WILDEBOER VR1 Volume Flow Controller User Manual
- September 14, 2024
- WILDEBOER
Table of Contents
VR1 Volume Flow Controller
Specifications
- Product: Volume flow controller VR1
- Flow Rate Range: 30 to 600 Pa
- Nominal Diameter: DN 80 to DN 315
- Flow Velocity: 1.1 to 12.2 m/s
- Control Accuracy: Set point flow rate
Product Overview
The VR1 volume flow controller is designed to regulate air flow
in ventilation systems efficiently.
Product Features
-
Dimensions: Available in various nominal
diameters from DN 80 to DN 315. -
Lip Seal: Ensures an airtight connection to
ventilation ducts. -
Set Point Adjustment: Allows for precise flow
rate control. -
Accessories: Optional accessories for factory
or on-site installation.
Product Description
The VR1 volume flow controller comes with acoustic insulation
with a sheet metal jacket for noise reduction and an SRC duct
silencer for enhanced performance.
Quick Dimensioning
Refer to the provided dimensions guide for proper installation
and optimal performance.
Installation
Follow these steps for proper installation:
-
Ensure proper distances to disturbance points as per
guidelines. -
Securely connect the volume flow controller to the ventilation
duct. -
Adjust the set point according to desired flow rate.
Technical Data
Refer to the dimensions and specifications provided for detailed
technical information on the VR1 volume flow controller.
FAQ
Q: What is the operating temperature range for the VR1 volume
flow controller?
A: The operating temperature range is specified in the user
manual. Please refer to the manual for detailed information.
Q: What are the areas of application for the different VR1
product variants?
A: The VR1-N is a mechanical controller, VRL1 is a mechanical
limiter, VRE1 is an electronic controller, and VRup/VRpro is an
electronic controller. Each variant has specific pressure
difference and flow rate ranges suitable for different
applications. Please refer to the product portfolio for more
details.
USER MANUAL
AIR DISTRIBUTION
Volume flow controller VR1
Trust you can build in.
Contents
VR1 volume flow controller
Contents
1
Product overview
3
2
Product features
4
3
Product description
6
3.1 Area of application
………………………………………………………………………………………………………………………………………………………………………………………… 6 3.2
Function……………………………………………………………………………………………………………………………………………………………………………………………………………….7
3.3
Accessories………………………………………………………………………………………………………………………………………………………………………………………………………….7
3.3.1 Acoustic insulation with sheet metal
jacket……………………………………………………………………………………………………………………………………….7 3.3.2 SRC duct
silencer…………………………………………………………………………………………………………………………………………………………………………………………7
4
Quick dimensioning
8
5
Installation
9
5.1 Distances to disturbance points………………………………………………………………………………………………………………………………………………………………… 9
6
Technical Data
10
6.1 Dimensions
……………………………………………………………………………………………………………………………………………………………………………………………………… 10
6.1.1 SRC duct
silencer………………………………………………………………………………………………………………………………………………………………………………………..11
6.2
Weights……………………………………………………………………………………………………………………………………………………………………………………………………………….11
6.3 Sound power level (flow noise)
………………………………………………………………………………………………………………………………………………………………….. 12 6.4 Sound
power level (radiated noise)
………………………………………………………………………………………………………………………………………………………….14 6.5 Set point
adjustment
…………………………………………………………………………………………………………………………………………………………………………………….16
6.5.1 Manual
………………………………………………………………………………………………………………………………………………………………………………………………………….16
6.5.2
Motorised……………………………………………………………………………………………………………………………………………………………………………………………………..16
7
Specification text
18
8 8.1 8.2 8.3
Wildeboer makes it easy
19
Wildeboer Configurator ………………………………………………………………………………………………………………………………………………………………………………19 WiDim dimensioning software…………………………………………………………………………………………………………………………………………………………………..19 Documents online…………………………………………………………………………………………………………………………………………………………………………………………..19
Description Functional principle Pressure difference Flow rate range Nominal
diameter Flow velocity Control accuracy
Operating temperature Further information
VR1 Mechanical controller 50 .. 1000Pa 50 … 3100 m³/h DN 80 … DN 315 2.1 … 15.5 m/s ±5 … ±10 % of set point flow rate -20 … +70 °C, short-term 90 °C In this document
Product portfolio:
Areas of application for circular volume flow controllers and limiters
VR1-N
VRL1
VRE1
VRup / VRpro
Mechanical controller
Mechanical limiter
Electronic controller
Electronic controller
30 … 600Pa
30 … 300Pa
20 … 1000Pa
5 … 1000Pa
30 … 2300 m³/h
13 … 1060 m³/h
34 … 5430 m³/h
42 … 5430 m³/h
DN 80 … DN 315
DN 80 … DN 250 DN 100 … DN400 DN 100 … DN400
1.1 … 12.2 m/s
0.8 … 6 m/s
1.2 … 12 m/s
1.5 … 12 m/s
approx. ±5 % of nominal flow rate*
±5 … ±10 % of
±5 … ±15 % of
±5 … ±20 % of
nominal flow rate set point flow rate set point flow rate
-20 … +70 °C, short-term 90 °C
+10 … +50 °C
+5 … +60 °C
0 … +50 °C
LINK
LINK
LINK
LINK
- or ±10 % from set point flow rate (depending on which deviation is greater)
Page 2 | 20
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Overview
VR1 volume flow controller
1 Product overview
VR1 volume flow controllers are maintenance-free, mechanically self-actuating
controllers for supply air and exhaust air ducts with constant flow rates that
operate without any auxiliary power supply. They are used especially at low
flow velocities and variable pressures to keep the flow rate constant as per
the set point value. The flow rate is set using a manual setting device with
pointer, scale and locking mechanism. As an option, the VR1 can be fitted with
a 24 V AC/DC or 230 V AC actuator for motorised set point adjustment for
applications with variable flow rates.
· Highest control accuracy at variable pressures · Factory preset for the set
point flow rate · Adjustable on site · Position-independent installation ·
Maintenance-free design · Sizes DN 80 to DN 315 · Casing tightness: Class C as
per DIN EN 1751 · Volume flow range: 50 … 3100 m³/h · Pressure range: 50 …
1000Pa · Flow velocities: 2.1 … 15.5 m/s · Temperature range: -20 … +70 °C,
short-term +90 °C · Hygiene certificate:
VDI 6022-1, VDI 3803-1, DIN1946-4, DINEN16798-3, SWKIVA104-01, SWKIVA105-01,
ÖNORMH6020, ÖNORMH6021 · Environment Product Declaration: EPD-WIL-20150036
-ICA-EN · Options · Reversible actuator with 2-point and 3-point control for
setting to two flow
rate set points, 230 V AC or 24 V AC/DC · Continuously adjustable reversible
actuator for setting to any flow rate set
point, 24 V AC/DC · Acoustic insulation with sheet metal jacket · SRC duct
silencer in lengths: 600 mm and 900 mm · Lip seals at both ends
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Page 3 | 20
Product features
VR1 Volume Flow Controller
2 Product features
1 Dimensions
2 Lip seal
3 Set point adjustment
4 Accessories
1 Dimensions
Nominal diameter [DN] 80 100 125 160 200 250 315
2 Lip seal
For airtight connection to ventilation ducts Optional accessories pre-
assembled at the factory or for on-site installation
Page 4 | 20
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Product features
VR1 volume flow controller
3 Set point adjustment Manual (basic version)
Manual setting device with setting pointer, scale and locking mechanism: The
flow rate set point values are set manually using the setting pointer within
the ranges min to max. The controllers are adjusted at the factory for the
entire volume flow range. The VR1 can be preset at the factory before delivery
For this purpose, the flow rate set point values must be specified when
ordering. Subsequent adjustment on site is possible.
Pre-installed at the factory before delivery
Actuator-driven (optional version)
M1: Reversible actuator 230 V AC with 2-point and 3-point control. The
corresponding motor limit stops are positioned in order to adjust the flow
rates. Optional accessories pre-assembled at the factory or for on-site
installation
M2: Reversible actuator 24 V AC/ DC with 2-point and 3-point control. The
corresponding motor limit stops are positioned in order to adjust the flow
rates. Optional accessories pre-assembled at the factory or for on-site
installation
M3: Continuously adjustable reversible actuator 24 V AC/DC To adjust the flow
rates, a reference signal is used from 0 … 10 V. Optional accessories pre-
assembled at the factory or for on-site installation For details, please refer
to Page 16.
4 Accessories
Acoustic insulation with sheet metal casing to reduce the external sound
radiation of the volume flow controller (radiated noise) Optional accessories
pre-assembled at the factory or for on-site installation
For details, please refer to Page 7.
SRC duct silencer for reducing flow noise in the connected ventilation duct.
Packing thickness: 50 mm mineral wool lengths: 600 mm 900 mm Optional
accessories for on-site installation For details, please refer to Page 7.
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Page 5 | 20
Product description
VR1 Volume Flow Controller
3 Product description
The VR1 volume flow controller is made of galvanised steel. The damper blade
which controls the flow rate is centrally supported and has stainless steel
bearing shafts in special bushes. The manual setting device is fitted with a
setting pointer, scale and locking mechanism. Flow rate set points can be
adjusted manually or by actuator within the flow rate ranges min to max. The
special control mechanism ensures high control accuracy, so with variable
pressures, the flow rate can be kept constant over the entire pressure range.
The adjustable volume flow set points depend on the nominal diameter of the
VR1.
4
5
4
5
6
Lu richtung air flow direction
Differenzdruck 30 … 600 Pa differential pressure
500 400 300 280
1400 1300
1200
1100 1000
900 800 700600
m³/h
Volumenstromregler VR1-250
volume flow controller
1
2
3
Item
1 2 3
4 5 6
Description Duct casing Label with scale and air direction indicator
Manual setting device with setting pointer, scale and locking mechanism
Lip seal (optional) Acoustic insulation with sheet metal jacket (optional)
Damper blade
Size [DN] 80 100 125 160 200 250 315
[m³/h] min 50 70 120 150 250 400 600
[m³/h] max 280 380 600 900 1300 2100 3100
3.1 Area of application
The VR1 volume flow controller is used in supply air and exhaust air ducts of
ventilation and air conditioning systems.
Notes · VR1 volume flow controllers are adjusted for the entire scaled
application area. · The flow rate set point is set during installation by
turning the setting pointer to the desired value on the scale and
locking this setting. This does not affect the control accuracy. · Volume flow
controllers that are preset at the factory can be installed directly. The flow
rate set point can be changed at
a later date by releasing the locking mechanism. · The VR1 volume flow
controller and the optional SRC duct silencer are supplied separately.
Assembly is carried out on
site. · Installation and operating instructions for the VR1 are available on
the Internet at www.wildeboer.de.
Page 6 | 20
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Product description
VR1 volume flow controller
3.2 Function
The VR1 volume flow controller operates without any auxiliary power supply.
The air flow in the ventilation duct generates a torque in the closing
direction when it hits the damper blade. This torque is counterbalanced by the
restoring torque of a blade spring so that the flow rate can be kept constant
within the tolerances, even if the pressure differences change. Additional
damping bellows ensures vibration-free movement of the damper blade.
3.3 Accessories
3.3.1 Acoustic insulation with sheet metal jacket
Acoustic insulation with a sheet metal jacket is supplied factory-mounted or for on-site installation.
Maximum possible reduction in radiated noise as a function of the nominal diameter:
DN Reduction
80
100
125
160
-18 dB
200
250
315
3.3.2 SRC duct silencer
The SRC duct silencer is supplied separately. Assembly is carried out on site along with the volume flow controller.
Maximum possible reduction in flow noise as a function of the silencer length:
DN
Outer diameter [mm]
80
200
100
200
125
225
160
260
200
300
250
355
315
415
L [mm]
600
900
-22 dB
–
-22 dB
-25 dB
-22 dB
-25 dB
-21 dB
-24 dB
-19 dB
-24 dB
-18 dB
-22 dB
-15 dB
-19 dB
Packing thickness: 50 mm mineral wool
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Page 7 | 20
Quick dimensioning
VR1 Volume Flow Controller
4 Quick dimensioning
The quick dimensioning table shows the expected sound power level of the VR1.
Intermediate values can be interpolated for a rough estimate. The exact values
for different differential pressures can be taken from the Wildeboer
dimensioning software WiDim. WiDim
Sound level
Size
[DN] 80 80 80 100 100 100 125 125 125 160 160 160 200 200 200 250 250 250 315
315 315
Flow rate
[m³/h] 50 160 280 70 220 380 120 360 600 150 525 900 250 750 1300 400 1200
2100 600 1800 3100
Flow velocity
v [m/s] 2.8 8.8 15.5 2.5 7.8 13.4 2.7 8.1 13.6 2.1 7.3 12.4 2.2 6.6 11.5 2.3
6.8 11.9 2.1 6.4 11.0
Differential pressure
p [Pa] 75 100 150 75 100 150 75 100 150 75 100 150 75 100 150 75 100 150 75
100 150
Flow noise
Sound power level L [dB(A)] WA 38.97 51.77 60.12 39.56 52.05 60.2 41.95 53.97
61.75 41.38 54.6 62.57 43.57 55.35 63.37 45.41 57.15 65.22 46.66 58.32 66.2
Radiated noise
Sound power level L [dB(A)] WA <20 37.39 48.45 <20 35.43 46.86 25.15 39.14
47.66 28.87 40.12 47.01 31.99 40.82 47.74 29.98 42.85 50.6 32.67 45.69 53.41
The sound power level of the radiated noise can be further reduced by using
acoustic insulation.
The mean sound pressure level in the room is:
· 26 dB lower with acoustic insulation · 8 dB lower without acoustic
insulation
than the sound power levels specified in the nomograms LWA. The sound pressure
level can be further reduced by carrying out additional sound attenuation
measures on site (suspended ceilings, high degree of room attenuation).
However, the acoustic insulation can only achieve the stated values if
connected ventilation ducts are also suitably soundproofed (insulated).
The sound power level of the flow noise can be reduced by up to 25 dB by using an SRC duct silencer. Page 7.
Page 8 | 20
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Installation
VR1 volume flow controller
5 Installation
The VR1 volume flow controller is installed regardless of the position and in
the air direction indicated on the label. To ensure lasting functionality and
leak tightness, stress-free installation in ventilation ducts is a
prerequisite.
Space requirement
To enable the scale to be read and the commissioning and servicing work to be
carried out, sufficient space should be kept free in the area of any
attachments. Inspection openings of sufficient size may required so that the
attachments are easily accessible.
Set point adjustment: manual
Set point adjustment: motorised
approx. 12 cm
approx. 12 cm
approx. 20 cm
approx. 28 cm
approx. 28 cm
approx. 28 cm
5.1 Distances to disturbance points
The stated control accuracy of D applies to a straight and disturbance-free
inflow. Fittings such as bends, branches or changes in cross-section cause
turbulence that can influence the flow rate measurement.
For the VR1 volume flow controller to work optimally, the flows must be
largely free of disturbance. After flow disturbance points (e.g. bends or
branches), the straight inlet and outlet sections shown as examples must be
observed; longer inlet sections may be required where several disturbance
points occur consecutively. Otherwise significant control deviations must be
expected.
Bend connection
Lu richtung air flow direction
Differenzdruck 30 … 600 Pa differential pressure
500 400 300 280
1400 1300
1200
1100 1000
900 800 700600
m³/h
Volumenstromregler VR1-N-250
volume flow controller
3 x DN
1,5 x DN
Branch-off from main duct
3 x DN
Volumenstromregler VR1-N-250
volume flow controller
Lu richtung air flow direction
Differenzdruck 30 … 600 Pa differential pressure
500 400 300 280
1400 1300
1200
1100 1000
900 800 700600
m³/h
1,5 x DN
The specified control accuracy of D can only be achieved with at least 3 x DN
straight flow path.
Note: EN 1506 must be observed for the design of ventilation duct connections.
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Page 9 | 20
Technical Data
VR1 Volume Flow Controller
6 Technical Data
General data
Nominal diameter
DN 80, DN 100, DN 125, DN 160, DN 200, DN 250, DN 315
Flow rate range
50 … 3100 m³/h
Control range
Approx. 18 … 100 % of nominal flow rate
Control accuracy
±5 … ±10 % of set point flow rate
Differential pressure range
50 … 1000Pa
Flow velocity
2.1 … 15.5 m/s
Operating temperature
-20 … +70 °C, short-term +90 °C
Relative humidity
95 %, non-condensing
Casing tightness as per DIN EN 1751 Class C
Maintenance-free design
Yes
Materials
Casing + damper blade
Galvanised steel
Bearing shafts
Stainless steel
6.1 Dimensions
Ød
Volumenstromregler VR1-250
volume flow controller
45 122
Lu richtung air flow direction
Differenzdruck 30 … 600 Pa differential pressure
500 400 300 280
1400 1300
1200
1100 1000
900 800 700600
m³/h
L1
Nominal diameter [DN] 80 100 125 160 200 250 315
L
0d [mm] 79 99 124 159 199 249 314
L1
L [mm] 329 329 329 329 329 407 457
L1 [mm] 40 40 40 40 40 60 60
X
Manual: 65 mm Motorised: 130 mm
X
A [m²] A
0.005 0.008 0.012 0.020 0.031 0.049 0.078
Page 10 | 20
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Technical Data
VR1 volume flow controller
6.1.1 SRC duct silencer
L1
L1
L
6.2 Weights
Nominal diameter [DN] 80 100 125 160 200 250 315
Actuator M1 M2 M3
Weight [g] 660 660 630
VR1 [kg] 1.13 1.24 1.39 1.60 1.88 3.35 4.53
Ø DN Outer – Ø
Size [DN] 80 100 125 160 200 250 315
Outer diam. [mm] 200 200 225 260 300 355 415
L [mm] –
L1 [mm]
600
40
900
Acoustic insulation [kg] Lip seal [g]
0.73
20
0.88
26
1.07
32
1.33
40
1.84
52
2.45
64
3.60
88
SRC duct silencer [kg]
600 mm
900 mm
3.00
–
3.80
5.70
4.50
6.30
5.10
7.80
6.20
10.00
7.80
11.50
9.10
13.10
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Page 11 | 20
Technical Data
VR1 Volume Flow Controller
6.3 Sound power level (flow noise)
Sound power level LWA [dB(A)]
Static pressure drop pS [Pa]
1000
65 950 60
900
850
800 750
700
650
600
550 55 500
450
400
350 300 50
250
200 45
150
100 40
50
50
100
Flow rate [m³/h]
3
4
5
6
7
Flow
velocity
v A
[m/s]
DN 80
70
150
200
250
280
8
9
10 11 12 13 14 15
Static pressure drop pS [Pa]
1000
65 950
900 60
850
800 750
700
650
600 550 500 55
450
400
350
300 50 250
200
150 45
100 40
50
70
100
150
Flow rate [m³/h]
3
4
5
6
Flow
velocity
v A
[m/s]
DN 100
70
200
250
7
8
9
300
350 380
10 11 12 13
Static pressure drop pS [Pa]
1000
65 950
900
850
800 750
700
60 650
600
550
500
450
400 55
350
300
250
200 50
150
100 45
50
120
200
Flow rate [m³/h]
3
4
5
Flow
velocity
v A
[m/s]
DN 125
70
75
300
400
500
600
6
7
8
9
10
11
12 13
Static pressure drop pS [Pa]
1000
65 950
900
850
800 750
700 60
650
600
550
500
450
400 55
350
300
250
200 150
100
50
150 200
300
Flow rate [m³/h]
3
4
Flow
velocity
v A
[m/s]
DN 160
70
400
500
5
6
7
75
600
700
8
9
10
800
900
11
12
Page 12 | 20
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Technical Data
VR1 volume flow controller
Static pressure drop pS [Pa]
Sound power level LWA [dB(A)] 1000 70
950 65
900
850
800 750
700
650
600
550 60
500
450
400
350
300 55
250
200 150
50 100
45 50
250 300 400 500 600 Flow rate [m³/h]
DN 200
700 800
3
4
5
6
7
Flow
velocity
v A
[m/s]
75
900 1000 1100 1200 1300
8
9
10
11
Static pressure drop pS [Pa]
1000 70
950
900
850
800 65
750
700
650
600
550
500
450 60
400
350
300
250 55
200
150 50
100 45
50 400 500 Flow rate [m³/h]
DN 250
75
1000
1500
2000 2100
3
4
5
Flow
velocity
v A
[m/s]
6
7
8
9
10
11
Static pressure drop pS [Pa]
1000 70
950
900
850
800
750 65
700
650
600 550
500
450
400 60
350
300
250 55
200
150 50
100
50
600
1000
Flow rate [m³/h]
3
4
Flow
velocity
v A
[m/s]
DN 315
75
80
1500
5
6
2000
2500
7
8
9
3000 3100
10
11
Nomenclature
[m³/h]
AA v
[m²] [m/s]
DDA pp S
[Pa] [Pa]
LWA DLWL-oct
[dB(A)] [dB] [dB]
f
[Hz]
L
[dB]
p
LpA
[dB(A)]
Flow rate
Inflow cross-section
Flow velocity in Static pressure
dArAop
Differential pressure
A-weighted sound power level
OROecclttaaatvviveeesmsooiudun-ndfrdeppqoouwweenercrlyelevveel lLtWo-oLctW=A LWA + DL
Sound pressure level
A-weighted sound pressure level
Example:
Specified: Size Flow rate Flow velocity Static pressure drop
Result: Flow noise Sound power level
DN 250 = 1200 m³/h vA = 6.79 m/s DpS= 277 Pa
L = 65 dB(A) WA
· The sound power levels of the flow noise can be further reduced by using the
SRC duct silencer. Further information Page 7
· The sound power levels inside the connecting duct are calculated in the
nomograms as A-weighted overall levels LWA.
· Corresponding octave sound power levels LW-oct for each size and for all
operating points are derived from the Wildeboer dimensioning software WiDim;
likewise the dimensioning with additional SRC duct silencer.
· Important: The sound levels indicated in the nomograms are stated as sound
power levels! They represent the sound energy introduced into the duct system.
They are used for acoustic calculations, e.g. when adding sound attenuators.
· Please note: In many cases, the sound pressure levels Lp or LpA are
specified, which give attenuations of up to 16 dB. When comparing numerical
values, always bear in mind the difference between the sound power level and
sound pressure level. Furthermore, the degree of attenuation is only obtained
with specific connected ducts, deflections, branches and rooms.
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Page 13 | 20
Technical Data
VR1 Volume Flow Controller
6.4 Sound power level (radiated noise)
Sound power level LWA [dB(A)]
Static pressure drop pS [Pa]pS [Pa]
1000
950 40
900
850
800 35
750
700
650
600
550
500
450 30
400
350
300
250 25
200
150 20
100
50 50
45 100
Flow rate [m³/h]
3
4
5
6
7
Flow
velocity
v A
[m/s]
DN 80
50
55
150
200
250
280
8
9
10 11 12 13 14 15
Static pressure drop pS [Pa]
1000 45
950
900
850
800 40
750
700
650
600
550 35
500
450
400
350 30
300
250 25
200
150 20
100
50
70
100
150
Flow rate [m³/h]
DN 100
50
200
250
3
4
5
6
7
8
9
Flow
velocity
v A
[m/s]
55
300
350 380
10 11 12 13
Static pressure drop pS [Pa]
1000 50
950
900
850
800
750
700
650 45
600
550
500
450
400 40
350
300
250 35
200
150
30 100
25 50
120
200
Flow rate [m³/h]
3
4
5
Flow
velocity
v A
[m/s]
DN 125
55
300
400
500
600
6
7
8
9
10
11
12 13
Static pressure drop pS [Pa]
1000 55
950
900 50
850
800
750
700
650
600
550 45
500
450
400
350
300 40
250
200
150
35
100
30 50
150 200
300
Flow rate [m³/h]
DN 160
400
500
3
4
5
Flow
velocity
v A
[m/s]
6
7
60
600
700
8
9
10
800
900
11
12
Page 14 | 20
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Technical Data
VR1 volume flow controller
Sound power level LWA [dB(A)]
Static pressure drop pS [Pa]
1000 55
950
900
850
800
750
700
650 50
600
550
500
450
400
350 45
300
250
200 40
150
100 35 50
250 300 400 500
Flow rate [m³/h]
DN 200
60
600 700 800
3
4
5
6
7
Flow
velocity
v A
[m/s]
900 1000 1100 1200 1300
8
9
10
11
Static pressure drop pS [Pa]
1000 60
950 55
900
850
800
750
700
650
600 50
550
500
450
400
350 45
300
250
200 40
150 35
100
50 400 500
Flow rate [m³/h]
DN 250 1000
3
4
5
Flow
velocity
v A
[m/s]
6
7
65
1500
2000 2100
8
9
10
11
Static pressure drop pS [Pa]
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
600
1000
Flow rate [m³/h]
3
4
Flow
velocity
v A
[m/s]
DN 315
1500
2000
2500
5
6
7
8
9
Example:
Specified: Size Flow rate Flow velocity Static pressure drop
Result: Radiated noise Sound power level
DN 250 = 1200 m³/h v = 6.79 m/s
A
Dp = 400 Pa S
LWA= 55 dB(A)
3000 3100
· The sound power levels of the radiated noise can be further reduced by using
acoustic insulation. Further information Page 7
· The sound pressure level can be further reduced by carrying out additional
sound attenuation measures on site (suspended ceilings, high degree of room
attenuation).
10
11
Nomenclature
[m³/h]
AA v
[m²] [m/s]
DDA pp S
[Pa] [Pa]
LWA DLWL-oct
[dB(A)] [dB] [dB]
f
[Hz]
L
[dB]
p
LpA
[dB(A)]
Flow rate
Inflow cross-section
Flow velocity in Static pressure
dArAop
Differential pressure
A-weighted sound power level
OROecclttaaatvviveeesmsooiudun-ndfrdeppqoouwweenercrlyelevveel lLtWo-oLctW=A LWA + DL
Sound pressure level
A-weighted sound pressure level
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Page 15 | 20
Technical Data
VR1 Volume Flow Controller
6.5 Set point adjustment
6.5.1 Manual
In the basic version, VR1 volume flow controllers are designed for manual
adjustment of the flow rate set point and operate without any auxiliary power
supply. The volume flow set point is preselected on an adjusting device and,
with variable pressures, is kept constant to a high degree of accuracy. The
volume flow controllers are adjusted at the factory for the entire volume flow
range.
6.5.2 Motorised
As an option, the set point adjustment can be motorised via factory-mounted electric actuators. Reversible actuators and continuously controllable reversible actuators are available for this.
Actuator and actuator size
Voltage
Electrical connection
AC tolerance
DC
Connected
tolerance
load
Wires
Power Run
Run time for 90°
Actuator
Manual adjustment
M1
230 V AC 85 … 265 V
–
M2 5 Nm 24V AC/DC
19.2 … 28.8 V
M3
24V AC/DC
19.2 … 28.8 V
3.5 VA 1.5 VA 2 VA
3 x 0.75 mm², 1 m long
4 x 0.75 mm², 1 m long
1.5 W 1 W
< 150 s
Pushbutton, lockable
Reversible actuators (M1, M2) open and close the volumetric flow controllers
with 230 V AC voltage or 24 V DC or AC voltage.
The M1 (230VAC) and M2 (24VAC/DC) actuators enable 2-point and 3-point
control. The corresponding motor limit stops are positioned in order to adjust
the two flow rates. As delivered, the two limit stops of the actuators are set
to the 0 direction of travel and the largest possible angle of rotation. The
maximum angle of rotation corresponds to the largest possible flow rate set
point, and the minimum is equivalent to a “cutoff” at a residual leakage that
is significantly lower than the minimum flow rate. This can be extended to
give 3-point control using an additional 0 circuit arrangement. When operated
in this way, the actuator remains in its current position and the VR1 volume
flow controller adjusts the corresponding set point.
Continuously adjustable reversible actuator (M3) with 24 V AC/DC sets the
volume flow controllers to any desired position. The position is specified by
means of a command signal of 0 or 2 to 10 V, position feedback via an output
signal of 2 to 10 V.
The M3 (24VAC/DC) actuator enables continuous set point adjustment. The
actuator is controlled with a setting voltage of Y = 0 … 10 V DC and moves to
the position specified by the control signal; however, the operating range of
the motor only starts at 2 V. The flow rate set point changes almost linearly
with the setting voltage. As delivered, the actuator is set to 0 direction of
travel and the adjustable mechanical limit stops are set for the largest
possible angle of rotation, which means that when Y = 10 V, the maximum angle
of rotation corresponds to the maximum volume flow set point, and at 0…2 V the
minimum angle of rotation is approached; this corresponds to a “cutoff” at a
residual leakage that is significantly lower than the minimum volume flow set
point. The purpose of the checkback voltage U = 2 … 10VDC is to provide an
electric indication of the volume flow set point setting and to serve as a
subsequent actuating signal for other actuators.
Notes · All the actuators are overload-proof, do not require limit switches, and stop automatically at the limit stop. · In the event of a power failure or interruption, the current actuator position is retained. · The direction of travel of all the adjusting actuators can be reversed via a pushbutton on the motor.
Page 16 | 20
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Technical Data
VR1 volume flow controller
Presetting Depending on the nominal diameter, the flow rate set point can be preset at the factory in the following increments.
Nominal diameter [DN] 80 100 125 160 200 250 315
Flow rate set pointmin 50 70 120 150 250 400 600
Flow rate set pointmax 280 380 600 900 1300 2100 3100
Increments 10 10 20 25 50 100 100
Electrical connection M1: 2- point control
N L1 230 V AC
1 23
M1: 3- point control
N
L 230 V AC
0
12
3
M1: Direction of travel
1 23
00
1
1
stop stop
M2: 2- point control 24 V AC 24 V DC
123
M2: 3- point control
24 V AC 24 V DC
0
12
3
M2: Direction of travel
1 23
00
1
1
stop stop
M3: Continuous control
24 V AC / DC
(-) Y (+)
U
2 … 10 V 2 … 10 V
1 235
M3: Direction of travel
1 23
00
1
1
2 V
10 V
M3: Direction of travel
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Page 17 | 20
Specification text
VR1 Volume Flow Controller
7 Specification text
Maintenance-free, circular volume flow controller for position-independent installation in circular ventilation ducts for supply and exhaust air in ventilation and air conditioning systems. Casing and control mechanism made of galvanized sheet steel, with acoustic insulation, with lip seals. With centrally supported damper blade for volume flow control, with stainless steel bearing shaft in special bushes. Adjustment device with rotary pointer, scale and locking device for the volume flow set point, can be adjusted manually or by actuator. Volume flow controller designed as mechanical controller for constant volume flows without any auxiliary power supply. With special control mechanism for a high degree of control accuracy throughout the entire control range. The volume flow set point must be infinitely adjustable throughout the control range. With variable pressures between 50 and 1000 Pa, the volume flow must be kept constant with a deviation of roughly ±5 % to ±10 %. Casing tightness class C as per DIN EN 1751. Certificate as proof of compliance with the hygiene requirements as per VDI 6022-1, VDI 3803-1, DIN 1946-4, DIN EN 16798-3, SWKI VA104-01, SWKI VA105-01, ÖNORM H6020 and ÖNORM H6021. With Environmental Product Declaration as per ISO 14025 and EN 15804.
……..
pcs.
Volume flow:
………
m³/h
Pressure drop:
………
Pa
Maximum sound power level
Flow noise
………
including SRC duct silencer
Radiated noise
………
dB(A) dB(A)
Manufacturer:
WILDEBOER
Type: VR1
Size: ………
Complete with fixings deliver:
……….
install:
……….
……….
……..
pc. SRC 600 / 900 duct silencer
deliver:
……….
install:
……….
……….
Delete text not printed in bold as required!
You can find this tender text on the website www.ausschreiben.de ausschreiben.de. Or you can use the specification text customised for your product selection in the Wildeboer Configurator Wildeboer Configurator.
Page 18 | 20
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Wildeboer makes it easy
VR1 volume flow controller
8 Wildeboer makes it easy 8.1 Wildeboer Configurator
· Quick, intuitive configuration of Wildeboer products · Easy calculation of
operating point data for the configured
product · 3D display of the product and download in various formats · Download
of data sheets, specification texts and version keys · Login area with
individual price display option
8.2 WiDim dimensioning software
· Functional, modern and intuitive dimensioning of Wildeboer products
· Conveniently collect operating point data, 3D product views, suitable
accessories and current revision documents in a single project
· Project can be output in various formats · A GAEB interface and an interface
based on VDI 3805 facilitate
a continuous planning process
8.3 Documents online
· Paperless and environmentally friendly online access to Wildeboer documents
· All documents in one central location and always up to date · Supporting
interactive formats and content
3.11 User manual – VR1 volume flow controller (C6584.003.001-09) – Version 00-00
Page 19 | 20
Always there for you
Locations & contact
Factory – Administration +49 4951 950-0 info@wildeboer.de www.wildeboer.de
Weener
Utrecht
Hamburg Hanover
Berlin
Cologne
Utrecht office +31 30 767 0150 info@utrecht.wildeboer.eu www.wildeboer.de/nl
Frankfurt
Ulm office +49 7392 9692-0 info@ulm.wildeboer.de www.wildeboer.de
Stuttgart
Ulm
Leipzig
Leipzig office +49 34444 310-0 info@leipzig.wildeboer.de www.wildeboer.de
Munich
Find out more at www.wildeboer.de/downloads
c6584.003.001-09_vr1_ahb_3.1_en_00-00
References
- Ausschreibungstexte kostenlos zum Download - AUSSCHREIBEN.DE
- Wildeboer Bauteile GmbH
- Wildeboer Bauteile GmbH
- Ausschreibungstexte kostenlos zum Download - AUSSCHREIBEN.DE
- Wildeboer Bauteile GmbH
- Wildeboer Bauteile GmbH
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>