 Damper blade with seal 1.4 Travel stop for CLOSED position 1.8 Lip seal 10.1 Spring return actuator 10.13 Thermoelectric release mechanism with temper-
ature sensor

Fig. 6: FKR-EU with fusible link (Fig. Flange construction)
1.1 Casing 1.2 Damper blade with seal 1.4 Travel stop for CLOSED position 1.6 Handle 1.10 Release tab 1.11 Flange 10.14 Thermal release mechanism with fusible link
Functional description
In fire dampers with a fusible link, damper closure is triggered by the fusible link. If the temperature inside the fire damper rises to 72 °C or 95 °C, the fusible link triggers a coil spring mechanism. The coil spring mechanism then causes the fire damper to close.
As an option, the fire damper can be either supplied or subsequently fitted with one or two limit switches. The limit switches can signal the damper blade position to the central BMS or fire alarm system. One limit switch each is required for damper blade positions OPEN and CLOSED.

Functional description
The spring return actuator enables the motorised opening and closing of the damper blade; it can be activated by the central BMS. Motorised fire dampers can be used to shut off ducts on a regular basis. As long as power is supplied to the actuator, the damper blade remains open. The spring return actuator closes the fire damper when one of the following events occur:
Temperature in the fire damper > 72 °C or > 95 °C Ambient temperature outside the release mecha-
nism > 72 °C The power supply is interrupted (power off to close)
As standard, the spring return actuator is equipped with limit switches that can be used to indicate the damper blade position.

Fire damper FKR-EU

21

Parts and function
FKR-EU with spring return actuator and duct smok…

4.4 FKR-EU with spring return actuator and duct smoke detector
FKR-EU with spring return actuator can optionally also be controlled by a duct smoke detector approved by the building authorities, e.g. RM-O-3-D.
Fig. 8: FKR-EU with spring return actuator and duct smoke detector in a rectangular duct 1.1 Casing 1.2 Damper blade with seal 1.4 Travel stop for CLOSED position 1.8 Lip seal 9.2 Rectangular duct, by others 10.1 Spring return actuator 10.12 Duct smoke detector RM-O-3-D 10.13 Thermoelectric release mechanism with temper-
ature sensor

Functional description
If the duct smoke detector detects smoke, the spring return actuator closes the damper blade. This prevents smoke from being transferred via ductwork into adjacent fire compartments even before it reaches a temperature that would trigger the thermoelectric release mechanism.
As long as power is supplied to the actuator, the damper blade remains open. The spring return actuator closes the fire damper when one of the following events occur:
The duct smoke detector detects smoke Temperature in the fire damper > 72 °C Ambient temperature outside the release mecha-
nism > 72 °C The power supply is interrupted (power off to close)
The duct smoke detector must be installed by others in a rectangular duct. Alternatively, the installation can be carried out on site in a circular duct, in a T-piece. The duct smoke detector must always be placed at the top. Deviating arrangements are possible, provided that the specifications of the general building inspectorate licence of the duct smoke detector are observed.

Fig. 9: FKR-EU with spring return actuator and duct smoke detector in a circular duct
1.1 Casing 1.2 Damper blade with seal 1.4 Travel stop for CLOSED position 1.8 Lip seal 9.15 T-piece or saddle connector, by others 10.1 Spring return actuator 10.12 Duct smoke detector RM-O-3-D 10.13 Thermoelectric release mechanism with temper-
ature sensor

22

Fire damper FKR-EU

Parts and function
FK-EU with fusible link and cover grille on both…
4.5 FK-EU with fusible link and cover grille on both sides as an upstream shutter for the air transfer unit

Fig. 10: FKR-EU with fusible link and cover grille as an upstream shutter for the air transfer unit (Fig. Spigot construction)
1.1 Casing 1.2 Damper blade with seal 1.4 Travel stop for CLOSED position 1.6 Handle 1.10 Release tab 9.2 Extension piece 9.10 Cover grilles 10.14 Thermal release mechanism with fusible link
Functional description
Upstream shutters of air transfer units prevent fire and smoke from spreading in buildings. The thermal release mechanism closes the upstream shutter of the air transfer unit when the release temperature of 72°C is reached. Smoke can, however, spread below this temperature.
The upstream shutter of the air transfer unit consists of the FKR-EU fire damper with a thermal release mechanism for 72°C and with cover grilles on both sides, but without a duct smoke detector.
The following applies to Germany: If fire dampers with a purely mechanical shut-off element are to be used as an upstream shutter of an air transfer unit, the local building regulations must be observed. Usually the use of such upstream shutters of air transfer units is restricted to pressure differential systems.

Fire damper FKR-EU

23

Installation
Installation situations
5 Installation
5.1 Installation situations
Note The performance classes of the fire damper and the wall or ceiling slab may differ. The lower performance class determines the performance class of the overall system.

Installation situations

Supporting construction

Installation location

Solid walls

in

Metal stud walls

in, combined assembly in, multiple mounting in, fire batt in

in, combined assembly in, multiple mounting in, installation kit TQ
in, fire batt
in, without installation kit Timber stud walls in
in, combined assembly in, multiple mounting in, installation kit TQ

Minimum thickness
[mm] 100 80 1 100 100 100 94 80 75 94 94 94 80 75 80 75 94 130 110 105 130 130 130 110 105

Class of performance EI TT (ve­ho, i o) S
up to EI 120 S EI 90 S EI 90 S EI 90 S EI 60 S EI 90 S EI 60 S EI 30 S EI 90 S EI 90 S EI 90 S EI 60 S EI 30 S EI 60 S EI 30 S EI 60 S EI 90 S EI 60 S EI 30 S EI 90 S EI 90 S EI 90 S EI 60 S EI 30 S

Installation type
N N N N W N 2 N 2 N 2 N 2 N E E E W W T N N N N N E E E

Chapter
Ä 39 Ä 39 Ä 41 Ä 43 Ä 45 Ä 54 Ä 54 Ä 54 Ä 57 Ä 59 Ä 62 Ä 62 Ä 62 Ä 66 Ä 66 Ä 65 Ä 74 Ä 74 Ä 74 Ä 74 Ä 81 Ä 85 Ä 85 Ä 85

  1. Gypsum wall boards EN12859 2) The class of performance depends on the installation details 3) Thickness increased near the installation opening 4) Cadolto system 5) Depending on local conditions

N = Mortar-based installation E = Installation kit W = Fire batt E = Dry mortarless installation

24

Fire damper FKR-EU

Installation
Installation situations

Installation situations

Supporting construction

Installation location

in, fire batt

Half-timbered con- in structions
in, combined assembly in, multiple mounting in, installation kit TQ

in, fire batt

Solid wood / cross laminated timber walls

in in, installation kit TQ in, fire batt

Shaft wall with

in

metal support

structure

Shaft wall without metal support structure Solid ceiling slabs

in, combined assembly in
in

in, combined assembly
in, multiple mounting
in, with concrete base
in, with concrete base
in, with concrete base, combined assembly
in, with concrete base, multiple mounting
in, hollow stone ceilings
in, hollow chamber ceilings

Minimum thickness
[mm] 110 105 140 110 140 140 140 110 140 110 95 95 95 90 90 3 80 75 90 50
100 (150) 3 100 (150) 3
150 150 100 100 100
100
150 150

Class of performance EI TT (ve­ho, i o) S
up to EI 60 S EI 30 S EI 90 S EI 30 S EI 90 S EI 90 S EI 90 S EI 30 S EI 60 S EI 30 S EI 90 S EI 90 S EI 60 S EI 90 S EI 30 S EI 90 S EI 30 S EI 90 S EI 90 S
EI 120 S EI 90 S EI 90 S EI 90 S EI 90 S EI 120 S EI 90 S
EI 90 S
EI 90 S EI 90 S

Installation type
W W N N N N E E W W N E W N N N N N N
N N N N N N N
N
N N

Chapter
Ä 87 Ä 87 Ä 74 Ä 74 Ä 76 Ä 81 Ä 85 Ä 85 Ä 87 Ä 87 Ä 93 Ä 95 Ä 96 Ä 100 Ä 100 Ä 100 Ä 100 Ä 101 Ä 104
Ä 106 Ä 106 Ä 110 Ä 112 Ä 114 Ä 114 Ä 115
Ä 117
Ä 120 Ä 121

  1. Gypsum wall boards EN12859 2) The class of performance depends on the installation details 3) Thickness increased near the installation opening 4) Cadolto system 5) Depending on local conditions

N = Mortar-based installation E = Installation kit W = Fire batt E = Dry mortarless installation

Fire damper FKR-EU

25

Installation
General installation information

Installation situations

Supporting construction

Installation location
in, ribbed ceilings in, composite ceilings in, combined with wooden beam ceilings in, combined solid wood ceiling in, combined lightweight ceiling
4

Minimum thickness
[mm] 150 3 150 150
150 150

Class of performance EI TT (ve­ho, i o) S
up to EI 90 S EI 90 S EI 90 S
EI 90 S EI 120 S

Installation type
N N N
N N

Chapter
Ä 122 Ä 123 Ä 124 Ä 125 Ä 126

Solid wood ceilings

in in, installation kit TQ

Wooden beam ceil- in ings

in, installation kit TQ

in, historical wooden beam ceilings

140 112.5 140 112.5 167.5 155 142.5 167.5 155 142.5
­ 5

EI 90 S EI 90 S EI 90 S EI 90 S EI 90 S EI 60 S EI 30 S EI 90 S EI 60 S EI 30 S EI 30 S

N

Ä 127

N

Ä 127

E

Ä 128

E

Ä 128

N

Ä 129

N

Ä 129

N

Ä 129

E

Ä 131

E

Ä 131

E

Ä 131

N

Ä 133

  1. Gypsum wall boards EN12859 2) The class of performance depends on the installation details 3) Thickness increased near the installation opening 4) Cadolto system 5) Depending on local conditions

N = Mortar-based installation E = Installation kit W = Fire batt E = Dry mortarless installation

5.2 Safety notes regarding installation
Sharp edges, sharp corners and thin sheet metal parts
CAUTION! Danger of injury from sharp edges, sharp corners and thin sheet metal parts! Sharp edges, sharp corners and thin sheet metal parts may cause cuts or grazes. ­ Be careful when carrying out any work. ­ Wear protective gloves, safety shoes and a hard
hat.

5.3 General installation information
NOTICE!
Risk of damage to the fire damper ­ Protect the fire damper from contamination and
damage. ­ Cover openings and release mechanism (e.g.
with plastic) to protect them from mortar and dripping water. ­ Do not remove the transport and installation protection (if any) until installation is complete.

26

Fire damper FKR-EU

Installation
General installation information

Control elements, electric actuator and inspection access panel must remain accessible for maintenance.
Loads imposed on the casing may impair the function of the fire damper. Install and connect the damper in such a way that no loads will be imposed on the installed damper. Ducts of combustible or non-combustible materials may be connected to fire dampers if the ducts have been installed straight and without any torsion.
Before installation: Perform a functional test, then close the fire damper Ä 141 .
The adhesive tape in the installation area must NOT be removed.
The product label must NOT be removed and must remain visible.
Protect the fire damper from humidity and condensation as they will damage the fire damper.
The construction variants with stainless steel or powder-coated casing and additionally with an impregnated damper blade meet more critical requirements for corrosion protection.
When installing the FKR-EU, the structural properties of the supporting construction (wall / ceiling) must be ensured by others, even in the event of a fire.
Unless stated otherwise in the respective installation details:
­ Each fire damper must be installed in a separate installation opening. The distance between two fire dampers is 200 mm.
­ The distance from load-bearing structural elements is 75 mm.
­ A maximum of two fire dampers must be installed in a single installation opening.
­ Fire dampers are allowed to be in mortar-based installation at a distance of 40 mm or 60 mm with installation kit TQ from steel beams, wooden beams or wooden ceilings with fire protection claddings. The fire-resistant cladding (panel material) must be manufactured in accordance with a national or European certificate and must lie against the supporting structure without cavities in the area of the fire damper.
If several fire dampers are used on the same duct, the following has to be ensured: If one damper closes, the maximum permitted upstream velocity for the other fire dampers that remain open must not be exceeded. This must be ensured by other, e.g., by switching off the fan or by mutual interlocking in the case of the construction with a spring return actuator.
As ducts may expand and walls may become deformed in the event of a fire, we recommend using flexible connectors for the following installation situations:
– Lightweight partition walls
– Lightweight shaft walls
– Fire batt systems

The flexible connectors should be installed in such a way that they absorb both tension and compression. Flexible ducts can be used as an alternative. Ducting must be installed in such a way that it does not impose any significant loads on the fire damper in the event of a fire. This can be achieved by a nonstraight duct, i.e. by bends or elbows, for example. Be sure to comply with the relevant national guidelines and regulations. The interior of the fire damper must be accessible for maintenance work and cleaning. Depending on the installation configuration it may be necessary to provide inspection panels in the connecting ducts. As an alternative to the inspection access, we recommend connecting the duct using flexible connectors (fastened with hose clamp) or sliding connectors. Load-bearing components Solid ceiling slabs and concrete beams, as well as load-bearing solid walls are called load- bearing components.
After installation
Clean the fire damper. Remove transport and installation protection or the
prop, if any. In case of mortar-based installation this protection must not be removed until the mortar has hardened. Test the function of the fire damper. Make electrical connections.
Connecting duct and extension piece
It is possible to insert screws near the spigot for fixing.
Equipotential bonding
Flange construction
The flange of the fire damper can be used for equipotential bonding; no holes must be drilled into the damper casing.
Spigot construction
The equipotential bonding is fixed, for example, with suitable clamps. Alternatively, it is allowable for drilled holes to be made near the spigot.
Thermal insulation
When using thermal insulation, especially for outside or exhaust air, fully bonded panel insulation materials made of elastomeric foams (synthetic rubber) can be used (e.g. Armaflex Ultima from Armacell). Be sure to comply with the relevant national guidelines and regulations for combustible building materials and smoke formation classes.

Fire damper FKR-EU

27

Installation
General installation information

Insulation is non-hazardous in terms of fire safety if the following requirements are met:
the insulation does not impair the function of the fire damper,
The fire damper remains accessible. The inspection accesses and product sticker remain
accessible. The insulation does not penetrate walls or ceilings.

Extension pieces
To ensure that the fire damper can be connected to the ductwork after installation even if the wall or ceiling is fairly thick, you should extend the fire damper with a suitable extension piece (attachment or extension by others) on the installation side Ä Chapter 6 `Accessories’ on page 137 .
Installation positions
The fire damper may be installed so that the damper blade shaft is horizontal or vertical or in all intermediate positions (0 ­ 360°).

Fig. 11: Thermal insulation
1 FKR-EU 2.1 Mortar 3.1 Solid wall 6.16 Insulation (elastomeric foam, flame- resistant, non-
dripping), around the perimeter, actuator and release mechanism, inspection accesses and product sticker must be accessible 9.2 Extension piece or duct Up to EI 120 S
Note: The installation situation shown is representative of all supporting constructions.
The following applies to Germany: In Germany, only insulation materials with a fire behaviour of at least C – s2, d0, may be used according to the specifications of the MVV TB (since 2019/1). This requirement is met by Armaflex Ultima insulation material from Armacell, for example. The applicable local building regulations must be observed. For notes on the use of elastomeric foams, see Ä 7 .

Fig. 12: Installation positions and distances
a Distance between two fire dampers; see Ä 26 . The distance also depends on the installation situation and is given in the installation details.
If a duct smoke detector is installed in the connected duct, it must be positioned at the top, regardless of the installation position. Deviating arrangements are possible, provided that the specifications of the general building inspectorate licence of the duct smoke detector are observed.

For installation in the UK please note:
The final connection between the fire damper and the HVAC ductwork should include a break-away joint, which will allow collapse of the ductwork during a fire without disturbing the integrity of the fire damper.

Breakaway or flexible joints (e.g. flexible connectors) should incorporate materials, fixings, clamps, etc, that are manufactured from a non-fire resistant material with a low melting point such as aluminium, plastic, etc.

Fig. 13: Any installation position (0 ­ 360°), duct smoke detector always at top 1 Keep clear to provide access for operation

28

Fire damper FKR-EU

Distances

Installation
General installation information

Fig. 14: Overview of distances
x Distance to load-bearing components (solid walls and ceiling slabs, concrete beams as well as steel girders, wooden beams and solid wood ceilings with fire-rated cladding)
s2 Distance between the fire dampers * Mixed installation with fire damper type FK2-EU

Distances (unless otherwise specified in the respective installation details)

Installation type

x [mm]

Mortar-based installation

40 ­ 225

Dry mortarless installation with installation kit TQ 1, 2

100 / 60 3

Dry mortarless installation with fire batt

40 ­ 600

1 See “Installation openings” table under the respective installation details 2 Installation into separate installation openings 3 With shortened cover plate 4 Separate installation opening 5 80 ­ 225 mm and/or 80 ­ 600 mm with flange construction

s2 [mm] 40 ­ 225 5
200 4
40 ­ 600 5

The perimeter gap is 225 mm with mortar-based installation and 40 ­ 600 mm with fire batt.

Fire damper FKR-EU

29

Installation
General installation information

Installation orientations (see installation details for fire resistance properties)

Supporting construction

Mortar-based installation

Solid wall

A ­ F

Gypsum wall boards

E, F

Lightweight partition walls / compartment walls with metal support structure

A ­ F

Timber stud wall or half-timbered construction

A ­ F

Solid wood wall / cross-laminated timber wall

A, B, D ­ F

Shaft wall with metal support structure

C, E, F

Shaft wall without metal support structure

E, F

Solid ceiling slab

A ­ F

Hollow chamber ceiling, hollow stone ceiling,

E, F

composite ceiling, ribbed ceiling

In combination with lightweight ceiling (Cadolto system)

A, B, D ­ F

In / in combination with solid wood ceiling

E / A, B, D ­ F

In / in combination with wooden beam ceiling E / A, B, D ­ F

Historical wooden beam ceilings

E

Installation type Dry mortarless
installation E, F E, F E, F
E / ­ E / ­

Fire batt installation A, B, D ­ F
A, B, D ­ F A, B, D ­ F A, B, D ­ F

30

Fire damper FKR-EU

Installation
General installation information

Perimeter gap “s1” With mortar-based installation the perimeter gap
“s1” must not exceed 225 mm (wall and ceiling). The perimeter gap »s« must be large enough so that mortar can be filled in even in case of thicker walls or ceilings. Be sure to close larger wall openings or holes beforehand and in a suitable way, i.e. depending on the type of wall. When there are larger openings in the solid ceiling slabs, the dampers must be encased in concrete when the ceiling section is created. The gap must be large enough so that mortar can be filled in. We recommend a gap of at least 20 mm (note the constructively required minimum installation opening size, e.g., for the flange construction). Reinforcement should meet structural requirements.
Fig. 15: Perimeter gap 1 FKR-EU 2.1 Mortar s1 Perimeter gap Maximum gap widths are based on EN 15882-2. Larger gaps do not have an adverse effect with regard to fire protection and are in our opinion not critical.

Mortar-based installation
Cover all openings and control elements of the fire damper (e.g. with plastic) to protect them from contamination.
If the wall thickness is >115 mm , extend the fire damper on the installation side with an extension piece or a spiral duct.
Push the fire dampers into the installation opening in a centred manner and secure them. The distance from the operating side to the wall/ceiling slab is 370 mm for the spigot construction and 342 mm for the flange construction. Connect extension piece or duct if required.
In case of mortar-based installation, the open spaces between the fire damper casing and the wall or ceiling slab must be closed off with mortar. Entrapped air is to be avoided. The mortar bed depth should be equal to the thickness of the wall but must be at least 100 mm.
If you install the fire damper as the solid wall or ceiling slab is being completed, perimeter gap »s1« is not required. The open spaces between the fire damper and the wall must be closed off with mortar; for installation into solid ceiling slabs, concrete can be used. Reinforcements should meet structural requirements.
The mortar bed depth should be equal to the thickness of the wall. If trim panels with appropriate fire resistance are used, a mortar bed depth of 100 mm suffices.
Mortar
DIN 1053: Groups II, IIa, III, IIIa; fire protection mortar of groups II, III
EN 998-2: Classes M 2.5 to M 20 or fire protection mortar of classes M 2.5 to M 20
Equivalent mortars that meet the requirements of the above standards, gypsum mortar or concrete
Mineral wool as filling material
Unless otherwise stated in the installation details, mineral wool with a gross density of 80 kg/m³ and a melting point of 1000 °C must be used.

Fire damper FKR-EU

31

Installation
General installation information

Installation with installation kit
For installation without a mortar-mix, the installation kit TQ can be used (only FKR-EU in spigot construction).
The installation kit is assembled on the fire damper at the factory. Fixing to the wall / ceiling slab is carried out according to the respective installation details.
The installation is carried out centred in the installation opening.
For installation near the floor or ceiling, professionally shorten the cover plate of the installation kit on one side.
Fixing to the wall / ceiling slab is carried out according to the respective installation details.

Installation with fire batt
The distance from the operating side flange to the wall or ceiling has to be 370 mm for the spigot construction and Flange construction 342 mm.
Fire batt systems consist of two layers of mineral wool slabs, gross density 140 kg/m³.
Apply fire-resistant sealant to the cut faces of the mineral wool slabs and fit them tightly into the installation opening. Seal any gaps between the mineral wool slabs and the installation opening, gaps between the cut faces of cut-to-size pieces, and gaps between slabs and the fire damper by applying fire-resistant sealant or coating. Use only sealant or coating that is suitable for the fire batt system.
Apply ablative coating to the mineral wool slabs, joints, transitions and any imperfections on the coated mineral wool slabs; coating thickness 2.5 mm.
Fix fire dampers on both sides of the wall, see Ä 136 .
If the wall/ceiling is fairly thick, you must use additional layers of mineral wool slabs on side A.
Fire batt systems are not suitable for use below flexible ceiling joints.

Fig. 16: Fire-resistant sealant
1 FKR-EU 2.4 Coated board system 8.21 Firestop sealant

32

Fire damper FKR-EU

Installation
General installation information

Fire batt systems
The following fire batt systems are acceptable (fire batt systems have to be provided by others). As for mineral wool slabs, all slabs that are part of the system and have been approved by the manufacturer may be used.
Promat®
Ablative coating Promastop®-CC Ablative coating Promastop®-I Ablative coating Intumex-CSP Ablative coating Intumex-AC
Hilti
Ablative coating CFS-CT Ablative coating CP 673 Fire-resistant sealant CFS-S ACR
HENSEL
Ablative coating HENSOMASTIK® 5 KS Farbe Fire-resistant sealant
HENSOMASTIK® 5 KS Spachtel
SVT
Ablative coating PYRO-SAFE FLAMMOTECT-A Farbe
Fire-resistant sealant PYRO-SAFE FLAMMOTECT-A Spachtel
OBO Bettermann
Ablative coating PYROCOAT® ASX Farbe Fire-resistant sealant PYROCOAT® ASX Spachtel
Würth
Ablative coating Würth Ablationsbeschichtung I (‘Ablation coating I’)
AGI
Ablative coating PYRO-SAFE Flammotect Combi S90
Fire-resistant sealant AGI Flammotect COMBI S90

Dimensions and distances for fire batt systems for wall installation

Fig. 17: Fire batt ­ installation in solid walls and ceiling slabs, lightweight partition, timber stud wall, half-timbered construction and solid wood walls E Installation area

Coated board system
Promat® Hilti Hensel SVT OBO Bettermann Würth AGI

B max. [mm] 3750 3000

H max. [mm] 1840 2115

1900

1400

Damper combination up to EI 90 S FKR-EU

s1 min. [mm] 40

s1 max. [mm] 600

Requirements for wall and ceiling systems
FKR-EU fire dampers must be installed in wall and ceiling systems if these walls and ceiling slabs have been erected in compliance with the relevant regulations and according to the manufacturers’ instructions, and if the information on the respective installation situation applies and the following requirements are met.
Provide any installation openings according to the installation details in this manual.

Fire damper FKR-EU

33

Installation
General installation information

Solid walls
Solid walls or compartment walls made of, for example, concrete, aerated concrete, masonry, or solid gypsum wallboards according to EN 12859 (without open spaces), gross density 350 kg/m³.
Wall thickness W 100 mm, solid gypsum wallboards W 80 mm.
Provide each installation opening and core drilled holes according to the local and structural conditions and with regard to the dimensions of the fire damper.

Distance between different TROX fire dampers in mortar-based installation in solid walls (one installation opening)

Item no. 1 2 3 3

Damper combination up to EI 90 S FKR-EU / FKR-EU FKR-EU ­ FK2-EU FKR-EU ­ FK- EU FKR-EU ­ FKRS-EU

Fig. 18: Distance from the FKR-EU to other TROX fire dampers in mortar-based installation * For flange construction

Lightweight partition walls with metal support structure
Lightweight partition walls, safety partition walls or walls to provide radiation protection, with metal support structure or steel support structure (box sections), with European classification to EN 13501-2 or equivalent national classification.
Cladding on both sides made of gypsum bonded or cement bonded panel materials, fibre-reinforced gypsum or fire-rated calcium silicate boards.
Wall thickness W 94 mm, for compartment walls or safety partition walls W 100 mm.
Distance between metal support structures 625 mm; distance between metal support structures in compartment walls 312.5 mm.
Compartment walls and safety partition walls may be provided with sheet steel inserts and may require less space between the metal studs.
Create an installation opening with trimmers (studs and noggings).
If necessary, provide trim panels and screw-fix them to the support structure
Additional layers of cladding (if stated in the usability certificate for the wall) or double stud constructions are approved.
Connect the metal sections near the installation opening according to the installation details in this manual.
If reinforcing boards are required, they must be screwed to the metal support structure at intervals of approx. 100 mm.
Installation only permitted in non-load-bearing walls (load-bearing wall constructions on request).
The structural properties of the wall must be ensured by others and any necessary compensation measures, especially with large installation openings, must be checked and taken into account by others.

34

Fire damper FKR-EU

Installation
General installation information

Lightweight partition walls with timber support structure / half-timbered construction
Lightweight partition walls, either timber stud walls or half-timbered constructions, with European classification to EN 13501-2 or equivalent national classification.
Cladding on both sides made of gypsum bonded or cement bonded panel materials, fibre-reinforced gypsum or fire-rated calcium silicate boards.
Wall thickness W 130 mm (W 110 for F60, W 105 for F30); wall thickness of half-timbered constructions W 140 mm (W 110 for F30).
Erect the timber stud wall or half-timbered construction according to the manufacturer’s instructions.
Additional layers of cladding (if stated in the usability certificate for the wall) or double stud constructions are approved.
Create an opening in the timber support structure with studs and trimmers.
Trim panels and reinforcing boards have to be made of cladding material and have to be fixed to the frame at a distance of about 100 mm.
The structural properties of the wall must be ensured by others and any necessary compensation measures, especially with large installation openings, must be checked and taken into account by others.
Solid wood walls
Fire-resistant solid wood walls or cross laminated timber walls with European or national certificate.
Wall thickness W 95 mm (with reinforcing board W 100 mm near the installation opening).
If required, additional gypsum bonded or cement bonded panel materials or fibre-reinforced gypsum board are permitted.

Shaft walls with metal support structure
Shaft walls or additional leaves with metal support structure or steel support structure (box sections), with European classification to EN 13501-2 or equivalent national classification.
Cladding on one side made of gypsum bonded or cement bonded panel materials, fibre-reinforced gypsum or fire-rated calcium silicate boards.
Wall thickness W 90 mm (W 75 for F30); cladding / reinforcing boards according to installation details.
625 mm distance between metal studs. Be sure to follow the manufacturers’ instructions for
the height, width and thickness of walls. Create an installation opening with trimmers (studs
and noggings). If necessary, provide trim panels and screw-fix them
to the support structure Installation is carried out with the actuator on the
outside of the shaft. If reinforcing boards are required, they must be
screwed to the metal support structure at intervals of approx. 100 mm. The structural properties of the wall must be ensured by others and any necessary compensation measures, especially with large installation openings, must be checked and taken into account by others.
Shaft walls without metal support structure
Shaft walls without metal support structure, with European classification according to EN 13501-2 or equivalent national classification.
Cladding on one side made of gypsum bonded or cement bonded panel materials, fibre-reinforced gypsum or fire-rated calcium silicate boards.
Shaft wall between two solid walls, without corner formation
Wall thickness W 50 mm. If reinforcing boards are required, they must be
screwed on at intervals of approx. 100 mm.

Fire damper FKR-EU

35

Installation
General installation information
Solid ceiling slabs
Solid ceiling slabs without open spaces, made of concrete or aerated concrete, gross density 450 kg/m³.
Ceiling thickness D 100 mm, thickness increased to D 150 mm.
Partial solid ceiling slab thickness 150 mm as combination with fire-resistant wooden beam ceilings (gluelam also), solid wood ceilings and lightweight ceilings (Cadolto module ceiling system only).
Provide each installation opening and core drilled holes according to the local and structural conditions and with regard to the dimensions of the fire damper.
Other ceiling types: ­ Hollow stone ceilings, D 150 mm ­ Hollow chamber ceilings, D 150 mm ­ Ribbed ceilings, thickness increased to D 150 mm ­ Composite ceilings, D 150 mm
The structural properties of the ceiling and the connection of the mortar/concrete grout to the ceiling or any necessary reinforcement must be checked and taken into account by others.
Solid wood ceilings
Solid wood or cross-laminated timber ceilings. Ceiling thickness D 140 mm or D 112.5 mm with
supplementary fire-resistant cladding.
Wooden beam ceilings
Wooden beam or gluelam construction. Ceiling thickness D 142.5 mm (ceiling- dependent)
with supplementary fire-resistant cladding. Historical wooden beam ceilings F30.

36

Fire damper FKR-EU

Installation
Installation kits > Installation kit TQ for dry mortarless install…
5.4 Installation kits 5.4.1 Installation kit TQ for dry mortarless installation
The installation kit TQ is an integral component of the fire damper and must be ordered together with the damper.
Fig. 19: Supply package and installation of installation kit TQ for dry mortarless installation 1 FKR-EU in spigot construction 2.11 Installation kit TQ with cover plate and intumescent seal

Fire damper FKR-EU

37

Installation
Solid walls > General
5.5 Solid walls 5.5.1 General

Fig. 20: Solid walls ­ arrangement / distances, side by side arrangement also applies to arrangement under one another

1 FKR-EU 3.1 Solid wall s1 Perimeter gap

s2 Distance between the fire dampers Spigot construction 40 ­ 225 mm Flange construction 80 ­ 225 mm

Installation type
Mortar-based installation Dry mortarless installation with fire batt 1

  1. Observe maximum permitted size of the fire batt! 2) Flange construction 80 ­ 225 mm or 80 ­ 600 mm

Installation opening [mm] Ænominal width + max. 450 mm
Ænominal width + max. 1200 mm

Distance [mm]

s1

s2

225

40 ­ 225 2

40 ­ 600

40 ­ 600 2

Additional requirements: solid walls
Solid wall Ä on page 34 Distances and installation orientations, Ä
tances’ on page 29

`Dis-

38

Fire damper FKR-EU

5.5.2 Mortar-based installation
Mortar-based installation into a solid wall

Installation
Solid walls > Mortar-based installation

Fig. 21: Mortar-based installation into a solid wall
1 FKR-EU 2.1 Mortar 3.1 Solid wall 4.1 Solid ceiling slab / solid floor

Z

Spigot construction 370 mm

Flange construction 342 mm

Installation near the floor analogous to

Up to EI 120 S

Mortar-based installation in solid wall, “flange to flange”

Fig. 22: Mortar-based installation into a solid wall, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other)

1 FKR-EU 2.1 Mortar 3.1 Solid wall Z Spigot construction 370 mm

Flange construction 342 mm s2 Spigot construction 40 ­ 225 mm
Flange construction 80 ­ 225 mm Up to EI 120

Fire damper FKR-EU

39

Installation
Solid walls > Mortar-based installation
Mortar-based installation into a solid wall made of gypsum wall boards

Fig. 23: Mortar-based installation into a solid wall made of gypsum wall boards

1

FKR-EU

Z

2.1 Mortar

3.14 Solid wall made of gypsum ball boards EN 12859 *

(formerly DIN 18163)

4.1 Solid ceiling slab

Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to Up to EI 90 S

40

Fire damper FKR-EU

Installation
Solid walls > Mortar-based installation
Mortar-based installation into a solid wall, FKR-EU and FK2-EU combined

Fig. 24: Mortar-based installation into a solid wall, FKR-EU and FK2-EU combined

1a FKR-EU 1b FK2-EU up to B × H 800 × 400 mm 2.1 Mortar 3.1 Solid wall Z Spigot construction 370 mm

Flange construction 342 mm s2 Spigot construction 40 ­ 225 mm
Flange construction 80 ­ 225 mm Up to EI 90 S

Note on combined installation:

Total fire damper surface area 1.2 m².
The number of fire dampers in an installation opening is limited by their size (B × H for FK2-EU and /or Æ nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²).
Alternative installation orientations of side-by-side, under or on top of one another possible. Details are available upon request. For installation details FK2-EU, see the installation and operating manual for this fire damper type.
Distance to load-bearing structural elements 40 mm
Distance of FKR-EU to a FK-EU 75 ­ 225 mm (flange construction 80 ­ 225 mm)

Fire damper FKR-EU

41

Installation
Solid walls > Mortar-based installation
Mortar-based installation into a solid wall with flexible ceiling joint

Fig. 25: Mortar-based installation into a solid wall with flexible ceiling joint

1

FKR-EU

2.1 Mortar

3.1 Solid wall

4.1 Solid ceiling slab

6.15 Mineral wool, depending on the flexible ceiling

joint

Z Spigot construction 370 mm Flange construction 342 mm Up to EI 120 S

  • After subsidence of the ceiling slab

Note on flexible ceiling joint: representative illustration. The distance to the ceiling depends on the design of the flexible ceiling joint, the expected ceiling subsidence and the specifications of the wall manufacturer.

Additional requirements: mortar-based installation into solid walls Solid wall Ä on page 34

42

Fire damper FKR-EU

Installation
Solid walls > Mortar-based installation ­ multiple occupancy…
5.5.3 Mortar-based installation ­ multiple occupancy of an installation opening

Fig. 26: Mortar-based installation ­ multiple occupancy of an installation opening

1 FKR-EU 2.1 Mortar 2.2 Concrete 3.1 Solid wall (load-bearing component)

4.1 Solid ceiling slab (load-bearing component) s2 Spigot construction 40 ­ 225 mm
Flange construction 80 ­ 225 mm Up to EI 90 S

Fire damper FKR-EU

43

Installation
Solid walls > Mortar-based installation ­ multiple occupancy…

Fig. 27: Mortar-based installation ­ multiple occupancy of an installation opening

1 FKR-EU 2.1 Mortar 3.1 Solid wall Z Spigot construction 370 mm

Flange construction 342 mm s2 Spigot construction 40 ­ 225 mm
Flange construction 80 ­ 225 mm Up to EI 90 S

Additional requirements: mortar-based installation ­ multiple occupancy of an installation opening
Solid wall, Ä on page 34
Total fire damper area (Æ nominal width) 4.8 m2 The number of fire dampers in an installation
opening is limited by their damper size (Æ nominal width) and the overall area of the fire dampers (4.8 m2). The dampers can be arranged in one or two rows. Distance to load-bearing structural elements 40 mm

If the actuators are located between the fire dampers, sufficient free space for inspection must be provided.
The mortar bed width is not allowed to exceed 225 mm, provide brick partition or lintel if necessary.

44

Fire damper FKR-EU

Installation
Solid walls > Dry mortarless installation with fire batt
5.5.4 Dry mortarless installation with fire batt
Dry mortarless installation with fire batt into a solid wall

Fig. 28: Dry mortarless installation with fire batt into a solid wall

1 FKR-EU

Z

2.4 Coated board system

3.1 Solid wall

4.1 Solid ceiling slab

Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to Up to EI 60 S

Dry mortarless installation with fire batt in solid wall, “flange to flange”

Fig. 29: Dry mortarless installation into a solid wall, with a fire batt, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other)

1 FKR-EU 2.4 Coated board system 3.1 Solid wall 4.1 Solid ceiling slab Z Spigot construction 370 mm

Flange construction 342 mm

s2

Spigot construction 40 ­ 600 mm

Flange construction 80 ­ 600 mm

Installation near the floor analogous to

Up to EI 60 S

Fire damper FKR-EU

45

Installation
Solid walls > Dry mortarless installation with fire batt
Additional requirements: dry mortarless installation with fire batt in solid walls Solid wall Ä on page 34 Fire batt systems, installation details, distances /
dimensions Ä on page 32 Suspension and fixing Ä Chapter 5.14 `Fixing the
fire damper’ on page 135

46

Fire damper FKR-EU

Installation
Lightweight partition walls > General
5.6 Lightweight partition walls 5.6.1 General
Lightweight partition wall with metal support structure and cladding on both sides

Fig. 30: Lightweight partition wall with metal support structure and cladding on both sides, caption Ä Fig. 33

Fire damper FKR-EU

47

Installation
Lightweight partition walls > General
Lightweight partition wall “flange to flange”

Fig. 31: Lightweight partition wall with metal support structure and cladding on both sides, flange to flange, Æ nominal width 315 ­ 400, caption Ä Fig. 33 For details see Fig. 30

48

Fire damper FKR-EU

Installation
Lightweight partition walls > General

Fig. 32: Lightweight partition wall with metal support structure and cladding on both sides, flange to flange, Æ nominal width 450 ­ 800, caption Ä Fig. 33 For details see Fig. 30

Fire damper FKR-EU

49

Installation
Lightweight partition walls > General
Compartment wall

Fig. 33: Compartment wall with metal support structure and cladding on both sides

50

Fire damper FKR-EU

Installation
Lightweight partition walls > General

A

Lightweight partition wall with metal support

structure or steel support structure / compart-

ment wall / safety partition wall

B

Lightweight partition wall with metal support

structure or steel support structure / compart-

ment wall / safety partition wall, installation near

the floor

C

Lightweight partition wall with metal support

structure or steel support structure / compart-

ment wall / safety partition wall, installation near

the ceiling

4.1 Solid ceiling slab / solid floor

5.1 Dry wall screw

5.6 Screw or steel rivet

6.5 Mineral wool (depending on wall construction)

7.1 UW section

7.1a UW section, cut in and bent or cut off

7.1b
7.2 7.3 7.10 7.13 7.23
A A1

UW section, only for mortar-based installation, nominal sizes Æ nominal width 450 – 800 CW section UA section Trim panels according to installation details Cladding Sheet steel layer depending on wall manufacturer (if any) Installation opening Opening in the metal support structure (without trim panels: A =A1) Closed side of metal section must face the installation opening

Fire damper FKR-EU

51

Installation
Lightweight partition walls > General

Fig. 34: Metal support structure of compartment wall, single and double stud system

5.1 Dry wall screw 5.2 Hexagon head screw M6 5.5 Carriage bolt, L 50 mm, with washer and nut 5.6 Steel rivet 5.14 Angle bracket

7.1 UW section 7.2 CW section 7.3 UA section * Installation opening according to installation
details

52

Fire damper FKR-EU

Installation
Lightweight partition walls > General

Installation opening A [mm]

Installation type

Nominal size Ænominal width

Mortar-based installation 1

315 355 400 450 500 560 630 710 800 A = Ænominal width + max. 450 mm A1 = A + (2 × trim panels)

Dry mortarless installation with installa- 435 475 520 570 620 680 750 830 920 tion kit TQ 1, 2, 3

Dry mortarless installation with fire batt 4

A = Ænominal width + 80 ­ 1200 mm A1 = A + (2 × trim panels / 4 × trim panels)

  1. Optional trim panels (max. 25 mm) 2) Installation opening tolerance ± 2 mm
  2. Installation kit TQ is available only for FKR-EU with spigot 4) Trim panels according to installation details required

Additional requirements: lightweight partition walls and compartment walls with metal support structure
Lightweight partition wall or compartment wall, Ä on page 34
Erecting a wall and creating an installation opening
Erect the lightweight partition wall according to the manufacturer’s instructions and create an installation opening
­ Variant 1: Provide the installation opening in the metal support structure with suitable metal sections, then clad the wall.
­ Variant 2: After cladding the wall, create a square wall opening (clear installation opening 475 mm) between the regular studs and brace it with a perimeter metal section. Screw metal sections onto both sides over the cladding, spaced approx. 100 mm apart.
­ In case of mortar-based installation of fire dampers from nominal size Æ450, install four additional sections 7.1b at an angle of 45° in order to reinforce the metal support structure.

Fire damper FKR-EU

53

Installation
Lightweight partition walls > Mortar-based installation
5.6.2 Mortar-based installation
Mortar-based installation into a lightweight partition wall, compartment wall or safety partition wall

Fig. 35: Mortar-based installation into a lightweight partition wall, compartment wall or safety partition wall

1

FKR-EU

7.13

2.1 Mortar

7.23

3.2 Lightweight partition wall with metal support

structure, cladding on both sides

9.2

3.6 Compartment wall or safety wall with metal sup- Z

port structure, cladding on both sides

4.1 Solid ceiling slab

6.5 Mineral wool (depending on wall construction)

6.11 Insulating strip (depending on wall construction)

­

7.5 Steel support structure (box section)

Cladding Sheet steel insert depending on wall manufacturer Extension piece or duct Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to optional Up to EI 90 S

54

Fire damper FKR-EU

Installation
Lightweight partition walls > Mortar-based installation
7.10 Trim panels (screw-fixed to metal support structure)
Mortar-based installation into a lightweight partition wall

Fig. 36: Mortar-based installation into a lightweight partition wall

1

FKR-EU

7.14

2.1 Mortar

3.2 Lightweight partition wall with metal support

9.2

structure, cladding on both sides

Z

3.6 Compartment wall or safety wall with metal sup-

port structure, cladding on both sides

6.5 Mineral wool (depending on wall construction)

6.11 Insulating strip (depending on wall construction)

­

7.10 Trim panels (screw-fixed to metal support struc-

ture)

7.13 Cladding

Reinforcing board of the same material as the wall Extension piece or duct Spigot construction 370 mm Flange construction 342 mm optional Up to EI 60 S EI 30 S

Fire damper FKR-EU

55

Installation
Lightweight partition walls > Mortar-based installation
Mortar-based installation in lightweight partition wall, “flange to flange

Fig. 37: Mortar-based installation into a lightweight partition wall, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other)

1

FKR-EU

2.1 Mortar

3.2 Lightweight partition wall with metal support

structure or steel support structure, cladding on

both sides

3.6 Compartment wall or safety wall with metal sup-

port structure, cladding on both sides

6.5 Mineral wool (depending on wall construction)

7.10 Trim panels

7.13 Cladding

7.14 Reinforcing board of the same material as the

wall

Z Spigot construction 370 mm Flange construction 342 mm
s2 Spigot construction 40 ­ 225 mm Flange construction 80 ­ 225 mm

Depending on the wall structure Up to EI 90 S Up to EI 60 S EI 30 S

56

Fire damper FKR-EU

Installation
Lightweight partition walls > Mortar-based installation
Mortar-based installation into a lightweight partition wall, FKR-EU and FK2-EU combined

Fig. 38: Mortar-based installation into a lightweight partition wall, FKR-EU and FK2-EU combined

1a FKR-EU

Z Spigot construction 370 mm

1b FK2-EU up to B × H 800 × 400 mm

Flange construction 342 mm

2.1 Mortar

s2 Spigot construction 40 ­ 225 mm

3.2 Lightweight partition wall with metal support struc-

Flange construction 80 ­ 225 mm

ture or steel support structure, cladding on both

Up to EI 90 S

sides

3.6 Compartment wall or safety wall with metal sup-

port structure, cladding on both sides

Note on combined installation:
Total fire damper surface area 1.2 m². The number of fire dampers in an installation opening is limited by their size (B × H for FK2-EU and /or
Æ nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²). Alternative installation orientations of side-by-side, under or on top of one another possible. Details are available
upon request. For installation details FK2-EU, see the installation and operating manual for this fire damper type. Distance to load-bearing structural elements 40 mm

Fire damper FKR-EU

57

Installation
Lightweight partition walls > Mortar-based installation
Frame construction, size-dependent, Ä Chapter 5.6.1 `General’ on page 47 Distance of FKR-EU to a FK-EU 75 ­ 225 mm (flange construction 80 ­ 225 mm)
Mortar-based installation into a lightweight partition wall, below a flexible ceiling joint

Fig. 39: Mortar-based installation into a lightweight partition wall, below a flexible ceiling joint

1

FKR-EU

2.1 Mortar

3.2 Lightweight partition wall with metal support

structure, cladding on both sides

3.6 Compartment wall or safety wall with metal sup-

port structure, cladding on both sides

4.1 Solid ceiling slab

5.1 Dry wall screw

6.5 Mineral wool (depending on wall construction)

6.13 Mineral wool strips, filler as an alternative (if

required to even out an uneven wall)

7.1 UW section

7.10 Trim panels

7.21 Ceiling joint strips (e.g. 4 × 10 mm)

Z

Spigot construction 370 mm

Flange construction 342 mm

Depending on the wall structure

Up to EI 90 S

Note: representative illustration. The distance to the ceiling depends on the design of the flexible ceiling joint, the expected ceiling subsidence and the specifications of the wall manufacturer.

Additional requirements: mortar-based installation into lightweight partition and compartment walls Lightweight partition wall or compartment wall,
Ä on page 34

58

Fire damper FKR-EU

Installation
Lightweight partition walls > Mortar-based installation ­ multiple occupancy…
5.6.3 Mortar-based installation ­ multiple occupancy of an installation opening

Fig. 40: Mortar-based installation ­ multiple occupancy of an installation opening

1 FKR-EU 2.1 Mortar 2.2 Concrete

3.1 Solid wall (load-bearing component) 4.1 Solid ceiling slab (load-bearing component)
Up to EI 90 S

Fire damper FKR-EU

59

Installation
Lightweight partition walls > Mortar-based installation ­ multiple occupancy…

Fig. 41: Mortar-based installation ­ multiple occupancy of an installation opening

1

FKR-EU

2.1 Mortar

3.2 Lightweight partition wall with metal support

structure, cladding on both sides

3.6 Compartment wall or safety wall with metal sup-

port structure, cladding on both sides

6.5 Mineral wool (depending on wall construction)

7.10 Trim panels

Z Spigot construction 370 mm Flange construction 342 mm
s2 Spigot construction 40 ­ 225 mm Flange construction 80 ­ 225 mm

Depending on the wall structure Up to EI 90 S

60

Fire damper FKR-EU

Installation
Lightweight partition walls > Mortar-based installation ­ multiple occupancy…
Additional requirements: mortar-based installation ­ multiple occupancy of an installation opening
Lightweight partition wall or compartment wall, Ä on page 34
Total fire damper area (Æ nominal width) 4.8 m2 The number of fire dampers in an installation
opening is limited by their damper size (Æ nominal width) and the overall area of the fire dampers (4.8 m2). The dampers can be arranged in one or two rows. Distance to load-bearing structural elements 40 mm If the actuators are located between the fire dampers, sufficient free space for inspection must be provided. The mortar bed width is not allowed to exceed 225 mm, provide separate trimmers if necessary.

Fire damper FKR-EU

61

Installation
Lightweight partition walls > Dry mortarless installation with installation …
5.6.4 Dry mortarless installation with installation kit TQ
Dry mortarless installation into a lightweight partition wall, with installation kit TQ

Fig. 42: Dry mortarless installation into a lightweight partition wall, with installation kit TQ

1

FKR-EU

7.10

2.11 Installation kit TQ (factory assembled)

7.11

3.2 Lightweight partition wall with metal support

structure, cladding on both sides

7.13

3.6 Compartment wall or safety wall with metal sup- 7.14

port structure, cladding on both sides

4.1 Solid ceiling slab

9.2

6.2 Mineral wool, 1000 °C, 80 kg/m³

6.5 Mineral wool (depending on wall construction)

­

6.13 Mineral wool strips A1, 5 mm thick, 1000°C,

filler as an alternative

Trim panels Trim panels, fire-resistant, 2-ply, max. 25 mm (alternative to 6.2 and 7.14) Cladding Reinforcing board, made of wall panels (up to the fire damper casing) Extension piece or duct Cover plate, shortened by others Up to EI 90 S

Note: ­ valid for all wall constructions and wall thicknesses. and valid for all wall thicknesses with a single stud frame.

62

Fire damper FKR-EU

Installation
Lightweight partition walls > Dry mortarless installation with installation …

Fig. 43: Dry mortarless installation into a lightweight partition wall, with installation kit TQ

1

FKR-EU

2.11 Installation kit TQ (factory assembled)

3.2 Lightweight partition wall with metal support

structure, cladding on both sides

7.13

Cladding

7.14

Reinforcing board made of wall panels (rein-

forcing board or alternatively wall cladding on

the back, up to the fire damper casing)

Fire damper FKR-EU

63

Installation
Lightweight partition walls > Dry mortarless installation with installation …

3.6 Compartment wall or safety wall with metal sup- 7.23

port structure, cladding on both sides

6.2 Mineral wool, 1000 °C, 80 kg/m³

9.2

6.5 Mineral wool (depending on wall construction)

Z

6.11 Insulating strip (depending on wall construction)

7.1 UW section

7.3 UA section

7.5 Steel support structure

7.10 Trim panels *

­

7.11 Trim panels, fire-resistant, 2-ply, max. 25 mm

(alternative to 6.2 and 7.14)

­

Sheet steel insert depending on wall manufacturer Extension piece or duct Spigot construction 370 mm Flange construction 342 mm The total thickness of the trim panels must not exceed 25 mm optional Up to EI 90 S
Up to EI 60S EI 30 S

Dry mortarless installation into a lightweight partition wall, below a flexible ceiling joint with installation kit TQ

Fig. 44: Dry mortarless installation into a lightweight partition wall, below a flexible ceiling joint with installation kit TQ

1

FKR-EU

2.11 Installation kit TQ (factory assembled)

3.2 Lightweight partition wall with metal support

structure, cladding on both sides

3.6 Compartment wall or safety wall with metal sup-

port structure, cladding on both sides

4.1 Solid ceiling slab

5.1 Dry wall screw

6.5 Mineral wool (depending on wall construction)

6.13 Mineral wool strips A1, 5 mm thick, 1000°C,

filler as an alternative

7.1 UW section

7.10 Trim panels

7.13 Cladding

7.21 Ceiling joint strips (e.g. 4 × 10 mm)

Z

Spigot construction 370 mm

Flange construction 342 mm

Depending on the wall structure

Up to EI 90 S

Note: representative illustration. The distance to the ceiling depends on the design of the flexible ceiling joint, the expected ceiling subsidence and the specifications of the wall manufacturer.

Additional requirements: dry mortarless installation with installation kit TQ in lightweight partition walls Lightweight partition wall or compartment wall,
Ä on page 34 Installation kit TQ, Ä on page 32

200 mm distance between two fire dampers in separate installation openings
Fasten the cover plate with 4 (for nominal widths up to 400 mm) or 12 (for nominal widths from 450 mm) dry wall screws Æ 4.2 mm to the metal support structure

64

Fire damper FKR-EU

Installation
Lightweight partition walls > Dry mortarless installation without installati…
5.6.5 Dry mortarless installation without installation kit

Fig. 45: Dry mortarless installation into a lightweight partition wall, without installation kit

1

FKR-EU

7.13

Cladding

2.19 Joint filler (ready-to-use putty or equivalent)

­

Up to EI 60 S

3.2 Lightweight partition wall with metal support

B

Operating side

structure, cladding on both sides

6.5 Mineral wool (depending on wall construction)

Additional requirements: dry mortarless installation into lightweight partition walls without installation kit
Lightweight partition wall, Ä on page 34 200 mm distance between two fire dampers 75 mm distance from fire damper to load-bearing
structural elements
1. Create a circular installation opening with nominal width +20 mm.
2. Chamfer the outer layer of the cladding all round on both sides and completely close off the surrounding gap on both sides with joint filler to the depth of the cladding.

Fire damper FKR-EU

65

Installation
Lightweight partition walls > Dry mortarless installation with fire batt
5.6.6 Dry mortarless installation with fire batt
Dry mortarless installation into a lightweight partition wall, with a fire batt

Fig. 46: Dry mortarless installation into a lightweight partition wall, with a fire batt

1

FKR-EU

7.13

2.4 Coated board system

7.14

3.2 Lightweight partition wall with metal support

structure, cladding on both sides

Z

3.6 Compartment wall or safety wall with metal sup-

port structure, cladding on both sides

4.1 Solid ceiling slab

­

6.5 Mineral wool (depending on wall construction)

7.10 Trim panels

7.11 Fire-resistant trim panels, double, in case of

W > 100 mm

Cladding Reinforcing board of the same material as the wall Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to Up to EI 60 S
EI 30 S

66

Fire damper FKR-EU

Installation
Lightweight partition walls > Dry mortarless installation with fire batt
Dry mortarless installation with fire batt, “flange to flange”

Fig. 47: Dry mortarless installation into a lightweight partition wall, with a fire batt, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other)

Fire damper FKR-EU

67

Installation
Lightweight partition walls > Dry mortarless installation with fire batt

1

FKR-EU

7.14

2.4 Coated board system

3.2 Lightweight partition wall with metal support

Z

structure, cladding on both sides

3.6 Compartment wall or safety wall with metal sup- s2

port structure, cladding on both sides

4.1 Solid ceiling slab

6.5 Mineral wool (depending on wall construction)

­

7.10 Trim panels

7.11 Fire-resistant trim panels, double, in case of

W > 100 mm

7.13 Cladding

Reinforcing board of the same material as the wall Spigot construction 370 mm Flange construction 342 mm Spigot construction 40 ­ 600 mm Flange construction 80 ­ 600 mm
Installation near the floor analogous to Up to EI 60 S
EI 30 S

68

Fire damper FKR-EU

Installation
Lightweight partition walls > Dry mortarless installation with fire batt
Approved combinations for thicker walls

Fig. 48: Dry mortarless installation into a lightweight partition wall, with a fire batt, approved combinations for thicker walls

2.4 Coated board system

7.10

3.2 Lightweight partition wall or compartment wall

with metal support structure or steel support

structure, cladding on both sides

­

3.6 Compartment wall or safety wall with metal sup-

­

port structure, cladding on both sides

4.1 Solid ceiling slab / solid floor

6.5 Mineral wool (depending on wall construction)

6.11 Insulating strip (depending on wall construction)

Trim panels (for W 100 mm, single-layer, from W > 100 mm and EI 60 S, double- layer) Installation near the floor analogous to EI 60 S EI 30 S EI 60 S EI 30 S to EI 60 S

Additional requirements: dry mortarless installation into lightweight partition walls, with fire batt
Lightweight partition wall, Ä on page 34 Fire batt systems, installation details, distances /
dimensions, Ä on page 32 Suspension and fixing, Ä Chapter 5.14 `Fixing the
fire damper’ on page 135

Fire damper FKR-EU

69

Installation
Lightweight partition walls with timber support … > General
5.7 Lightweight partition walls with timber support structure or half-timbered constructions
5.7.1 General
Lightweight partition wall with timber support structure and cladding on both sides

Fig. 49: Lightweight partition wall with timber support structure and cladding on both sides, illustration caption Fig. 51

70

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > General
Lightweight partition wall with timber support structure, “flange to flange”

Fig. 50: Lightweight partition wall with timber support structure and cladding on both sides, flange to flange, nominal sizes: Æ nominal width 315 ­ 400, caption Fig. 51 For details see Fig. 49

Fire damper FKR-EU

71

Installation
Lightweight partition walls with timber support … > General

Fig. 51: Lightweight partition wall with timber support structure and cladding on both sides, flange to flange, nominal sizes: Æ nominal width 450 ­ 800

A

Timber stud wall

B

Timber stud wall, installation near the floor

C

Timber stud wall, installation near the ceiling

4.1 Solid ceiling slab / solid floor

5.1 Dry wall screw

5.13 Wood screw or pin

6.5 Mineral wool (depending on wall construction)

7.7 7.7a
7.11 7.13 7.17
A A1

Timber stud, at least 60 × 80 mm Timber support structure, min. 60 × 80 mm, only for mortar-based installation, nominal sizes: Æ nominal width 450 ­ 800 Trim panels, double layer, staggered joints Cladding Trimmers, timber stud / nogging, at least 60 × 80 mm Clear installation opening Opening in the timber support structure, A1 = A + (4 × trim panels)

For details see Fig. 49

72

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > General
Lightweight partition wall, half-timbered construction with cladding on both sides

Fig. 52: Lightweight partition wall, half-timbered construction with cladding on both sides

5.1 Dry wall screw 6.8 Infill* 7.9 Timber structure 7.11 Trim panels, double layer, staggered joints

7.13 *
A A1

Cladding Cavities completely filled with mineral wool 50 kg/m³, bricks, aerated concrete, lightweight concrete, reinforced concrete or clay Clear installation opening Opening in the half-timbered construction, A1 = A + (4 × trim panels)

Additional requirements: lightweight partition walls with timber support structure / half-timbered construction Timber stud wall or half-timbered construction, Ä on page 35

Installation opening A [mm]

Installation type

Nominal size Ænominal width

Mortar-based installation

315 355 400 450 500 560 630 710 800 A = Ænominal width + max. 450 mm A1 = A + (4 × trim panels)

Dry mortarless installation with installa- 435 475 520 570 620 680 750 830 920 tion kit TQ1, 2

Dry mortarless installation with fire batt

A = Ænominal width + 80 ­ 1200 mm

  1. Installation opening tolerance ± 2 mm

  2. Installation kit TQ is available only for FKR-EU with spigot

Fire damper FKR-EU

73

Installation
Lightweight partition walls with timber support … > Mortar-based installation
5.7.2 Mortar-based installation
Timber studs

Fig. 53: Mortar-based installation into a lightweight partition wall with timber support structure

1 2.1 3.4
4.1 6.5 7.7
7.10 7.11
7.12 7.13 7.13a

FKR-EU Mortar Timber stud wall (also timber panel constructions), cladding on both sides Solid ceiling slab / solid floor Mineral wool (depending on wall construction) Timber support structure, min. 60 × 80 mm (min. 60 × 60 mm with F60) Trim panels (fire-resistant) Trim panels, double layer with staggered joints, fire-resistant Trim panels, wood sheet, at least 600 kg/³ Cladding Cladding, fire-resistant

7.13b 7.14
7.17
Z

Cladding, wood sheet, at least 600 kg/³ Reinforcing board of the same material as the wall Trimmers, timber support structure / nogging, at least 60 × 80 mm (min. 60 × 60 mm with F60) Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to Up to EI 90 S Up to EI 60 S EI 30 S
EI 30 to EI 90 S

74

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > Mortar-based installation
Timber support structure, “flange to flange”

Fig. 54: Mortar-based installation into a lightweight partition wall with timber support structure, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other)

1 2.1 3.4
6.5 7.7
7.11
7.13 7.13a 7.14

FKR-EU Mortar Timber stud wall (also timber panel constructions), cladding on both sides Mineral wool (depending on wall construction) Timber support structure / nogging, at least 60 × 80 mm (at least 60 × 60 mm with F60) Trim panels, double layer with staggered joints, fire-resistant Cladding Cladding, fire-resistant Reinforcing board of the same material as the wall

7.17 Trimmers, timber support structure / nogging,

at least 60 × 80 mm (min. 60 × 60 mm with F60)

Z

Spigot construction 370 mm

Flange construction 342 mm

s2 Spigot construction 40 ­ 225 mm

Flange construction 80 ­ 225 mm

Up to EI 90 S

Up to EI 60 S

EI 30 S

Fire damper FKR-EU

75

Installation
Lightweight partition walls with timber support … > Mortar-based installation
Timber support structure, combined, FKR-EU and FK2-EU

Fig. 55: Mortar-based installation into a lightweight partition wall with timber support structure, FK2-EU and FKR-EU combined

1a FKR-EU 1b FK2-EU up to B × H 800 × 400 mm 2.1 Mortar 3.4 Timber stud wall (also timber panel construc-
tions), cladding on both sides 6.5 Mineral wool (depending on wall construction) 7.7 Timber support structure / nogging,
at least 60 × 80 mm (at least 60 × 60 mm with F60)

7.17 Trimmers, timber support structure / nogging,

at least 60 × 80 mm (min. 60 × 60 mm with F60)

Z

Spigot construction 370 mm

Flange construction 342 mm

s2 Spigot construction 40 ­ 225 mm

Flange construction 80 ­ 225 mm

Up to EI 90 S

76

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > Mortar-based installation
7.11 Trim panels, double layer with staggered joints, fire-resistant
Note on combined installation: Total fire damper surface area 1.2 m². The number of fire dampers in an installation opening is limited by their size (B × H for FK2-EU and /or
Æ nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²). Alternative installation orientations of side-by-side, under or on top of one another possible. Details are available
upon request. For installation details FK2-EU, see the installation and operating manual for this fire damper type. Distance to load-bearing structural elements 40 mm Distance of FKR-EU to a FK-EU 75 ­ 225 mm (flange construction 80 ­ 225 mm)
Timber structure

Fig. 56: Mortar-based installation into a lightweight partition wall, half- timbered construction

1

FKR-EU

2.1 Mortar

3.5 Half-timbered construction, cladding on both

sides

4.1 Solid ceiling slab / solid floor

6.8 Infill (cavities completely filled with mineral wool

1000 °C, 50 kg/m³, or bricks, aerated con-

crete, lightweight concrete, reinforced concrete

or clay)

7.9 Timber structure

7.11 Trim panels, double layer with staggered joints,

fire-resistant

7.13 Cladding

7.14 Reinforcing board of the same material as the

wall

Z

Spigot construction 370 mm

Flange construction 342 mm

Installation near the floor analogous to

Up to EI 90 S

EI 30 S

EI 30 S to EI 90 S

Fire damper FKR-EU

77

Installation
Lightweight partition walls with timber support … > Mortar-based installation
Half-timbered construction, “flange to flange”

Fig. 57: Mortar-based installation into a lightweight partition wall with half-timbered construction, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other)

1

FKR-EU

2.1 Mortar

3.5 Half-timbered construction, cladding on both

sides

4.1 Solid ceiling slab / solid floor

6.8 Infill (cavities completely filled with mineral wool

1000 °C, 50 kg/m³, or bricks, aerated con-

crete, lightweight concrete, reinforced concrete

or clay)

7.9 Timber structure

7.11 Trim panels, double layer with staggered joints,

fire-resistant

7.13 Cladding

7.14 Reinforcing board of the same material as the

wall

9.2 Extension piece or duct Z Spigot construction 370 mm
Flange construction 342 mm s2 Spigot construction 40 ­ 225 mm
Flange construction 80 ­ 225 mm * Installation near the floor analogous to
Up to EI 90 S EI 30 S EI 30 to EI 90 S

78

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > Mortar-based installation
Half-timbered construction, combined, FKR-EU and FK2-EU

Fig. 58: Mortar-based installation into a lightweight partition wall with half-timbered construction, FK2-EU and FKREU combined

1a FKR-EU

7.11 Trim panels, double layer with staggered joints,

1b FK2-EU up to B × H 800 × 400 mm

fire-resistant

2.1 Mortar

Z

Spigot construction 370 mm

3.5 Half-timbered construction, cladding on both sides

Flange construction 342 mm

6.8 Infill (cavities completely filled with mineral wool s2 Spigot construction 40 ­ 225 mm

1000 °C, 50 kg/m³, or bricks, aerated concrete,

Flange construction 80 ­ 225 mm

lightweight concrete, reinforced concrete or clay)

Up to EI 90 S

7.9 Timber structure

Fire damper FKR-EU

79

Installation
Lightweight partition walls with timber support … > Mortar-based installation
Note on combined installation: Total fire damper surface area 1.2 m². The number of fire dampers in an installation opening is limited by their size (B × H for FK2-EU and /or
Æ nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²). Alternative installation orientations of side-by-side, under or on top of one another possible. Details are available
upon request. For installation details FK2-EU, see the installation and operating manual for this fire damper type. Distance to load-bearing structural elements 40 mm Distance of FKR-EU to a FK-EU 75 ­ 225 mm (flange construction 80 ­ 225 mm)
Additional requirements: mortar-based installation in lightweight partition wall with timber support structure / half-timbered construction Timber stud wall or half-timbered construction,
Ä on page 35

80

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > Mortar-based installation ­ multiple occupancy…
5.7.3 Mortar-based installation ­ multiple occupancy of an installation opening
Timber stud wall

Fig. 59: Mortar-based installation ­ multiple occupancy of an installation opening

1 FKR-EU 2.1 Mortar 2.2 Concrete

3.1 Solid wall (load-bearing component) 4.1 Solid ceiling slab (load-bearing component)
Up to EI 90 S

Fire damper FKR-EU

81

Installation
Lightweight partition walls with timber support … > Mortar-based installation ­ multiple occupancy…

Fig. 60: Mortar-based installation ­ multiple occupancy of an installation opening in timber stud wall

1

FKR-EU

2.1 Mortar

3.4 Timber stud wall (also timber panel construc-

tions), cladding on both sides

6.5 Mineral wool (depending on wall construction)

7.7 Timber support structure, min. 60 × 80 mm (min.

60 × 60 mm with F60)

7.11 Trim panels, double layer with staggered joints,

fire-resistant

7.17 Trimmers, timber support structure / nogging,

at least 60 × 80 mm (min. 60 × 60 mm with F60)

Z

Spigot construction 370 mm

Flange construction 342 mm

s2 Spigot construction 40 ­ 225 mm

Flange construction 80 ­ 225 mm

Up to EI 90 S

82

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > Mortar-based installation ­ multiple occupancy…
Half-timbered wall

Fig. 61: Mortar-based installation ­ multiple occupancy of an installation opening in half-timbered construction

1

FKR-EU

Z Spigot construction 370 mm

2.1 Mortar

Flange construction 342 mm

3.5 Half-timbered construction, cladding on both

s2 Spigot construction 40 ­ 225 mm

sides

Flange construction 80 ­ 225 mm

6.8 Infill (cavities completely filled with mineral wool

Up to EI 90 S

1000 °C, 50 kg/m³, or bricks, aerated con-

crete, lightweight concrete, reinforced concrete or

clay)

7.9 Timber structure

7.11 Trim panels, double layer with staggered joints,

fire-resistant

Fire damper FKR-EU

83

Installation
Lightweight partition walls with timber support … > Mortar-based installation ­ multiple occupancy…
Additional requirements: mortar-based installation ­ multiple occupancy of an installation opening
Timber stud wall or half-timbered construction, Ä on page 35
Total fire damper area (Æ nominal width) 4.8 m2 The number of fire dampers in an installation
opening is limited by their damper size (Æ nominal width) and the overall area of the fire dampers (4.8 m2) The dampers can be arranged in one or two rows. Distance to load-bearing structural elements 40 mm If the actuators are located between the fire dampers, sufficient free space for inspection must be provided. The mortar bed width is not allowed to exceed 225 mm, provide separate trimmers if necessary.

84

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > Dry mortarless installation with installation …
5.7.4 Dry mortarless installation with installation kit TQ
Timber studs

Fig. 62: Dry mortarless installation into a lightweight partition wall with timber support structure, with installation kit TQ

1 2.11 3.4
4.1 6.5 6.13
7.7
7.10 7.11
7.12
7.13 7.13a

FKR-EU Installation kit TQ (factory assembled) Timber stud wall (also timber panel constructions), cladding on both sides Solid ceiling slab / solid floor Mineral wool (depending on wall construction) Mineral wool strips A1, 5 mm thick, 1000°C, filler as an alternative Timber support structure / nogging, at least 60 × 80 mm (at least 60 × 60 mm with F60) Trim panels, 12.5 mm, fire- resistant Trim panels, double layer, 2 × 12.5 mm with staggered joints, fire- resistant Trim panels, wood sheet, max. 12.5 mm, at least 600 kg/³ Cladding Cladding, fire-resistant

7.13b 7.14
7.17
Z


Cladding, wood sheet, at least 600 kg/³ Reinforcing board of the same material as the wall Trimmers, timber support structure / nogging, at least 60 × 80 mm (min. 60 × 60 mm with F60) Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to Cover plate, shortened by others Up to EI 90 S Up to EI 60 S EI 30 S
EI 30 to EI 90 S

Fire damper FKR-EU

85

Installation
Lightweight partition walls with timber support … > Dry mortarless installation with installation …
Timber structure

Fig. 63: Dry mortarless installation into a lightweight partition wall, half- timbered construction, using installation kit TQ

1

FKR-EU

7.13

2.11 Installation kit TQ (factory assembled)

7.14

3.5 Half-timbered construction, cladding on both

sides

Z

4.1 Solid ceiling slab / solid floor

6.8 Infill (cavities completely filled with mineral wool *

1000 °C, 50 kg/m³, or bricks, aerated con-

**

crete, lightweight concrete, reinforced concrete

or clay)

6.13 Mineral wool strips A1, 5 mm thick, 1000°C,

filler as an alternative

7.9 Timber structure

7.11 Trim panels, double layer, 2 × 12.5 mm with stag-

gered joints, fire-resistant

Cladding Reinforcing board of the same material as the wall Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to Cover plate, shortened by others Up to EI 90 S
EI 30 S

Additional requirements: dry mortarless installation with installation kit TQ into lightweight partition walls with timber support structure / half-timbered construction
Timber stud wall or half-timbered construction, Ä on page 35
Installation kit TQ, Ä on page 32 200 mm distance between two fire dampers in
separate installation openings The total thickness of the trim panels must not
exceed 25 mm Fix the cover plate with dry wall screws Æ 4.2 mm
to the timber support structure all round; nominal width up to 400 mm: 4 screws; nominal width from 450 mm: 12 screws

86

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > Dry mortarless installation with fire batt
5.7.5 Dry mortarless installation with fire batt
Timber studs

Fig. 64: Dry mortarless installation with fire batt into a lightweight partition wall with timber support structure

1

FKR-EU

2.4 Coated board system

3.4 Timber stud wall (also timber panel construc-

tions), cladding on both sides

4.1 Solid ceiling slab / solid floor

6.5 Mineral wool (depending on wall construction)

7.7 Timber stud / nogging, at least 60 × 60 mm

7.10 Trim panels (fire-resistant)

7.11 Trim panels, double layer with staggered joints,

fire-resistant

7.12 Trim panels, wood sheet, at least 600 kg/³

7.13 Cladding

7.13a 7.13b 7.14
7.17
Z

Cladding, fire-resistant Cladding, wood sheet, at least 600 kg/³ Reinforcing board of the same material as the wall Trimmers, timber stud / nogging, at least 60 × 60 mm Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to Up to EI 60 S
EI 30 S
EI 30 to EI 60 S

Fire damper FKR-EU

87

Installation
Lightweight partition walls with timber support … > Dry mortarless installation with fire batt
Timber support structure “flange to flange”

Fig. 65: Dry mortarless installation into a lightweight partition wall with timber support structure, with a fire batt, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other)

88

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > Dry mortarless installation with fire batt

1 2.4 3.4
4.1 6.5 7.7 7.10 7.11
7.12 7.13 7.13a

FKR-EU Coated board system Timber stud wall (also timber panel constructions), cladding on both sides Solid ceiling slab / solid floor Mineral wool (depending on wall construction) Timber stud / nogging, at least 60 × 60 mm Trim panels (fire-resistant) Trim panels, double layer with staggered joints, fire-resistant Trim panels, wood sheet, at least 600 kg/³ Cladding Cladding, fire-resistant

7.13b 7.14 7.17 Z s2 *

Cladding, wood sheet, at least 600 kg/³ Reinforcing board of the same material as the wall Trimmers, timber stud / nogging, at least 60 × 60 mm Spigot construction 370 mm Flange construction 342 mm Spigot construction 40 ­ 600 mm Flange construction 80 ­ 600 mm
Installation near the floor analogous to Up to EI 60 S
EI 30 S
EI 30 S to EI 60 S

Timber structure

Fig. 66: Dry mortarless installation with fire batt into a half-timbered construction

1

FKR-EU

7.13

2.4 Coated board system

7.14

3.5 Half-timbered construction, cladding on both

sides

Z

4.1 Solid ceiling slab / solid floor

6.8 Infill (cavities completely filled with mineral wool *

1000 °C, 50 kg/m³, or bricks, aerated con-

crete, lightweight concrete, reinforced concrete or

clay)

7.9 Timber structure

7.11 Trim panels, double layer with staggered joints,

fire-resistant

Cladding Reinforcing board of the same material as the wall Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to Up to EI 60 S
EI 30 S

Fire damper FKR-EU

89

Installation
Lightweight partition walls with timber support … > Dry mortarless installation with fire batt
Half-timbered construction “flange to flange”

Fig. 67: Dry mortarless installation into a half-timbered construction, with a fire batt, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other)

1

FKR-EU

7.14 Reinforcing board of the same material as the

2.4 Coated board system

wall

3.5 Half-timbered construction, cladding on both

Z

Spigot construction 370 mm

sides

Flange construction 342 mm

4.1 Solid ceiling slab / solid floor

s2

Spigot construction 40 ­ 600 mm

6.8 Infill (cavities completely filled with mineral wool

Flange construction 80 ­ 600 mm

1000 °C, 50 kg/m³, or bricks, aerated con-

Installation near the floor analogous to

crete, lightweight concrete, reinforced concrete

Up to EI 60 S

or clay)

EI 30 S

7.9 Timber structure

7.11 Trim panels, double layer with staggered joints,

fire-resistant

7.13 Cladding

90

Fire damper FKR-EU

Installation
Lightweight partition walls with timber support … > Dry mortarless installation with fire batt
Additional requirements: dry mortarless installation with fire batt into lightweight partition walls with timber support structure Timber stud wall or half-timbered construction,
Ä on page 35 Fire batt systems, installation details, distances /
dimensions, Ä on page 32 f Suspension and fixing Ä Chapter 5.14 `Fixing the
fire damper’ on page 135

Fire damper FKR-EU

91

Installation
Solid wood walls > General
5.8 Solid wood walls 5.8.1 General

Fig. 68: Solid wood wall 3.11 Solid wood wall / CLT wall 4.1 Solid ceiling slab / solid floor 5.13 Wood screw or pin
Additional requirements: solid wood walls Solid wood wall or CLT wall, Ä on page 35

7.10 A A1

Trim panels (optional) Clear installation opening Opening in a solid wood wall / CLT wall (without trim panels: A1 = A)

Installation opening A [mm]

Installation type

Nominal size Ænominal width

Mortar-based installation

315 355 400 450 500 560 630 710 800 A = Ænominal width + max. 450 mm A1 = A + (4 × trim panels)

Dry mortarless installation with installa- 435 475 520 570 620 680 750 830 920 tion kit TQ1, 2

Dry mortarless installation with fire batt

A = Ænominal width + 80 ­ 1200 mm

  1. Installation opening tolerance + 2 mm

  2. Installation kit TQ is available only for FKR-EU with spigot

92

Fire damper FKR-EU

5.8.2 Mortar-based installation

Installation
Solid wood walls > Mortar-based installation

Fig. 69: Mortar-based installation into a solid wood wall or CLT wall

1

FKR-EU

7.14

2.1

Mortar

3.11 Solid wood wall / CLT wall

4.1

Solid ceiling slab / solid floor

Z

5.13 Wood screw or pin

7.10 Trim panels

7.13a Cladding, single-layer, fire-resistant

­

Reinforcing board of the same material (required for W < 100 mm, optionally on the operating or installation side) Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to optional Up to EI 90 S

Fire damper FKR-EU

93

Installation
Solid wood walls > Mortar-based installation
Solid wood wall/CLT wall, “flange to flange”

Fig. 70: Mortar-based installation into a solid wood wall or CLT wall, flange to flange, illustration shows side by side installation (applies also to installation of dampers on top of each other)

1 2.1 3.11 4.1 5.13 7.10 7.13a 7.14

FKR-EU Mortar Solid wood wall / CLT wall Solid ceiling slab / solid floor Wood screw or pin Trim panels Cladding, single-layer, fire-resistant Reinforcing board of the same material (required for W < 100 mm, optionally on the operating or installation side)

Z

Spigot construction 370 mm

Flange construction 342 mm

s2

Spigot construction 40 ­ 225 mm

Flange construction 80 ­ 225 mm

Installation near the floor analogous to

optional

­

Up to EI 90 S

Additional requirements: mortar-based installation into solid wood walls Solid wood wall or CLT wall, Ä on page 35

94

Fire damper FKR-EU

Installation
Solid wood walls > Dry mortarless installation with installation …
5.8.3 Dry mortarless installation with installation kit TQ

Fig. 71: Dry mortarless installation into a solid wood wall or CLT wall, with installation kit TQ

1

FKR-EU

Z

2.11 Installation kit TQ (factory assembled)

3.11 Solid wood wall / CLT wall

4.1

Solid ceiling slab / solid floor

**

6.13 Mineral wool strips A1, 5 mm thick, 1000°C, #

filler as an alternative

­

7.10 Trim panels (fire-resistant)

7.13a Cladding, single-layer, fire-resistant

Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to Cover plate, shortened by others optional Up to EI 90 S

Additional requirements: dry mortarless installation with installation kit TQ in solid wood walls
Solid wood wall or CLT wall, Ä on page 35 Installation kit TQ, Ä on page 32
200 mm distance between two fire dampers in separate installation openings
Fasten the cover plate to the solid wood or CLT wall with 4 (for nominal widths up to 400 mm) or 12 (for nominal widths from 450 mm) dry wall screws Æ 4.2 mm

Fire damper FKR-EU

95

Installation
Solid wood walls > Dry mortarless installation with fire batt
5.8.4 Dry mortarless installation with fire batt

Fig. 72: Dry mortarless installation into a timber wall or CLT wall, with a fire batt

1 2.4 3.11 4.1 7.10 7.13a

FKR-EU Coated board system Solid wood wall / CLT wall Solid ceiling slab / solid floor Trim panels (fire-resistant) Cladding, single-layer, fire- resistant

7.14

Reinforcing board of the same material as the

wall

Z

Spigot construction 370 mm

Flange construction 342 mm

Installation near the floor analogous to

optional

­

Up to EI 60 S

96

Fire damper FKR-EU

Solid wood wall/CLT wall, “flange to flange”

Installation
Solid wood walls > Dry mortarless installation with fire batt

Fig. 73: Dry mortarless installation into a solid wood wall or CLT wall, with a fire batt, “flange to flange”

1

FKR-EU

Z

2.4

Coated board system

3.11 Solid wood wall / CLT wall

s2

4.1

Solid ceiling slab / solid floor

7.10 Trim panels (fire-resistant)

7.13a Cladding, single-layer, fire-resistant

7.14 Reinforcing board of the same material as the

­

wall

Spigot construction 370 mm Flange construction 342 mm Spigot construction 40 ­ 600 mm Flange construction 80 ­ 600 mm
Installation near the floor analogous to optional Up to EI 60 S

Additional requirements: dry mortarless installation with fire batt in solid wood walls
Solid wood wall or CLT wall, Ä on page 35 Fire batt systems, installation details, distances /
dimensions, Ä on page 32 f Suspension and fixing Ä Chapter 5.14 `Fixing the
fire damper’ on page 135

Fire damper FKR-EU

97

Installation
Shaft walls with metal support structure > General
5.9 Shaft walls with metal support structure 5.9.1 General
Shaft walls with metal support structure and cladding on one side

Fig. 74: Shaft walls with metal support structure and cladding on one side

98

Fire damper FKR-EU

A

Shaft wall

B

Shaft wall, installation near the floor

C

Shaft wall, installation near the ceiling

5.1 Dry wall screw

5.6 Screw or steel rivet

7.1 UW section

7.1a Fold the tab inward or cut it off

7.1b UW section, nominal sizes:

Æ nominal width 450 – 800

Installation
Shaft walls with metal support structure > General

7.2 7.10 7.13
7.14 A A1

CW section Optional trim panels Double layer cladding, on one side of the metal stud system Reinforcing strip Installation opening Opening in the metal support structure (without trim panels: A =A1) Closed side of metal section must face the installation opening

Additional requirements: shaft walls with metal support structure Shaft wall with metal support structure, Ä on page 35
Erecting a wall and creating an installation opening Erect the shaft wall according to the manufacturer’s instructions and create an installation opening, see Fig. 74
­ Provide the installation opening in the metal support structure with support sections. ­ In case of mortar-based installation of fire dampers from nominal size Ænominal width 450, install four addi-
tional sections 7.1b at an angle of 45° in order to reinforce the metal support structure.

Installation type Mortar-based installation 1

  1. Optional trim panels

Installation opening A [mm] Nominal size Ænominal width
315 355 400 450 500 560 630 710 800 A = Ænominal width + max. 450 mm A1 = A + (2 × trim panels)

Fire damper FKR-EU

99

Installation
Shaft walls with metal support structure > Mortar-based installation
5.9.2 Mortar-based installation
Mortar-based installation into shaft wall with metal support structure

Fig. 75: Mortar-based installation into shaft wall with metal support structure

1

FKR-EU

2.1 Mortar

3.7 Shaft wall with metal support structure, cladding

on one side

3.10 Wall without adequate fire resistance rating

4.1 Solid ceiling slab / solid floor

5.1 Dry wall screw

6.5 Mineral wool (depending on wall construction)

7.1 UW section

7.5 Steel support structure (box section)

7.10 Trim panels

7.13.1 7.14
9.2 Z

  • ­ ­

Cladding, single-layer, adjusted Reinforcing board of the same material as the wall Extension piece or duct Spigot construction 370 mm Flange construction 342 mm
Installation near the floor analogous to optional Up to EI 90 S
EI 30 S
EI 30 S ­ EI 90 S

100

Fire damper FKR-EU

Installation
Shaft walls with metal support structure > Mortar-based installation 7.13 Cladding, double layer, fire-resistant
Mortar-based installation into a shaft wall, FKR-EU and FK2-EU combined

Fig. 76: Mortar-based installation into a shaft wall, FKR-EU and FK2-EU combined

1a FKR-EU 1b FK2-EU up to B × H 800 × 400 mm 2.1 Mortar 3.7 Shaft wall with metal support structure, cladding
on one side 7.10 Trim panels 7.13 Cladding 7.14 Reinforcing board of the same material as the
wall

optional Z Spigot construction 370 mm

Flange construction 342 mm s2 Spigot construction 40 ­ 225 mm
Flange construction 80 ­ 225 mm Up to EI 90 S

Fire damper FKR-EU

101

Installation
Shaft walls with metal support structure > Mortar-based installation
Note on combined installation:
Total fire damper surface area 1.2 m². The number of fire dampers in an installation
opening is limited by their size (B × H for FK2-EU and /or Æ nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²). Alternative installation orientations of side-by-side, under or on top of one another possible. Details are available upon request. For installation details FK2-EU, see the installation and operating manual for this fire damper type. Distance to load-bearing structural elements 40 mm Distance of FKR-EU to a FK-EU 75 ­ 225 mm (flange construction 80 ­ 225 mm)
Additional requirements: mortar-based installation into shaft walls with metal support structure
Shaft wall with metal support structure, Ä on page 35
200 mm distance between two fire dampers (installation of each fire damper in separate installation openings, exception combined installation)

102

Fire damper FKR-EU

Installation
Shaft walls without metal support structure > General
5.10 Shaft walls without metal support structure 5.10.1 General
Shaft wall without metal support structure and with cladding on one side

Fig. 77: Shaft wall without metal support structure and with cladding on one side

A

Wall construction for nominal sizes Æ 315 ­ 400

mm

B

Wall construction for nominal sizes Æ 450 ­ 800

mm

5.1 Dry wall screw

7.1 UW section

7.1b UW section, for nominal sizes Ænominal width

450 – 800

7.10 Optional trim panels

7.13
7.14 A A1 *

Double layer cladding, on one side of the metal stud system Reinforcing strip Installation opening Opening (without trim panels: A =A1) Closed side of metal section must face the installation opening

Additional requirements: shaft walls without metal support structure Shaft wall without metal support structure, Ä on page 35

Fire damper FKR-EU

103

Installation
Shaft walls without metal support structure > Mortar-based installation
Erecting a wall and creating an installation opening Erect the shaft wall according to the manufacturer’s instructions and create an installation opening with rein-
forcing strips, see Fig. 77 ­ Option A: Create an opening in the cladding and reinforce it along the perimeter.
­ Option B: Provide the installation opening in the metal support structure with support sections. Install four additional sections at an angle of 45° in order to reinforce the metal support structure. Fix the cladding and reinforce the installation opening along the perimeter.

Installation type Mortar-based installation 1

  1. Optional trim panels

Installation opening A [mm] Nominal size Ænominal width
315 355 400 450 500 560 630 710 800 A = Ænominal width + max. 450 mm A1 = A + (2 × trim panels)

5.10.2 Mortar-based installation
Mortar-based installation into shaft wall without metal support structure

Fig. 78: Mortar-based installation into shaft wall without metal support structure

1

FKR-EU

2.1 Mortar

3.9 Shaft wall without metal support structure, clad-

ding on one side

4.1 Solid ceiling slab / solid floor

5.1 Dry wall screw

7.1 UW section

7.13 Cladding, double layer, fire-resistant

7.14 Reinforcing board of the same material as the

wall

9.2 Extension piece or duct

Z

Spigot construction 370 mm

Flange construction 342 mm

Installation near the floor analogous to

Up to EI 90 S

Additional requirements: mortar-based installation into shaft walls without metal support structure Shaft wall, Ä on page 35

104

Fire damper FKR-EU

5.11 Solid ceiling slabs 5.11.1 General

Installation
Solid ceiling slabs > General

Fig. 79: Solid ceilings ­ arrangement / distances, side-by-side arrangement by way of example

1 FKR-EU 4.1 Solid ceiling slab

s1 Perimeter gap, Ä on page 31 s2 Distance between the fire dampers, Ä
tances’ on page 29

`Dis-

Installation type

Installation opening [mm]

Mortar-based installation

  1. Spigot construction, with flange construction 80 ­ 225 mm

Ænominal width + max. 450 mm

Distance [mm]

s1

s2

225

40 ­ 225 1

Additional requirements: solid ceiling slabs Solid ceiling slab, Ä on page 36 Distances and installation orientations, Ä `Dis-
tances’ on page 29

Fire damper FKR-EU

105

Installation
Solid ceiling slabs > Mortar-based installation into solid ceiling s…
5.11.2 Mortar-based installation into solid ceiling slabs
Mortar-based installation into a solid ceiling slab, suspended or upright

Fig. 80: Mortar-based installation into a solid ceiling slab, suspended or upright

1 FKR-EU 2.1 Mortar 2.2 Reinforced concrete 4.1 Solid ceiling slab

9.2

Extension piece or duct

Z

Spigot construction 370 mm

Flange construction 342 mm

­

Up to EI 120 S

106

Fire damper FKR-EU

Installation
Solid ceiling slabs > Mortar-based installation into solid ceiling s…
Mortar-based installation into a solid ceiling slab with screed and footfall sound insulation, suspended or upright

Fig. 81: Mortar-based installation into a solid ceiling slab with screed and footfall sound insulation, suspended or upright

1

FKR-EU

2.1 Mortar

2.2 Reinforced concrete

4.1 Solid ceiling slab

6.22 Screed

6.23

Footfall sound insulation

9.2

Extension piece or duct

Z

Spigot construction 370 mm

Flange construction 342 mm

­

Up to EI 120 S

Fire damper FKR-EU

107

Installation
Solid ceiling slabs > Mortar-based installation into solid ceiling s…
Mortar-based installation into solid ceiling slab, “flange to flange”

Fig. 82: Mortar-based installation in solid ceiling slab, “flange to flange”, shown upright (also applicable for suspended arrangement)

1 FKR-EU 2.1 Mortar 2.2 Reinforced concrete 4.1 Solid ceiling slab 9.2 Extension piece or duct

Z

Spigot construction 370 mm

Flange construction 342 mm

s2

Spigot construction 40 ­ 225 mm

Flange construction 80 ­ 225 mm

Up to EI 120 S

108

Fire damper FKR-EU

Installation
Solid ceiling slabs > Mortar-based installation into solid ceiling s…
Mortar-based installation into a solid ceiling slab with screed and footfall sound insulation, “flange to flange”

Fig. 83: Mortar-based installation in solid ceiling slab with screed and footfall sound insulation, “flange to flange”, shown upright (also applicable for suspended arrangement)

1

FKR-EU

2.1 Mortar

2.2 Reinforced concrete

4.1 Solid ceiling slab

6.22 Screed

6.23 Footfall sound insulation

9.2 Extension piece or duct

Z

Spigot construction 370 mm

Flange construction 342 mm

s2

Spigot construction 40 ­ 225 mm

Flange construction 80 ­ 225 mm

Up to EI 120 S

Fire damper FKR-EU

109

Installation
Solid ceiling slabs > Mortar-based installation into solid ceiling s…
Mortar-based installation into a solid ceiling slab, FKR-EU and FK2-EU combined

Fig. 84: Mortar-based installation in solid ceiling slab, combined, FKR-EU and FK2-EU, shown upright (also applicable for suspended arrangement)

1b FKR-EU 1a FK2-EU up to B × H 800 × 400 mm 2.1 Mortar 2.2 Concrete 4.1 Solid ceiling slab

Z Spigot construction 370 mm Flange construction 342 mm
s2 Spigot construction 40 ­ 225 mm Flange construction 80 ­ 225 mm Up to EI 90 S

Note on combined installation:
Total fire damper surface area 1.2 m². The number of fire dampers in an installation opening is limited by their size (B × H for FK2-EU and /or
Æ nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²). Alternative installation orientations of side-by-side possible. Details are available upon request.
For installation details FK2-EU, see the installation and operating manual for this fire damper type. Structural properties of the ceiling construction, including the attachment to the mortar/concrete or any required
reinforcement, have to be evaluated and ensured by others. Distance of FKR-EU to a FK-EU 75 ­ 225 mm (flange construction 80 ­ 225 mm)

110

Fire damper FKR-EU

Installation
Solid ceiling slabs > Mortar-based installation into solid ceiling s…
Additional requirements: mortar-based installation into solid ceiling slabs Solid ceiling slab, Ä on page 36 40 mm distance from fire damper to load- bearing
structural elements

Fire damper FKR-EU

111

Installation
Solid ceiling slabs > Mortar-based installation ­ multiple occupancy…
5.11.3 Mortar-based installation ­ multiple occupancy of an installation opening

Fig. 85: Mortar-based installation ­ multiple occupancy of an installation opening

1 FKR-EU 2.1 Mortar 2.2 Concrete 3.1 Solid wall (load-bearing component)

s2 Spigot construction 40 ­ 225 mm Flange construction 80 ­ 225 mm Up to EI 90 S

112

Fire damper FKR-EU

Installation
Solid ceiling slabs > Mortar-based installation ­ multiple occupancy…

Fig. 86: Mortar-based installation ­ multiple occupancy of one installation opening, shown upright (also applicable for suspended arrangement)

1 FKR-EU 2.1 Mortar 2.2 Concrete 4.1 Solid ceiling slab Z Spigot construction 370 mm

Flange construction 342 mm s2 Spigot construction 40 ­ 225 mm
Flange construction 80 ­ 225 mm Up to EI 90 S

Additional requirements: mortar-based installation ­ multiple occupancy of an installation opening
Solid ceiling slab, Ä on page 36
Total fire damper area (Æ nominal width) 4.8 m2
The number of fire dampers in an installation opening is limited by their damper size (Æ nominal width) and the overall area of the fire dampers (4.8 m2).
Structural properties of the ceiling construction, including the attachment to the mortar/concrete or any required reinforcement, have to be evaluated and ensured by others.

Fire damper FKR-EU

113

Installation
Solid ceiling slabs > Mortar-based installation into a concrete base
5.11.4 Mortar-based installation into a concrete base
Mortar-based installation with concrete base into a solid ceiling slab, upright

Fig. 87: Mortar-based installation with concrete base into a solid ceiling slab, upright

1

FKR-EU

2.3 Concrete base

4.1 Solid ceiling slab

5.22 Steel fabric, Æ 8 mm, mesh aperture 150 mm,

or equivalent, for number of fixing points see table Ä 114

9.2 Extension piece or duct Z Spigot construction 370 mm
Flange construction 342 mm Up to EI 120 S

Note: EI 120 S also for two FKR-EU with spacing of 60 ­ 225 mm.

Minimum number of fixing points in the bare ceiling

B
Æ 315 Æ 500 Æ 800

Æ 315 4 6 8

A Æ 500
6 8 10

Æ 800 8 10 12

114

Fire damper FKR-EU

Installation
Solid ceiling slabs > Mortar-based installation into a concrete base
Mortar-based installation with concrete base into a solid ceiling slab, upright, combined, FKR-EU and FK2EU

Fig. 88: Mortar-based installation with concrete base into a solid ceiling slab, upright, combined, FKR-EU and FK2EU

1a FKR-EU 1b FK2-EU up to B × H 800 × 400 mm 2.3 Concrete base 4.1 Solid ceiling slab 5.22 Steel fabric, Æ 8 mm, mesh aperture 150 mm,
or equivalent, for number of fixing points see table Ä 114 9.2 Extension piece or duct

Z Spigot construction 370 mm Flange construction 342 mm
s2 Spigot construction 40 ­ 225 mm Flange construction 80 ­ 225 mm Up to EI 90 S

Fire damper FKR-EU

115

Installation
Solid ceiling slabs > Mortar-based installation into a concrete base

Note on combined installation:
Combined configuration up to 1.2 m² fire damper area. The number of fire dampers in an installation opening is limited by their size (B × H for FK2-EU and /or
Æ nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²). Alternative installation orientations of side-by-side possible. Details are available upon request.
For installation details FK2-EU, see the installation and operating manual for this fire damper type. Structural properties of the ceiling construction, including the attachment to the mortar/concrete or any required
reinforcement, have to be evaluated and ensured by others.

Minimum number of fixing points in the bare ceiling

H
100 400 700

200 4 6 8

500 6 8 10

B 800
8 10 12

1100 10 12 14

1400 12 14 16

Additional requirements: mortar-based installation into solid ceiling slab with concrete base
Solid ceiling slab, Ä on page 36 40 mm distance from fire damper to load- bearing
structural elements If the distance to adjacent solid walls is < 150 mm
and if the concrete base has been correctly attached, no reinforcement is required on the wall side. Concrete bases H 150 mm do not require reinforcement Distance of 40 mm between two FKR-EU units, 80 mm for flange construction Distance to fire dampers FK2-EU 70 ­ 225 mm Distance of FKR-EU to a FK-EU 75 ­ 225 mm (flange construction 80 ­ 225 mm)
1. Screw the fire damper to the existing, dysfunctional fire damper or to the ducting.
2. Create a concrete base according to Fig. 87 to Fig. 88 or equivalent.
3. Structural and fire resistance properties of the ceiling construction, including the attachment to the concrete or any required reinforcement, have to be evaluated and ensured by others.

116

Fire damper FKR-EU

Installation
Solid ceiling slabs > Mortar-based installation into the concrete ba…
5.11.5 Mortar-based installation into the concrete base ­ multiple occupancy of an installation opening

Fig. 89: Mortar-based installation into the concrete base ­ multiple occupancy of an installation opening

1 FKR-EU 2.1 Mortar 2.2 Concrete 3.1 Solid wall (load-bearing component)

s2 Spigot construction 40 ­ 225 mm Flange construction 80 ­ 225 mm Up to EI 90 S

Fire damper FKR-EU

117

Installation
Solid ceiling slabs > Mortar-based installation into the concrete ba…

Fig. 90: Mortar-based installation with concrete base into a solid ceiling slab, upright, multiple occupancy of an installation opening

1

FKR-EU

2.3 Concrete base

4.1 Solid ceiling slab

5.22 Steel fabric, Æ 8 mm, mesh aperture 150 mm,

or equivalent, for number of fixing points see table Ä 114

9.2 Extension piece or duct

Z Spigot construction 370 mm Flange construction 342 mm
s2 Spigot construction 40 ­ 225 mm Flange construction 80 ­ 225 mm Up to EI 90 S

118

Fire damper FKR-EU

Installation
Solid ceiling slabs > Mortar-based installation into the concrete ba…

Minimum number of fixing points in the bare ceiling

B
315 500 800 1100 1400 1700 2000

315 4 6 8 10 12 14 16

500 6 8 10 12 14 16 18

800 8 10 12 14 16 18 20

A 1100
10 12 14 16 18 20 22

1400

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals