Danfoss KP 1 Pressure Switch Installation Guide
- September 4, 2024
- Danfoss
Table of Contents
Danfoss KP 1 Pressure Switch
Pressure switch
- KP 1, KP 1W, KP 1A, KP 2, KP 4, KP 5, KP 5A, KP 6W, KP 6B, KP 6S, KP 6AW, KP 6AB, KP 6AS, KP 7W, KP 7B, KP 7S
Refrigerants
- R22, R134a, R404A, R407A, R407C, R407F, R410A*) R422B, R422D, R448A, R449A, R452A, R507A, R513A, R717**)
- For a complete list of approved refrigerants, go to http://products.danfoss.com/all-products/
- only for KP 6W, KP 6B, KP 6S, KP 6AW, KP 6AB, KP 6AS
- only for KP 1A, KP 5A, KP 6AW, KP 6AB, KP6 AS
Ambient temperatures
Ambient temperatures / Mounting requirements
- Relative humidity RH: 30 – 98%
- Vibration resistance: 4 g (10 – 1000 Hz)
Test pressure (Ptest) PS/MWP
Ptestmax.:
- KP 1, KP 2: 20 bar pe (285 psig)
- KP 2: 12 bar pe (174 psig)
- KP 4: 24 bar pe (343 psig)
- KP 5, KP 7: 35 bar pe (510 psig)
- KP 6: 46,5 bar pe (675 psig)
Type | Regulation range | PS/MWP |
---|
KP 1
KP 1, reset
KP 1 W
KP 2
KP 2
KP 4
| -0.2 – 7.5 bar
-0.9 – 7.0 bar
0.5 – 3.0 bar
-0.2 – 5.0 bar
-0.2 – 3.5 bar
-0.2 – 7.5 bar
| 245 psig / 17 bar
245 psig / 17 bar
245 psig / 17 bar
245 psig / 17 bar
145 psig / 10 bar
312 psig / 21,5 bar
KP 5
KP 6
KP 7
| 8 – 32 bar
8 – 42 bar
8 – 32 bar
| 510 psig / 35 bar
675 psig / 46,5 bar
510 psig / 35 bar
Enclosure
- A: 8 – 32 UNC (M4)
- B: Enclosure IP30 (EN 60529)
- C: Enclosure IP44 (EN 60529)
Connections
Connections for KP 1A, KP 5A, KP 6AS
Mounting
CAUTION
Disconnect the power supply before wiring connections are made or serviced to
avoid possible electrical shock or damage to equipment. Do never touch live
parts with your fingers or with any tool.
- Short circuit protection: Fuse 16 Amp.
When used acc. to UL regulations
- Listed refrigeration controller 61B5
Voltage| FL LR
A A
|
Resist. load
|
Pilot duty
---|---|---|---
AC DC
240| —| 8| 48| 8 A|
3A
120| —| 16| 96| 16 A
—| 240| —| —| —| 12 W
- Use copper wire only Tightening torque 20 lb. in.
Manual trip function
Automatic reset
Manual reset
Type | Differential |
---|---|
KP 1, KP 1A | 0.7 bar (10 psi) |
KP 5, KP 5A | 3 bar (43 psi) |
KP 6B, KP 6S, KP 6AB, KP 6AS, KP 7B, KP 7S | 4 bar (58 psi) |
Adjustment
CAUTION
Only for selected A2L refrigerants: R455A, R454C, R1234yf, R1234yz, R1234ze
For a complete list of approved A2L refrigerants, go to
http://products.danfoss.com/all-products/
Electrical rating
- AC-3: 16 A / 250 V AC
- AC-15: 10 A / 250 V AC
Voltage| Current Range| Power factor (cos phi)|
Frequency
---|---|---|---
250V AC| ≤ 4.0 A| PF ≥ 0,400| 50Hz/60Hz
250V AC| > 4.0 to 6.0 A| PF ≥ 0,594| 50Hz/60Hz
250V AC| > 6.0 to 16,0 A| PF ≥ 0,780| 50Hz/60Hz
IMPORTANT NOTICE
Safety requirements
- KP pressure switches shall only be employed in the units/systems that comply with the requirements for charge limits and requirements for avoiding ignition sources of IEC 60335-2-24, IEC 60335-2-40, IEC 60335-2-89, ISO 5149, EN378-1 or equivalent.
- Applying the overload on the KPs must be prevented. If by any chance it was damaged, the system/unit shall be stopped and KP shall be replaced as necessary.
- Electrostatic discharge protection and Electrical leakage protection shall be surely implemented by grounding or other measures.
- Only trained personnel are authorized to handle flammable refrigerant systems and may do the installation, maintenance, and exchange of the switch by using appropriate tools.
- It is recommended to regularly check the function of the KP switch.
- KP pressure switches must be installed in an area with a low risk of mechanical damage.
- Corrosion protection of KP pressure switches must be taken into account when used in a corrosive environment.
- Cables shall not be in contact with sharp edges. The cables shall be connected with adequate stress relief to prevent pulling forces can be carried through the cable to the terminal.
- In the event of pressure pulsation in the system, where the switch is connected, these must be effectively dumped to prevent failure of the bellows. The cycle frequency of the KP switch shall be kept as low as possible.
- The KP switches shall not be installed in places where a high level of vibration is present.
Disclaimer
The user is responsible for ensuring that third parties also comply with this
Notice, e.g. in case the KP switches are supplied to third parties, and e.g.
that all installation guides are available with the KP switches during
installation. It is required that all conditions of this guide are met and
secured when using KP pressure switches.
Danfoss shall not be responsible for any kind of direct and indirect or
consequential damage or loss, including, but not limited to, loss of property,
production, loss of property, or human injury arising out of the explosion or
fire caused by the flammable nature of refrigerant.