Heatit (Thermo-Floor) Heatit Z-Relay 25A HEAE4512554 Manual

September 9, 2024
Heatit (Thermo-Floor)

Heatit (Thermo-Floor)

Heatit Z-Relay 25A

SKU: HEAE4512554

Quickstart

This is a
secure
Relay
for
Europe
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
Clicking the inclusion button in the module

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

  • The Heatit Z-Relay is a Z-Wave module housed in a water-resistant casing with 10 membrane cable entries.
  • It features 1 relay output, 3 multi-purpose inputs, and a Z-Wave radio for wireless network interfacing.
  • The module requires a 230V AC mains power supply.
  • The relay output can be freely controlled via the Z-Wave network, suitable for controlling devices like valve actuators and stoves.
  • Two inputs can be configured as digital or analog for NTC temperature sensors, while the third can function as a digital input or connect to a flood sensor.
  • The module allows configuration of the status indicator LED on its circuit board.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

The Heatit Z-Relay can be factory reset by pressing the inclusion button in the module for at least 10 seconds.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Installation

  • Only authorized technicians should perform work involving 230V mains power, adhering to country-specific guidelines and norms.
  • Before assembly, ensure the power supply is switched off and safeguarded against reactivation.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Clicking the inclusion button in the module

Exclusion

Clicking the inclusion button in the module

Product Usage

Temperature inputs
Input 1 and 2 can be used as temperature inputs by connecting NTC sensors to the inputs. The type of NTC sensor can be configured by means of configuration parameters 3 and 4.A temperature offset can be configured for each of the inputs by means of configuration parameters 5 and 6.

Flood sensor input
Input 3 is a flood sensor input where it is possible to connect a simple flood sensor. The flood sensor can be left lying on the floor (on an electrically insulating surface), or attached to the floor or a wall. Designed for flood detection, it senses water and other electrically conductive liquids. The sensitivity of the sensor can be configured by means of configuration parameter 14.
It is possible for the flood input to directly control the Heatit Z-Relay output, either to turn the relay output ON or OFF when a flood is detected, or when no flood is detected, see configuration parameters 12 and 13.

Relay Output
The relay output is a high power “normally open” (NO) contact that can be used for several purposes. It is possible to control the relay from the Z-Wave network, or it can be controlled by the flood sensor input.
The Heatit Z-Relay monitors the current used by the load connected to the relay output. The energy that the load consumes is calculated by means of the measured current and the voltage entered in configuration parameter 15. Energy data is sent to the controller through the Z-Wave network. These data values that the controller is able to receive are: current (A), power (Watt), and the energy consumed over time (kWh).

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group Number Maximum Nodes Description
1 5 lifeline
2 5 Sensor Multilevel Report for input 1.
3 5 Sensor Multilevel Report for input 2.
4 5 Basic Report On / Off when the flood sensor detects a flood.
5 5 Basic Set On / Off when the flood sensor detects a flood
6 5 Notification Report when the flood sensor detects a flood.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Status LED.

Configuration of the status LED.

Size: 1 Byte, Default Value: 1

Setting Description
0 LED turned off.
1 LED turned on.
2 LED flashing at 1 second intervals (“½ Hz).
3 LED flashing at “½ second interval (1 Hz).

Parameter 2: LED brightness level

Configure the percentage of light in the status LED, when the LED is turned on.

Size: 1 Byte, Default Value: 50

Setting Description
1 – 100 Brightness level of the LED

Parameter 3: Thermistor type for input 1

Configures the thermistor type connected to input 1.

Size: 1 Byte, Default Value: 0

Setting Description
0 Input disabled.
1 10K NTC

Parameter 4: Thermistor type for input 2

Configures the thermistor type connected to input 2.

Size: 1 Byte, Default Value: 0

Setting Description
0 Input disabled.
1 10K NTC

Parameter 5: Temperature offset on input 1.

Configures a temperature offset that can be added to the measured temperature in order to get a more accurate measurement from the thermistor on input 1.
Size: 1 Byte, Default Value: 0

Setting Description

Parameter 6: Temperature offset on input 2.

Configures a temperature offset that can be added to the measured temperature in order to get a more accurate measurement from the thermistor on input 2.
Size: 1 Byte, Default Value: 0

Setting Description
-40 – 40 -4,0 – 4,0″°C.

Parameter 7: Time interval for reports sent about input 1.

Configures the time interval between when sensor reports are transmitted for input 1.

Size: 2 Byte, Default Value: 6

Setting Description

Parameter 8: Time interval for reports sent about input 2.

Configures the time interval between when sensor reports are transmitted for input 2.

Size: 2 Byte, Default Value: 6

Setting Description

Parameter 9: Time interval between notification reports for input 3.

Configures the time interval between when notification reports for flood input 3.
Size: 2 Byte, Default Value: 6

Setting Description
0 – 8640 0 – 86 400 seconds.

Parameter 10: Time interval between meter reports.

Configures the time interval between when meter reports for reporting the energy (kWh) consumed by the load connected to the relay output.

Size: 2 Byte, Default Value: 2

Setting Description
0 – 8640 0 – 86 400 seconds.

Parameter 11: Flood steady timer.

Configures the time that the flood input (input 3) has to be steady before the state is accepted as a valid state.gures the time that the flood input (input 3) has to be steady before the state is accepted as a valid state.

Size: 1 Byte, Default Value: 6

Setting Description
0 – 60 0 – 60 seconds.

Parameter 12: Auto relay on.

Configures internal states that will cause the relay to be turned on.

Size: 1 Byte, Default Value: 1

Setting Description
0 Relay is not turned on automatically.
1 The relay is turned on when a flood is detected.
2 The relay is turned on when no flood is detected.

Parameter 13: Auto relay off.

Configures internal states that will cause the relay to be turned off.

Size: 1 Byte, Default Value: 2

Setting Description
0 Relay is not turned off automatically.
1 The relay is turned off when a flood is detected.
2 The relay is turned off when no flood is detected.

Parameter 14: Flood detection threshold.

Configures the threshold for input 3 that will cause a flood to be detected.

Size: 2 Byte, Default Value: 2048

Setting Description
0 – 4095 Low value means a low detection threshold, high value will cause the

input to be more sensitive.

Parameter 15: Voltage

Configures the value used for power calculation, as only the current for the load on the relay output is measured.

Size: 1 Byte, Default Value: 220

Setting Description
0 – 250 Volt

Parameter 18: Size of load connected on the relay output.

Configures a constant value that will be used in power metering when this value is different from 0. This value specifies the actual load in Watt used for power metering.
Size: 2 Byte, Default Value: 0

Setting Description
0 – 6000 Watt

Technical Data

Dimensions 100 x 100 x 46 mm
Weight 223 gr
Hardware Platform ZM5101
EAN 7071236014126
IP Class IP 55
Voltage 230 V
Load 25 A
Device Type Relay
Generic Device Class Binary Switch
Firmware Version 00.08
Z-Wave Version 04.3d
Z-Wave Product Id 0x019b.0x0003.0x0208
Frequency Europe – 868,4 Mhz
Maximum transmission power 5 mW

Supported Command Classes

  • Basic
  • Switch Binary
  • Meter
  • Association Grp Info
  • Device Reset Locally
  • Zwaveplus Info
  • Multi Channel
  • Supervision
  • Configuration
  • Manufacturer Specific
  • Powerlevel
  • Firmware Update Md
  • Association
  • Version
  • Multi Channel Association
  • Security
  • Transport Service
  • Security 2

Controlled Command Classes

  • Transport Service
  • Security 2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Heatit (Thermo-Floor) User Manuals

Related Manuals