Heatit (Thermo-Floor) Heatit Z-TRM2fx HEAE5430555 Manual
- June 8, 2024
- Heatit (Thermo-Floor)
Table of Contents
- Heatit (Thermo-Floor)
- Heatit Z-TRM2fx
- SKU: HEAE5430555
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Installation
- Inclusion/Exclusion
- Product Usage
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: Operation Mode
- Parameter 2: Sensor mode
- Parameter 3: Floor sensor type
- Parameter 4: Temperature control hysteresis (DIFF I)
- Parameter 5: Floor minimum temperature limit (FLo)
- Parameter 6: Floor maximum temperature limit (FHi)
- Parameter 7: Air (A2) minimum temperature limit (ALo)
- Parameter 8: Air (A2) maximum temperature limit (AHi)
- Parameter 9: Heating mode setpoint (CO)
- Parameter 10: Energy saving mode setpoint (ECO)
- Parameter 11: Cooling setpoint (COOL)
- Parameter 12: Floor sensor calibration
- Parameter 13: External sensor calibration
- Parameter 14: Temperature display
- Parameter 15: Button brightnessdimmed state
- Parameter 16: Button brightnessactive state
- Parameter 17: Display brightnessdimmed state
- Parameter 18: Display brightnessactive state
- Parameter 19: Temperature report interval
- Parameter 20: Temperature report hysteresis
- Parameter 21: Meter report interval
- Parameter 22: Meter report delta value
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Heatit (Thermo-Floor)
Heatit Z-TRM2fx
SKU: HEAE5430555
Quickstart
This is a
secure
HVAC-Thermostat
for
Europe.
To run this device please connect it to your mains power supply.
Adding the device:To add the thermostat to your home automation gateway, press Center (confirm) for 10 seconds. The display will show OFF. Press Right (down) 4 times till you see Con in the display. Now start add device in your home automation software. Start adding mode by pressing Center (confirm) button for approximately 2 seconds. The icon will appear in the display. Adding Mode is indicated in the display by some circling LED segments in the display until the timeout occurs after 20 seconds or the module has been added in the network. Confirmation will show Inc/EcL in the display. If adding fails, Err (error) will appear.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
Heatit Z-TRM2fx is equipped with a single pole switch and it fits most System 55 frames (Elko RS16, Schneider Exxact, Gira, Jung etc.). The thermostat can withstand a load of max 13A /2900W at 230V. At higher” loads” the thermostat must control a” contactor. The thermostat may be connected to two wired external sensors. The thermostat has the capacity of up to 8 associations (relays, wall plugs etc.).The thermostat is designed for electrical heating.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
By pressing buttons Right and Center (down and confirm) for 20 seconds, the thermostat will perform a complete factory reset.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Installation
Now connect the wires to the thermostat”’s terminals:
Use 1,5mm”² or 2,5mm”² according to load.
HEATING (N) ” Heating cable connection (Neutral)
N ” Power connection (Neutral) 230V
L ” Power connection (Live) 230V
HEATING (L) ” Heating cable connection (Live)
PILOT ” 230V pilot signal (ECO temp)
FLOOR SENSOR ” NTC type (10, 12, 15, 22, 33 or 47kΩ).” Default 10kΩ.
EXTERNAL SENSOR ” NTC type (10, 12, 15, 22, 33 or 47kΩ).” Default 10kΩ.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
Press” Center ” (confirm)” for 10 seconds. The” display will show
OFF. ” Press” Right ” (down) 4 times till you see” Con ” in the
display.
Start ” adding mode” by ” pressing” Center (confirm) ” button”
for approximately 2 seconds.
Exclusion
Press” Center ” (confirm)” for 10 seconds. The” display will show
OFF. ” Press” Right ” (down) 4 times till you see” Con ” in the
display.
Start ” removing mode” by ” pressing” Center (confirm) ”
button” for approximately 2 seconds.
Product Usage
PROGRAMMING YOUR THERMOSTAT
To activate the programming mode, press Center (confirm) for 10 seconds. Now
the display will show OFF.”
Now you are in programming mode. To scroll up and down in the menu use button
1 and 3 (left and right) to navigate.”
To enter submenu press Center (confirm). Always confirm” your setting by pressing Center (confirm) for 2 seconds.
Menu:
OFF ” Turns the thermostat off.
Sensors:
F ” Choice of sensors
Depending on your choice of sensors, the menu will change.
SEn ” Select the right Ohm value for your external/floor sensor.” NTC type (10, 12, 15, 22, 33 or 47kΩ). Default 10kΩ.
CAE ” Calibration for external sensor.
CAF ” Calibration for floor sensor.
br1 ” Brightness of display can be adjusted in this menu.
Con ” Activation of inclusion/exclusion mode.
diF ” Hysteresis.
ALo ” Setting lowest allowed temperature (limitation).” (Airsensor)
AHI ” Setting highest allowed temperature (limitation).” (Airsensor)
FLO ” Setting lowest allowed temperature (limitation).” (Floor sensor)
FHI ” Setting highest allowed temperature (limitation).” (Floor sensor)
HEA ” Switch between heating and cooling function.
ESC ” Escape “– exit programming menu.
TEMPERATURE SHOWN IN DISPLAY
The temperature shown in the display is the actual temperature” for floor sensor and the external room sensor. You are able to” calibrate the sensor values.
CHOICE OF SENSOR
The thermostat has a range of choices when it comes to sensors. To get to the menu you have to press Center (confirm) for 10 seconds, then press Right (down) once and an F shows in the display. Then press Center (confirm) again and you can” choose one of these modes, while moving up and down with” buttons Left or Right.
F ” Floor sensor
A2 ” External room sensor
A2F ” External room sensor + Floor sensor
When you have decided on the sensor mode you want to use, press the Center (confirm) button. If you choose F without” having a floor sensor connected, Er4 will be shown in the display. If you choose A2 or A2F and there is no external sensor” installed, Er5 will be displayed on the screen.
NOTE: ” Wooden floors require that a floor sensor is connected in order to limit the floor temperature to a maximum of 27″°C” (in accordance with specifications from most wooden floor” manufacturers).
SELECT THE RIGHT OHM VALUE FOR YOUR EXTERNAL” FLOOR SENSOR
The following values are available: NTC type (10, 12, 15, 22, 33 or 47kΩ). Default 10kΩ. The function is only active when an external” sensor is connected. Confirm with Center (confirm) button.
CALIBRATION
In this mode you are able to adjust the displayed temperature. If the thermostat of some reason (or sensor) is not calibrated properly you are able to make minor changes to the temperature. You are able to raise/lower the set point by up to 4″°C. Confirm with Center (confirm) button. This function is only available for the floor sensor and external” room sensor.
BRIGHTNESS
Use Left and Right (up and down) button to adjust the” brightness between 0-9. Confirm with Center (confirm) button.
HYSTERESIS (DIF)
In this mode you are able to make changes to the hysteresis in the thermostat. This means that you can changes the hysteresis from 0,3″°C up to max 3,0″°C. Confirm with Center (confirm)” button. Default setting is 0,5″°C. When using a waterbased” heating, the recommended hysteresis is a minimum of 1,0″°C.
MIN/MAX TEMPERATURE SETTINGS
FLO ” Min Floor temperature
FHI ” Max Floor temperature
ALo ” Min Air/room temperature
AHI ” Max Air/room temperature” Confirm with Center (confirm)
HEA ” Choose whether the thermostat is to be used for heating” or cooling.
ESC ” Leaving programming mode.” Confirm with Center (confirm) button.
STANDBY AND MAIN SCREE N
When the thermostat remains untouched for a while, it will” automatically go to standby screen. Standby screen shows the temperature in the room or floor if the thermostat is connected to external sensors. By pressing Left or Right (up or down)” button the setpoint will be shown in the display.
DISPLAY ON/OFF – don/doF
Activate by pressing Left and Center (up and confirm) button for” 10 seconds. The display light is temporarily activated if one of” the buttons is pushed.
In case doF is activated, the screen will be blank (can be used if installed where people are sensitive to the light of the display). A very nice feature when used in a bedroom. When touching the display, the screen lights up.
CHILDLOCK – LOC
By pressing Left and Right (up and down) buttons for 10 seconds, child lock will be activated and no changes can be made. Trying to make changes causes the LOC text to appear in the display. Child lock is deactivated by pressing Left and Right (up and down) buttons for 10 seconds. OPn will appear” in the display.
FACTORY RESET – RES
By pressing buttons Right and Center (down and confirm) for 20 seconds, the thermostat will perform a complete factory reset. NB! Please use this procedure only when the primary controller/gateway is missing or otherwise inoperable.
CO/ECO MODE
The thermostat has 2 main programs, CO “– comfort mode and ECO – economy mode. When Center (confirm) button is pushed for 2 seconds you switch between the 2 modes. You would” normally have 2 different set-points for the different modes.
CO ” “– mode: Is used for normal use. Example: 21″°C.
ECO ” “– mode: Is a setback mode that you can use if the thermostat is
installed in a room or a house that is rarely used.
The ECO-mode can also be activated by the pilot wire if this is connected.
Example: 18″°C. Some gateways also support switching between CO/ECO mode. In
most circumstances, the CO/ECO function can be regarded as” a home/away
function.
ERROR CODES
Err: ” Adding fails
Er2: ” Z-Wave error
Er3: ” Internal error
Er4: ” Floor sensor error
Er5: ” External sensor error
If you have chosen F sensor mode without having a floor” sensor connected, Er4 will be shown in the display. If you have” chosen A2, and there is no external sensors installed, Er5 will beshown in the display. If the Er1, Er2 or Er3 error codes are shown,
contact your local dealer or Thermo-Floor AS.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 1|
Lifeline. (Normally used by the Z-Wave” Controller) Sends:
– Thermostat Setpoint Reports
– Thermostat Mode Reports
---|---|---
2| 5| Send Multilevel Sensor Reports.
3| 5| Send Multilevel Sensor Reports.
4| 5| Send Binary Switch Set commands representing the status of the internal
relay.
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: Operation Mode
__
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Off |
---|---|
1 | Heating mode |
2 | Cooling mode (not implemented) |
11 | Energy saving heating mode |
Parameter 2: Sensor mode
__
Size: 1 Byte, Default Value: 0
SettingDescription
0 | F-mode, floor sensor mode. |
---|---|
3 | A2-mode, external room sensor mode |
4 | A2F-mode, external sensor with floor limitation |
Parameter 3: Floor sensor type
__
Size: 1 Byte, Default Value: 0
SettingDescription
0 | 10K NTC. |
---|---|
1 | 12K NTC |
2 | 15K NTC |
3 | 22K NTC |
4 | 33K NTC |
5 | 47K NTC |
Parameter 4: Temperature control hysteresis (DIFF I)
__
Size: 1 Byte, Default Value: 5
SettingDescription
3 – 30 | 0.3″°C – 3.0″°C |
---|
Parameter 5: Floor minimum temperature limit (FLo)
__
Size: 2 Byte, Default Value: 50
SettingDescription
50 – 400 | 5.0″°C – 40.0″°C |
---|
Parameter 6: Floor maximum temperature limit (FHi)
__
Size: 2 Byte, Default Value: 400
SettingDescription
50 – 400 | 5.0″°C – 40.0″°C |
---|
Parameter 7: Air (A2) minimum temperature limit (ALo)
__
Size: 2 Byte, Default Value: 50
SettingDescription
50 – 400 | 5.0″°C – 40.0″°C |
---|
Parameter 8: Air (A2) maximum temperature limit (AHi)
__
Size: 2 Byte, Default Value: 400
SettingDescription
50 – 400 | 5.0″°C – 40.0″°C |
---|
Parameter 9: Heating mode setpoint (CO)
__
Size: 2 Byte, Default Value: 210
SettingDescription
3 – 30 | 0.3″°C – 3.0C |
---|---|
50 – 400 | 5.0″°C – 40.0″°C |
Parameter 10: Energy saving mode setpoint (ECO)
__
Size: 2 Byte, Default Value: 180
SettingDescription
50 – 400 | 5.0″°C – 40.0″°C. |
---|
Parameter 11: Cooling setpoint (COOL)
__
Size: 2 Byte, Default Value: 210
SettingDescription
50 – 400 | 5.0″°C – 40.0″°C |
---|
Parameter 12: Floor sensor calibration
__
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 40 | 0 – 4.0″°C. |
---|---|
215 – 255 | -4,0 – -0,1″°C |
Parameter 13: External sensor calibration
__
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 40 | 0 – 4.0″°C. |
---|---|
215 – 255 | -4,0 – -0,1″°C |
Parameter 14: Temperature display
Selects which temperature is shown on the display.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Display setpoint temperature |
---|---|
1 | Display measured temperature |
Parameter 15: Button brightnessdimmed state
Configure the brightness of the buttons, in dimmed state.
Size: 1 Byte, Default Value: 50
SettingDescription
0 – 100 | in % |
---|
Parameter 16: Button brightnessactive state
Configure the brightness of the buttons, in active state.
Size: 1 Byte, Default Value: 100
SettingDescription
0 – 100 | in % |
---|
Parameter 17: Display brightnessdimmed state
Configure the brightness of the display, in dimmed state.
Size: 1 Byte, Default Value: 50
SettingDescription
0 – 100 | in % |
---|
Parameter 18: Display brightnessactive state
Configure the brightness of the display, in active state.
Size: 1 Byte, Default Value: 100
SettingDescription
0 – 100 | in % |
---|
Parameter 19: Temperature report interval
Time interval between consecutive temperature reports. Temperature reports
can be also sent as a result of polling.
Size: 2 Byte, Default Value: 60
SettingDescription
0 | Reporting of temperatures disabled |
---|---|
30 – 32767 | in seconds |
Parameter 20: Temperature report hysteresis
The temperature report will be sent if there is a difference in temperature
value from the previous value reported, defined in this parameter
(hysteresis). Temperature reports can be also sent as a result of polling.
Size: 1 Byte, Default Value: 10
SettingDescription
1 – 100 | 0.1″°C – 10.0″°C |
---|
Parameter 21: Meter report interval
Time interval between consecutive meter reports. Meter reports can be also
sent as a result of polling.
Size: 2 Byte, Default Value: 60
SettingDescription
0 | Reporting of metering values is disabled |
---|---|
30 – 32767 | in seconds |
Parameter 22: Meter report delta value
Delta value in kWh between consecutive meter reports. Meter reports can be
also sent as a result of polling.
Size: 1 Byte, Default Value: 10
SettingDescription
0 – 127 | A delta value of 0 – 12.7 kWh will result in a metering report. |
---|
Technical Data
Dimensions | 86,5 x 51,75 x 86,5 mm |
---|---|
Weight | 108 gr |
Hardware Platform | ZM5101 |
EAN | 7071236014850 |
IP Class | IP IP 20 |
Voltage | 230 V |
Load | 13 A |
Device Type | Thermostat – HVAC |
Network Operation | Always On Slave |
Z-Wave Version | 6.71.03 |
Certification ID | ZC10-18116305 |
Z-Wave Product Id | 0x019B.0x0003.0x0202 |
IP (Ingress Protection) Rated | ok |
Supported Meter Type | Electric Energy |
Thermostat Power Source | Mains powered (120V/240V) |
Neutral Wire Required | ok |
Supported Notification Types | Heat Alarm |
Thermostat Modes | AutoAwayCoolEnergy Save HeatHeat |
Color | White |
Thermostat HVAC Systems Supported | Cool OnlyHeat OnlySimple Relay |
Sensors | HeatTarget TemperatureVoltageWater Temperature |
Firmware Updatable | Updatable by Consumer by RF |
Frequency | Europe – 868,4 Mhz |
Maximum transmission power | 5 mW |
Supported Command Classes
- Association Grp Info
- Association V2
- Basic V2
- Switch Binary
- Configuration V3
- Device Reset Locally
- Firmware Update Md V4
- Manufacturer Specific V2
- Meter V3
- Multi Channel Association V3
- Multi Channel V4
- Powerlevel
- Security 2
- Security
- Sensor Multilevel V5
- Supervision
- Thermostat Mode V3
- Thermostat Setpoint V3
- Transport Service V2
- Version V3
- Zwaveplus Info V2
Controlled Command Classes
- Switch Binary
- Sensor Multilevel V5
- Thermostat Mode V3
- Thermostat Setpoint V3
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>