MITSUBISHI ELECTRIC TPEFYW027MA1W0A HVRF Ducted System Owner’s Manual

September 11, 2024
Mitsubishi Electric

MITSUBISHI ELECTRIC TPEFYW027MA1W0A HVRF Ducted System

Product Usage Instructions

Installation:

  1. Ensure proper spacing for maintenance at the bottom of the unit.
  2. Use an M10 screw for suspension bolt installation.
  3. For units with multiple fans, follow the specific instructions provided.

Maintenance

  1. Regularly clean or replace the air filter as needed.
  2. Check drain pipes and lift mechanism for any blockages or Vleaks.

Operation:

  1. Use the appropriate HBC Controller for system control.
  2. Ensure proper water pipe connections for efficient operation.

Frequently Asked Questions

  • Q: What should I do if the unit is not cooling/heating properly?
    A: Check the air filter for blockages and ensure proper airflow. Additionally, verify that the power source is stable and the settings are correct on the HBC Controller.

  • Q: How often should I clean the air filter?
    A: It is recommended to clean or replace the air filter every 1-2 months depending on usage and environmental conditions.

Job Name:
System Reference:
Date:

GENERAL FEATURES

  • Dual set point functionality
  • Multiple fan speed settings
  • Auto fan mode
  • 9-7/8” (250mm) high for low ceiling heights
  • uilt-in condensate lift; lifts to 27-9/16” (700 mm)
  • Ducted fan coil supporting multiple configurations for flexible installation
  • Hydronic-based indoor coil
  • Built-in Manual Air Vent

Specifications

Specifications System
Unit Type TPEFYW027MA1W0A
Cooling capacity (Nominal)1 BTU/H
Heating capacity (Nominal)1 BTU/H
Power source Voltage, Phase, Hertz

Power Consumption

| Cooling| kW| 0.142
Heating| kW| 0.140

Current

| Cooling| A| 1.24/1.12
Heating| A| 1.24/1.12
MCA| A| 2.88/2.88
Maximum Overcurrent Protection (MOCP)| A| 15
Recommended Fuse Size| A| 15
External finish| Galvanized Steel Plate
External Dimensions| In. [mm]| 43-5/16 x 28-7/8 x 9-7/8 [1,100 x 732 x 250]
Net weight| Lbs [kg]| 67 [30]
Heat exchanger| Cross fin (Aluminum fin and copper tube)

Fan

| Type x quantity| Sirocco fan x 2

External Static pressure

|

in.WG

| Selectable;

0.14, 0.2, 0.28, 0.4, 0.6 In. WG;

factory set to Factory set to 0.2 In. WG

Airflow rate| CFM| 618–742–883
Motor type| DC brushless motor
Motor Output| kW| 0.121
Motor FLA| A| 1.4
Sound pressure level (Measured in anechoic room)| dB(A)| 31–35–39
Air filter| PP Honeycomb fabric (washable)
Diameter of drain pipe| In. [mm]| O.D. 1-1/4 [32]
Drain lift mechanism| In. [mm]| 27-9/16 [700]
Connectable HBC Controller| CMB-WP-NU-AA, CMB-WP-NU-AB
Design Pressure| PSI (Mpa)| 145/1

Diameter of Water Pipe Connections (O.D.)

| Supply Connection (O.D.)| mm| 22
Return Connection (O.D.)| mm| 22
Water Volume| Gallons (Liters)| 0.554 (2.1)

NOTES:

  • Cooling | Indoor: 81° F (27° C) DB / 66° F (19°C) WB; Outdoor 95° F (35° C) DB
  • Heating | Indoor: 68° F (20° C) DB; Outdoor 45° F (7° C) DB / 43° F (6° C) WB

ACCESSORIES

INDOOR UNIT ACCESSORIES: TPEFYW027MA1W0A

Control Interface Deluxe Wired MA Remote Controller □ TAR-41MAAU

Wired Remote Controller

| Simple MA Remote Controller†| □ TAC-YT53CRAU-J
Smart ME Remote Controller – Backlit touchscreen| □ TAR-U01MEDU-K
Touch MA Controller†| □ TAR-CT01MAU-SB

Wireless Remote Controller

| Wireless MA Remote Controller| □ TAR-FL32MA-E
Wireless Remote Contoller| □ PAR-SL101A-E

Condensate

| Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended]| □| X87-721
Blue Diamond (MaxiBlue Advanced) Mini Condensate Pump w/ Reservoir & Sensor (110V) up to 48,000 BTU/H [recommended]| □|

X87-711

Blue Diamond (MegaBlue Advanced) Condensate Pump w/ Reservoir & Sensor| □| X87-835
Blue Diamond Alarm Extension Cable — 6.5 Ft.| □| C13-192
Blue Diamond MultiTank — collection tank for use with multiple pumps| □| C21-014
Blue Diamond Sensor Extension Cable — 15 Ft.| □| C13-103
Drain Pan Level Sensor/Control| □ SS610E
Sauermann Condensate Pump| □| SI30-230

Control Interface

| 3-Pin Connector| □ PAC-715AD
CN24 Relay Kit| □ CN24RELAY-KIT-CM3
Connector and wire for Operation status/error using CN51| □ PAC-725AD
Disconnect Switch| (30A/600V/UL) [fits 2” X 4” utility box] – White| □ TAZ- MS303W
Filter Box| Filter Box with MERV 13 Filter| □ FBM2-3-A

HBC Controller

| Hybrid VRF Main BC 16 Port| □ TCMBM1016VA11N4
Hybrid VRF Main BC 8 Port| □ TCMBM0108VA11N4
Hybrid VRF Sub BC 16 Port| □ TCMBS1016VB11N4
Hybrid VRF Sub BC 8 Port| □ TCMBS0108VB11N4

HVRF Accessories

| (2x) Isolation Ball Valve and (2x) 22mm Compression Fitting| □ KIT2-NA10883-CAL
25mm Isoflow Multi, 25m Coil w/ 1” Titan| □| 13630061001-REH
25mm PVDF SDR11 Sleeve (Box QTY 50)| □| 11803271001-REH
25mm SDR11 Coupling (Bag QTY 10)| □| 11690101001-REH
25mm SDR11 Elbow (Bag QTY 10)| □| 11691261001-REH
25mm SDR11 x 3/4” FPT Fitting (Bag QTY 1)| □| 15012451001-REH
25mm SDR11 x 3/4” MPT Fitting(Bag QTY 10)| □| 15012461001-REH
25mm x 25mm x 25mm SDR11 Tee(Bag QTY 10)| □| 11690561001-REH
25mm x 25mm x 25mm SDR11 Tee(Bag QTY 10)| □| 15012471001-REH
40mm Isoflow Multi, 5m Stick w/ 1.5” Titan| □| 13630071001-REH
40mm PVDF SDR11 Sleeve (Box QTY 25)| □| 11803291001-REH
40mm SDR11 Coupling (Bag QTY 5)| □| 11690151001-REH
40mm SDR11 Elbow (Box QTY 1)| □| 11691301001-REH
40mm SDR11 x 3/4” MPT Fitting (Box QTY 1)| □| 15012481001-REH
40mm x 40mm x 25mm SDR11 Tee (Bag QTY 1)| □| 11690691001-REH
Compact Discal AAV w/ Hydroscopic Cap and Drain Plug| □ KIT3-NA10884-CAL
Copper Press Tailpieces (3/4”)| □ KIT5-NA10881-CAL
Drain Valve w/ Brass NPT T-Fitting| □ KIT4-NA10885-CAL
RAUTOOL A-Light2 Kombi Tool KIT| □| 11094491001-REH

DIMENSIONS

INDOOR UNIT DIMENSIONS: TPEFYW027MA1W0A

TPEFYW06, 08, 12, 15, 18, 24, 27, 30, 36, 48MA1W0A

Unit: mm (in.)

FORM# TPEFYW027MA1W0A – 202405

Specifications are subject to change without notice.

© 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.