WILDEBOER VR1 Volume Flow Controller User Manual

September 14, 2024
WILDEBOER

VR1 Volume Flow Controller

Specifications

  • Product: Volume flow controller VR1
  • Flow Rate Range: 30 to 600 Pa
  • Nominal Diameter: DN 80 to DN 315
  • Flow Velocity: 1.1 to 12.2 m/s
  • Control Accuracy: Set point flow rate

Product Overview

The VR1 volume flow controller is designed to regulate air flow
in ventilation systems efficiently.

Product Features

  • Dimensions: Available in various nominal
    diameters from DN 80 to DN 315.

  • Lip Seal: Ensures an airtight connection to
    ventilation ducts.

  • Set Point Adjustment: Allows for precise flow
    rate control.

  • Accessories: Optional accessories for factory
    or on-site installation.

Product Description

The VR1 volume flow controller comes with acoustic insulation
with a sheet metal jacket for noise reduction and an SRC duct
silencer for enhanced performance.

Quick Dimensioning

Refer to the provided dimensions guide for proper installation
and optimal performance.

Installation

Follow these steps for proper installation:

  1. Ensure proper distances to disturbance points as per
    guidelines.

  2. Securely connect the volume flow controller to the ventilation
    duct.

  3. Adjust the set point according to desired flow rate.

Technical Data

Refer to the dimensions and specifications provided for detailed
technical information on the VR1 volume flow controller.

FAQ

Q: What is the operating temperature range for the VR1 volume

flow controller?

A: The operating temperature range is specified in the user
manual. Please refer to the manual for detailed information.

Q: What are the areas of application for the different VR1

product variants?

A: The VR1-N is a mechanical controller, VRL1 is a mechanical
limiter, VRE1 is an electronic controller, and VRup/VRpro is an
electronic controller. Each variant has specific pressure
difference and flow rate ranges suitable for different
applications. Please refer to the product portfolio for more
details.

USER MANUAL
AIR DISTRIBUTION
Volume flow controller VR1
Trust you can build in.

Contents
VR1 volume flow controller

Contents

1

Product overview

3

2

Product features

4

3

Product description

6

3.1 Area of application ………………………………………………………………………………………………………………………………………………………………………………………… 6 3.2 Function……………………………………………………………………………………………………………………………………………………………………………………………………………….7 3.3 Accessories………………………………………………………………………………………………………………………………………………………………………………………………………….7
3.3.1 Acoustic insulation with sheet metal jacket……………………………………………………………………………………………………………………………………….7 3.3.2 SRC duct silencer…………………………………………………………………………………………………………………………………………………………………………………………7

4

Quick dimensioning

8

5

Installation

9

5.1 Distances to disturbance points………………………………………………………………………………………………………………………………………………………………… 9

6

Technical Data

10

6.1 Dimensions ……………………………………………………………………………………………………………………………………………………………………………………………………… 10 6.1.1 SRC duct silencer………………………………………………………………………………………………………………………………………………………………………………………..11
6.2 Weights……………………………………………………………………………………………………………………………………………………………………………………………………………….11 6.3 Sound power level (flow noise) ………………………………………………………………………………………………………………………………………………………………….. 12 6.4 Sound power level (radiated noise) ………………………………………………………………………………………………………………………………………………………….14 6.5 Set point adjustment …………………………………………………………………………………………………………………………………………………………………………………….16
6.5.1 Manual ………………………………………………………………………………………………………………………………………………………………………………………………………….16 6.5.2 Motorised……………………………………………………………………………………………………………………………………………………………………………………………………..16

7

Specification text

18

8 8.1 8.2 8.3

Wildeboer makes it easy

19

Wildeboer Configurator ………………………………………………………………………………………………………………………………………………………………………………19 WiDim dimensioning software…………………………………………………………………………………………………………………………………………………………………..19 Documents online…………………………………………………………………………………………………………………………………………………………………………………………..19

Description Functional principle Pressure difference Flow rate range Nominal diameter Flow velocity Control accuracy
Operating temperature Further information

VR1 Mechanical controller 50 .. 1000Pa 50 … 3100 m³/h DN 80 … DN 315 2.1 … 15.5 m/s ±5 … ±10 % of set point flow rate -20 … +70 °C, short-term 90 °C In this document

Product portfolio:
Areas of application for circular volume flow controllers and limiters

VR1-N

VRL1

VRE1

VRup / VRpro

Mechanical controller

Mechanical limiter

Electronic controller

Electronic controller

30 … 600Pa

30 … 300Pa

20 … 1000Pa

5 … 1000Pa

30 … 2300 m³/h

13 … 1060 m³/h

34 … 5430 m³/h

42 … 5430 m³/h

DN 80 … DN 315

DN 80 … DN 250 DN 100 … DN400 DN 100 … DN400

1.1 … 12.2 m/s

0.8 … 6 m/s

1.2 … 12 m/s

1.5 … 12 m/s

approx. ±5 % of nominal flow rate*

±5 … ±10 % of

±5 … ±15 % of

±5 … ±20 % of

nominal flow rate set point flow rate set point flow rate

-20 … +70 °C, short-term 90 °C

+10 … +50 °C

+5 … +60 °C

0 … +50 °C

LINK

LINK

LINK

LINK

  • or ±10 % from set point flow rate (depending on which deviation is greater)

Page 2 | 20

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Overview
VR1 volume flow controller
1 Product overview
VR1 volume flow controllers are maintenance-free, mechanically self-actuating controllers for supply air and exhaust air ducts with constant flow rates that operate without any auxiliary power supply. They are used especially at low flow velocities and variable pressures to keep the flow rate constant as per the set point value. The flow rate is set using a manual setting device with pointer, scale and locking mechanism. As an option, the VR1 can be fitted with a 24 V AC/DC or 230 V AC actuator for motorised set point adjustment for applications with variable flow rates.
· Highest control accuracy at variable pressures · Factory preset for the set point flow rate · Adjustable on site · Position-independent installation · Maintenance-free design · Sizes DN 80 to DN 315 · Casing tightness: Class C as per DIN EN 1751 · Volume flow range: 50 … 3100 m³/h · Pressure range: 50 … 1000Pa · Flow velocities: 2.1 … 15.5 m/s · Temperature range: -20 … +70 °C, short-term +90 °C · Hygiene certificate:
VDI 6022-1, VDI 3803-1, DIN1946-4, DINEN16798-3, SWKIVA104-01, SWKIVA105-01, ÖNORMH6020, ÖNORMH6021 · Environment Product Declaration: EPD-WIL-20150036 -ICA-EN · Options · Reversible actuator with 2-point and 3-point control for setting to two flow
rate set points, 230 V AC or 24 V AC/DC · Continuously adjustable reversible actuator for setting to any flow rate set
point, 24 V AC/DC · Acoustic insulation with sheet metal jacket · SRC duct silencer in lengths: 600 mm and 900 mm · Lip seals at both ends

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Page 3 | 20

Product features
VR1 Volume Flow Controller
2 Product features

1 Dimensions

2 Lip seal

3 Set point adjustment

4 Accessories

1 Dimensions
Nominal diameter [DN] 80 100 125 160 200 250 315
2 Lip seal
For airtight connection to ventilation ducts Optional accessories pre- assembled at the factory or for on-site installation

Page 4 | 20

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Product features
VR1 volume flow controller

3 Set point adjustment Manual (basic version)

Manual setting device with setting pointer, scale and locking mechanism: The flow rate set point values are set manually using the setting pointer within the ranges min to max. The controllers are adjusted at the factory for the entire volume flow range. The VR1 can be preset at the factory before delivery For this purpose, the flow rate set point values must be specified when ordering. Subsequent adjustment on site is possible.
Pre-installed at the factory before delivery

Actuator-driven (optional version)
M1: Reversible actuator 230 V AC with 2-point and 3-point control. The corresponding motor limit stops are positioned in order to adjust the flow rates. Optional accessories pre-assembled at the factory or for on-site installation
M2: Reversible actuator 24 V AC/ DC with 2-point and 3-point control. The corresponding motor limit stops are positioned in order to adjust the flow rates. Optional accessories pre-assembled at the factory or for on-site installation
M3: Continuously adjustable reversible actuator 24 V AC/DC To adjust the flow rates, a reference signal is used from 0 … 10 V. Optional accessories pre- assembled at the factory or for on-site installation For details, please refer to Page 16.
4 Accessories
Acoustic insulation with sheet metal casing to reduce the external sound radiation of the volume flow controller (radiated noise) Optional accessories pre-assembled at the factory or for on-site installation
For details, please refer to Page 7.
SRC duct silencer for reducing flow noise in the connected ventilation duct. Packing thickness: 50 mm mineral wool lengths: 600 mm 900 mm Optional accessories for on-site installation For details, please refer to Page 7.

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Page 5 | 20

Product description
VR1 Volume Flow Controller

3 Product description
The VR1 volume flow controller is made of galvanised steel. The damper blade which controls the flow rate is centrally supported and has stainless steel bearing shafts in special bushes. The manual setting device is fitted with a setting pointer, scale and locking mechanism. Flow rate set points can be adjusted manually or by actuator within the flow rate ranges min to max. The special control mechanism ensures high control accuracy, so with variable pressures, the flow rate can be kept constant over the entire pressure range.
The adjustable volume flow set points depend on the nominal diameter of the VR1.

4

5

4

5

6

Lu richtung air flow direction
Differenzdruck 30 … 600 Pa differential pressure
500 400 300 280

1400 1300
1200
1100 1000
900 800 700600

m³/h

Volumenstromregler VR1-250
volume flow controller

1

2

3

Item
1 2 3
4 5 6

Description Duct casing Label with scale and air direction indicator
Manual setting device with setting pointer, scale and locking mechanism
Lip seal (optional) Acoustic insulation with sheet metal jacket (optional) Damper blade

Size [DN] 80 100 125 160 200 250 315

[m³/h] min 50 70 120 150 250 400 600

[m³/h] max 280 380 600 900 1300 2100 3100

3.1 Area of application
The VR1 volume flow controller is used in supply air and exhaust air ducts of ventilation and air conditioning systems.
Notes · VR1 volume flow controllers are adjusted for the entire scaled application area. · The flow rate set point is set during installation by turning the setting pointer to the desired value on the scale and
locking this setting. This does not affect the control accuracy. · Volume flow controllers that are preset at the factory can be installed directly. The flow rate set point can be changed at
a later date by releasing the locking mechanism. · The VR1 volume flow controller and the optional SRC duct silencer are supplied separately. Assembly is carried out on
site. · Installation and operating instructions for the VR1 are available on the Internet at www.wildeboer.de.

Page 6 | 20

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Product description
VR1 volume flow controller

3.2 Function
The VR1 volume flow controller operates without any auxiliary power supply. The air flow in the ventilation duct generates a torque in the closing direction when it hits the damper blade. This torque is counterbalanced by the restoring torque of a blade spring so that the flow rate can be kept constant within the tolerances, even if the pressure differences change. Additional damping bellows ensures vibration-free movement of the damper blade.

3.3 Accessories

3.3.1 Acoustic insulation with sheet metal jacket

Acoustic insulation with a sheet metal jacket is supplied factory-mounted or for on-site installation.

Maximum possible reduction in radiated noise as a function of the nominal diameter:

DN Reduction

80

100

125

160

-18 dB

200

250

315

3.3.2 SRC duct silencer

The SRC duct silencer is supplied separately. Assembly is carried out on site along with the volume flow controller.

Maximum possible reduction in flow noise as a function of the silencer length:

DN

Outer diameter [mm]

80

200

100

200

125

225

160

260

200

300

250

355

315

415

L [mm]

600

900

-22 dB

-22 dB

-25 dB

-22 dB

-25 dB

-21 dB

-24 dB

-19 dB

-24 dB

-18 dB

-22 dB

-15 dB

-19 dB

Packing thickness: 50 mm mineral wool

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Page 7 | 20

Quick dimensioning
VR1 Volume Flow Controller

4 Quick dimensioning
The quick dimensioning table shows the expected sound power level of the VR1. Intermediate values can be interpolated for a rough estimate. The exact values for different differential pressures can be taken from the Wildeboer dimensioning software WiDim. WiDim

Sound level

Size
[DN] 80 80 80 100 100 100 125 125 125 160 160 160 200 200 200 250 250 250 315 315 315

Flow rate
[m³/h] 50 160 280 70 220 380 120 360 600 150 525 900 250 750 1300 400 1200 2100 600 1800 3100

Flow velocity
v [m/s] 2.8 8.8 15.5 2.5 7.8 13.4 2.7 8.1 13.6 2.1 7.3 12.4 2.2 6.6 11.5 2.3 6.8 11.9 2.1 6.4 11.0

Differential pressure
p [Pa] 75 100 150 75 100 150 75 100 150 75 100 150 75 100 150 75 100 150 75 100 150

Flow noise
Sound power level L [dB(A)] WA 38.97 51.77 60.12 39.56 52.05 60.2 41.95 53.97 61.75 41.38 54.6 62.57 43.57 55.35 63.37 45.41 57.15 65.22 46.66 58.32 66.2

Radiated noise
Sound power level L [dB(A)] WA <20 37.39 48.45 <20 35.43 46.86 25.15 39.14 47.66 28.87 40.12 47.01 31.99 40.82 47.74 29.98 42.85 50.6 32.67 45.69 53.41

The sound power level of the radiated noise can be further reduced by using acoustic insulation.
The mean sound pressure level in the room is:
· 26 dB lower with acoustic insulation · 8 dB lower without acoustic insulation
than the sound power levels specified in the nomograms LWA. The sound pressure level can be further reduced by carrying out additional sound attenuation measures on site (suspended ceilings, high degree of room attenuation). However, the acoustic insulation can only achieve the stated values if connected ventilation ducts are also suitably soundproofed (insulated).

The sound power level of the flow noise can be reduced by up to 25 dB by using an SRC duct silencer. Page 7.

Page 8 | 20

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Installation
VR1 volume flow controller

5 Installation

The VR1 volume flow controller is installed regardless of the position and in the air direction indicated on the label. To ensure lasting functionality and leak tightness, stress-free installation in ventilation ducts is a prerequisite.
Space requirement
To enable the scale to be read and the commissioning and servicing work to be carried out, sufficient space should be kept free in the area of any attachments. Inspection openings of sufficient size may required so that the attachments are easily accessible.

Set point adjustment: manual

Set point adjustment: motorised

approx. 12 cm

approx. 12 cm

approx. 20 cm

approx. 28 cm

approx. 28 cm

approx. 28 cm

5.1 Distances to disturbance points
The stated control accuracy of D applies to a straight and disturbance-free inflow. Fittings such as bends, branches or changes in cross-section cause turbulence that can influence the flow rate measurement.
For the VR1 volume flow controller to work optimally, the flows must be largely free of disturbance. After flow disturbance points (e.g. bends or branches), the straight inlet and outlet sections shown as examples must be observed; longer inlet sections may be required where several disturbance points occur consecutively. Otherwise significant control deviations must be expected.

Bend connection

Lu richtung air flow direction
Differenzdruck 30 … 600 Pa differential pressure
500 400 300 280

1400 1300
1200
1100 1000
900 800 700600

m³/h

Volumenstromregler VR1-N-250
volume flow controller

3 x DN

1,5 x DN

Branch-off from main duct

3 x DN

Volumenstromregler VR1-N-250
volume flow controller

Lu richtung air flow direction
Differenzdruck 30 … 600 Pa differential pressure
500 400 300 280

1400 1300
1200
1100 1000
900 800 700600

m³/h

1,5 x DN

The specified control accuracy of D can only be achieved with at least 3 x DN straight flow path.
Note: EN 1506 must be observed for the design of ventilation duct connections.

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Page 9 | 20

Technical Data
VR1 Volume Flow Controller

6 Technical Data

General data

Nominal diameter

DN 80, DN 100, DN 125, DN 160, DN 200, DN 250, DN 315

Flow rate range

50 … 3100 m³/h

Control range

Approx. 18 … 100 % of nominal flow rate

Control accuracy

±5 … ±10 % of set point flow rate

Differential pressure range

50 … 1000Pa

Flow velocity

2.1 … 15.5 m/s

Operating temperature

-20 … +70 °C, short-term +90 °C

Relative humidity

95 %, non-condensing

Casing tightness as per DIN EN 1751 Class C

Maintenance-free design

Yes

Materials

Casing + damper blade

Galvanised steel

Bearing shafts

Stainless steel

6.1 Dimensions

Ød
Volumenstromregler VR1-250
volume flow controller
45 122

Lu richtung air flow direction
Differenzdruck 30 … 600 Pa differential pressure
500 400 300 280

1400 1300
1200
1100 1000
900 800 700600

m³/h

L1
Nominal diameter [DN] 80 100 125 160 200 250 315

L
0d [mm] 79 99 124 159 199 249 314

L1
L [mm] 329 329 329 329 329 407 457

L1 [mm] 40 40 40 40 40 60 60

X
Manual: 65 mm Motorised: 130 mm

X
A [m²] A
0.005 0.008 0.012 0.020 0.031 0.049 0.078

Page 10 | 20

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Technical Data
VR1 volume flow controller

6.1.1 SRC duct silencer

L1

L1

L

6.2 Weights

Nominal diameter [DN] 80 100 125 160 200 250 315

Actuator M1 M2 M3

Weight [g] 660 660 630

VR1 [kg] 1.13 1.24 1.39 1.60 1.88 3.35 4.53

Ø DN Outer – Ø

Size [DN] 80 100 125 160 200 250 315

Outer diam. [mm] 200 200 225 260 300 355 415

L [mm] –

L1 [mm]

600

40

900

Acoustic insulation [kg] Lip seal [g]

0.73

20

0.88

26

1.07

32

1.33

40

1.84

52

2.45

64

3.60

88

SRC duct silencer [kg]

600 mm

900 mm

3.00

3.80

5.70

4.50

6.30

5.10

7.80

6.20

10.00

7.80

11.50

9.10

13.10

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Page 11 | 20

Technical Data
VR1 Volume Flow Controller

6.3 Sound power level (flow noise)

Sound power level LWA [dB(A)]

Static pressure drop pS [Pa]

1000
65 950 60

900

850

800 750

700

650

600

550 55 500

450

400

350 300 50

250

200 45
150

100 40

50

50

100

Flow rate [m³/h]

3

4

5

6

7

Flow

velocity

v A

[m/s]

DN 80
70

150

200

250

280

8

9

10 11 12 13 14 15

Static pressure drop pS [Pa]

1000
65 950

900 60

850

800 750

700

650

600 550 500 55

450

400

350

300 50 250

200

150 45

100 40
50

70

100

150

Flow rate [m³/h]

3

4

5

6

Flow

velocity

v A

[m/s]

DN 100
70

200

250

7

8

9

300

350 380

10 11 12 13

Static pressure drop pS [Pa]

1000
65 950

900

850

800 750

700
60 650

600

550

500

450

400 55
350
300

250

200 50
150

100 45

50

120

200

Flow rate [m³/h]

3

4

5

Flow

velocity

v A

[m/s]

DN 125

70

75

300

400

500

600

6

7

8

9

10

11

12 13

Static pressure drop pS [Pa]

1000
65 950

900

850

800 750

700 60
650

600

550

500

450

400 55
350
300

250

200 150

100

50

150 200

300

Flow rate [m³/h]

3

4

Flow

velocity

v A

[m/s]

DN 160
70

400

500

5

6

7

75

600

700

8

9

10

800

900

11

12

Page 12 | 20

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Technical Data
VR1 volume flow controller

Static pressure drop pS [Pa]

Sound power level LWA [dB(A)] 1000 70
950 65
900
850
800 750
700
650
600
550 60
500
450
400
350
300 55
250
200 150
50 100
45 50
250 300 400 500 600 Flow rate [m³/h]

DN 200
700 800

3

4

5

6

7

Flow

velocity

v A

[m/s]

75

900 1000 1100 1200 1300

8

9

10

11

Static pressure drop pS [Pa]

1000 70
950
900
850
800 65
750
700
650
600
550
500
450 60
400
350
300
250 55
200
150 50
100 45
50 400 500 Flow rate [m³/h]

DN 250
75

1000

1500

2000 2100

3

4

5

Flow

velocity

v A

[m/s]

6

7

8

9

10

11

Static pressure drop pS [Pa]

1000 70
950

900

850

800
750 65
700

650

600 550

500

450

400 60
350

300

250 55
200
150 50
100

50

600

1000

Flow rate [m³/h]

3

4

Flow

velocity

v A

[m/s]

DN 315

75

80

1500

5

6

2000

2500

7

8

9

3000 3100

10

11

Nomenclature

[m³/h]

AA v

[m²] [m/s]

DDA pp S

[Pa] [Pa]

LWA DLWL-oct

[dB(A)] [dB] [dB]

f

[Hz]

L

[dB]

p
LpA

[dB(A)]

Flow rate

Inflow cross-section

Flow velocity in Static pressure

dArAop

Differential pressure

A-weighted sound power level

OROecclttaaatvviveeesmsooiudun-ndfrdeppqoouwweenercrlyelevveel lLtWo-oLctW=A LWA + DL

Sound pressure level

A-weighted sound pressure level

Example:
Specified: Size Flow rate Flow velocity Static pressure drop
Result: Flow noise Sound power level

DN 250 = 1200 m³/h vA = 6.79 m/s DpS= 277 Pa
L = 65 dB(A) WA

· The sound power levels of the flow noise can be further reduced by using the SRC duct silencer. Further information Page 7
· The sound power levels inside the connecting duct are calculated in the nomograms as A-weighted overall levels LWA.
· Corresponding octave sound power levels LW-oct for each size and for all operating points are derived from the Wildeboer dimensioning software WiDim; likewise the dimensioning with additional SRC duct silencer.
· Important: The sound levels indicated in the nomograms are stated as sound power levels! They represent the sound energy introduced into the duct system. They are used for acoustic calculations, e.g. when adding sound attenuators.
· Please note: In many cases, the sound pressure levels Lp or LpA are specified, which give attenuations of up to 16 dB. When comparing numerical values, always bear in mind the difference between the sound power level and sound pressure level. Furthermore, the degree of attenuation is only obtained with specific connected ducts, deflections, branches and rooms.

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Page 13 | 20

Technical Data
VR1 Volume Flow Controller

6.4 Sound power level (radiated noise)
Sound power level LWA [dB(A)]

Static pressure drop pS [Pa]pS [Pa]

1000
950 40
900
850
800 35
750
700
650
600
550
500
450 30
400
350
300
250 25
200
150 20
100
50 50

45 100

Flow rate [m³/h]

3

4

5

6

7

Flow

velocity

v A

[m/s]

DN 80

50

55

150

200

250

280

8

9

10 11 12 13 14 15

Static pressure drop pS [Pa]

1000 45
950

900

850

800 40
750

700

650

600

550 35
500

450

400

350 30
300

250 25
200

150 20
100

50

70

100

150

Flow rate [m³/h]

DN 100
50

200

250

3

4

5

6

7

8

9

Flow

velocity

v A

[m/s]

55

300

350 380

10 11 12 13

Static pressure drop pS [Pa]

1000 50
950

900

850

800

750

700

650 45
600

550

500

450

400 40
350

300

250 35
200

150

30 100

25 50

120

200

Flow rate [m³/h]

3

4

5

Flow

velocity

v A

[m/s]

DN 125
55

300

400

500

600

6

7

8

9

10

11

12 13

Static pressure drop pS [Pa]

1000 55
950

900 50
850

800

750

700

650

600

550 45
500

450

400

350

300 40
250

200

150

35

100

30 50

150 200

300

Flow rate [m³/h]

DN 160

400

500

3

4

5

Flow

velocity

v A

[m/s]

6

7

60

600

700

8

9

10

800

900

11

12

Page 14 | 20

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Technical Data
VR1 volume flow controller

Sound power level LWA [dB(A)]

Static pressure drop pS [Pa]

1000 55
950
900
850
800
750
700
650 50
600
550
500
450
400
350 45
300
250
200 40
150
100 35 50
250 300 400 500
Flow rate [m³/h]

DN 200
60
600 700 800

3

4

5

6

7

Flow

velocity

v A

[m/s]

900 1000 1100 1200 1300

8

9

10

11

Static pressure drop pS [Pa]

1000 60
950 55
900
850
800
750
700
650
600 50
550
500
450
400
350 45
300
250
200 40
150 35
100
50 400 500
Flow rate [m³/h]

DN 250 1000

3

4

5

Flow

velocity

v A

[m/s]

6

7

65

1500

2000 2100

8

9

10

11

Static pressure drop pS [Pa]

1000

950

900

850

800

750

700

650

600

550

500

450

400

350

300

250

200

150

100

50

600

1000

Flow rate [m³/h]

3

4

Flow

velocity

v A

[m/s]

DN 315

1500

2000

2500

5

6

7

8

9

Example:
Specified: Size Flow rate Flow velocity Static pressure drop
Result: Radiated noise Sound power level

DN 250 = 1200 m³/h v = 6.79 m/s
A
Dp = 400 Pa S
LWA= 55 dB(A)

3000 3100

· The sound power levels of the radiated noise can be further reduced by using acoustic insulation. Further information Page 7
· The sound pressure level can be further reduced by carrying out additional sound attenuation measures on site (suspended ceilings, high degree of room attenuation).

10

11

Nomenclature

[m³/h]

AA v

[m²] [m/s]

DDA pp S

[Pa] [Pa]

LWA DLWL-oct

[dB(A)] [dB] [dB]

f

[Hz]

L

[dB]

p
LpA

[dB(A)]

Flow rate

Inflow cross-section

Flow velocity in Static pressure

dArAop

Differential pressure

A-weighted sound power level

OROecclttaaatvviveeesmsooiudun-ndfrdeppqoouwweenercrlyelevveel lLtWo-oLctW=A LWA + DL

Sound pressure level

A-weighted sound pressure level

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Page 15 | 20

Technical Data
VR1 Volume Flow Controller

6.5 Set point adjustment
6.5.1 Manual
In the basic version, VR1 volume flow controllers are designed for manual adjustment of the flow rate set point and operate without any auxiliary power supply. The volume flow set point is preselected on an adjusting device and, with variable pressures, is kept constant to a high degree of accuracy. The volume flow controllers are adjusted at the factory for the entire volume flow range.

6.5.2 Motorised

As an option, the set point adjustment can be motorised via factory-mounted electric actuators. Reversible actuators and continuously controllable reversible actuators are available for this.

Actuator and actuator size

Voltage

Electrical connection

AC tolerance

DC

Connected

tolerance

load

Wires

Power Run

Run time for 90°
Actuator

Manual adjustment

M1

230 V AC 85 … 265 V

M2 5 Nm 24V AC/DC

19.2 … 28.8 V

M3

24V AC/DC

19.2 … 28.8 V

3.5 VA 1.5 VA 2 VA

3 x 0.75 mm², 1 m long
4 x 0.75 mm², 1 m long

1.5 W 1 W

< 150 s

Pushbutton, lockable

Reversible actuators (M1, M2) open and close the volumetric flow controllers with 230 V AC voltage or 24 V DC or AC voltage.
The M1 (230VAC) and M2 (24VAC/DC) actuators enable 2-point and 3-point control. The corresponding motor limit stops are positioned in order to adjust the two flow rates. As delivered, the two limit stops of the actuators are set to the 0 direction of travel and the largest possible angle of rotation. The maximum angle of rotation corresponds to the largest possible flow rate set point, and the minimum is equivalent to a “cutoff” at a residual leakage that is significantly lower than the minimum flow rate. This can be extended to give 3-point control using an additional 0 circuit arrangement. When operated in this way, the actuator remains in its current position and the VR1 volume flow controller adjusts the corresponding set point.

Continuously adjustable reversible actuator (M3) with 24 V AC/DC sets the volume flow controllers to any desired position. The position is specified by means of a command signal of 0 or 2 to 10 V, position feedback via an output signal of 2 to 10 V.
The M3 (24VAC/DC) actuator enables continuous set point adjustment. The actuator is controlled with a setting voltage of Y = 0 … 10 V DC and moves to the position specified by the control signal; however, the operating range of the motor only starts at 2 V. The flow rate set point changes almost linearly with the setting voltage. As delivered, the actuator is set to 0 direction of travel and the adjustable mechanical limit stops are set for the largest possible angle of rotation, which means that when Y = 10 V, the maximum angle of rotation corresponds to the maximum volume flow set point, and at 0…2 V the minimum angle of rotation is approached; this corresponds to a “cutoff” at a residual leakage that is significantly lower than the minimum volume flow set point. The purpose of the checkback voltage U = 2 … 10VDC is to provide an electric indication of the volume flow set point setting and to serve as a subsequent actuating signal for other actuators.

Notes · All the actuators are overload-proof, do not require limit switches, and stop automatically at the limit stop. · In the event of a power failure or interruption, the current actuator position is retained. · The direction of travel of all the adjusting actuators can be reversed via a pushbutton on the motor.

Page 16 | 20

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Technical Data
VR1 volume flow controller

Presetting Depending on the nominal diameter, the flow rate set point can be preset at the factory in the following increments.

Nominal diameter [DN] 80 100 125 160 200 250 315

Flow rate set pointmin 50 70 120 150 250 400 600

Flow rate set pointmax 280 380 600 900 1300 2100 3100

Increments 10 10 20 25 50 100 100

Electrical connection M1: 2- point control
N L1 230 V AC
1 23

M1: 3- point control

N

L 230 V AC

0

12

3

M1: Direction of travel

1 23

00

1

1

stop stop

M2: 2- point control 24 V AC 24 V DC
123

M2: 3- point control
24 V AC 24 V DC

0

12

3

M2: Direction of travel

1 23

00

1

1

stop stop

M3: Continuous control

24 V AC / DC

(-) Y (+)
U

2 … 10 V 2 … 10 V

1 235

M3: Direction of travel

1 23

00

1

1

2 V

10 V

M3: Direction of travel

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Page 17 | 20

Specification text
VR1 Volume Flow Controller

7 Specification text

Maintenance-free, circular volume flow controller for position-independent installation in circular ventilation ducts for supply and exhaust air in ventilation and air conditioning systems. Casing and control mechanism made of galvanized sheet steel, with acoustic insulation, with lip seals. With centrally supported damper blade for volume flow control, with stainless steel bearing shaft in special bushes. Adjustment device with rotary pointer, scale and locking device for the volume flow set point, can be adjusted manually or by actuator. Volume flow controller designed as mechanical controller for constant volume flows without any auxiliary power supply. With special control mechanism for a high degree of control accuracy throughout the entire control range. The volume flow set point must be infinitely adjustable throughout the control range. With variable pressures between 50 and 1000 Pa, the volume flow must be kept constant with a deviation of roughly ±5 % to ±10 %. Casing tightness class C as per DIN EN 1751. Certificate as proof of compliance with the hygiene requirements as per VDI 6022-1, VDI 3803-1, DIN 1946-4, DIN EN 16798-3, SWKI VA104-01, SWKI VA105-01, ÖNORM H6020 and ÖNORM H6021. With Environmental Product Declaration as per ISO 14025 and EN 15804.

……..

pcs.

Volume flow:

………

m³/h

Pressure drop:

………

Pa

Maximum sound power level

Flow noise

………

including SRC duct silencer

Radiated noise

………

dB(A) dB(A)

Manufacturer:

WILDEBOER

Type: VR1

Size: ………

Complete with fixings deliver:

……….

install:

……….

……….

……..

pc. SRC 600 / 900 duct silencer

deliver:

……….

install:

……….

……….

Delete text not printed in bold as required!

You can find this tender text on the website www.ausschreiben.de ausschreiben.de. Or you can use the specification text customised for your product selection in the Wildeboer Configurator Wildeboer Configurator.

Page 18 | 20

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Wildeboer makes it easy
VR1 volume flow controller
8 Wildeboer makes it easy 8.1 Wildeboer Configurator
· Quick, intuitive configuration of Wildeboer products · Easy calculation of operating point data for the configured
product · 3D display of the product and download in various formats · Download of data sheets, specification texts and version keys · Login area with individual price display option
8.2 WiDim dimensioning software
· Functional, modern and intuitive dimensioning of Wildeboer products
· Conveniently collect operating point data, 3D product views, suitable accessories and current revision documents in a single project
· Project can be output in various formats · A GAEB interface and an interface based on VDI 3805 facilitate
a continuous planning process
8.3 Documents online
· Paperless and environmentally friendly online access to Wildeboer documents
· All documents in one central location and always up to date · Supporting interactive formats and content

3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00

Page 19 | 20

Always there for you
Locations & contact

Factory – Administration +49 4951 950-0 info@wildeboer.de www.wildeboer.de
Weener
Utrecht

Hamburg Hanover

Berlin

Cologne
Utrecht office +31 30 767 0150 info@utrecht.wildeboer.eu www.wildeboer.de/nl

Frankfurt

Ulm office +49 7392 9692-0 info@ulm.wildeboer.de www.wildeboer.de

Stuttgart

Ulm

Leipzig
Leipzig office +49 34444 310-0 info@leipzig.wildeboer.de www.wildeboer.de
Munich
Find out more at www.wildeboer.de/downloads

c6584.003.001-09_vr1_ahb_3.1_en_00-00

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals